Professional Documents
Culture Documents
QEZ3 220kV Typical Section For One of Projects in Qatar
QEZ3 220kV Typical Section For One of Projects in Qatar
QEZ3 220kV Typical Section For One of Projects in Qatar
1 Phase Spacing (450mm), Depth of cable top from finished surface level (1100mm) as per KAHRAMAA "HV and EHV Underground Cable Design" section 1.3.1.
450mm
150mm 150mm
450mm
150mm 150mm
450mm
1500mm
2600mm
1500mm
2600mm
1500mm
2600mm
1500mm
9700mm
Notes: The width of corridor is subject to change with change in no of circuits.
TYPICAL 220kV SECTION - WITH THREE 220kV CRICUITS FOR SINGLE SUPER SUBSATION
1 Phase Spacing (450mm), Depth of cable top from finished surface level (1100mm) as per KAHRAMAA "HV and EHV Underground Cable Design" section 1.3.1.
450mm
100mm 200mm
450mm
100mm 200mm
450mm
100mm 200mm
1500mm
1450mm
1500mm
1450mm
1500mm
1450mm
1500mm
9000mm Notes: The width of corridor is subject to change with change in no of circuits.