Transformer Fire Wall

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 1

RE-011-13-17

As per IEC standard 61936-1 2002 Recommendations for Separation distances

between outdoor Transformers and buildings , Table 16,


Transformer oil volume = 2800 liters Clearance to other transformers for this oil volume = 5 Meters (=16.4 Feet) Actual clearance between transformers = 14 Feet For the installation of explosion wall two things would have to be done 1. Rerouting of the Low voltage side cables for Transformer T1 as these cables are routed between the two transformers. 2. Transformer T1 will have to be relocated to ensure clearance as per IEC 61936-1 2002