Transformers
- Transform Electrical Power From One Voltage to
Another at the Same Frequency
- One Winding
==> Auto Transformer
Two Windings
==> 2 Winding Transformer
Three Windings ==> 3 Winding Transformer
- Winding
Primary Winding
Secondary Winding
Tertiary Winding
1

750 MVA 525/228 kV Transformer

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


2 66

350 MVA 13.8 kV / 230 kV Transformer () 3

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


3 66

Two Windings Transformer


5

Vector Groups
 Vector Voltage Comparison Between Primary and
Secondary
 Primary

Phase A Always at 0 ( 12 ) OClock

 Secondary Phase a

At Designated Group
Ex. At 1 , 5 , 11 OClock
6

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


4 66

Example 1

Transformer Vector Group Dy 1

Primary Connection Delta


Vector Phase A at 0 ( 12 ) OClock
Secondary Connection Wye
Vector Phase a at 1 OClock

Vector Group Connected of 3-phase Transformer

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


5 66

Transformer of Same Vector Group can be Connected For


Parallel Operation
In the case of Two Winding Transformers Commonly used
 Dy 1
 Dy 5
 Dy 7
 Dy 11
9

10

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


6 66

11

12

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


7 66

13

Type of Transformers
1)

Distribution Transformers
Rating : Up to
Voltage : Up to

2)

3150 kVA
36 kV

Power Transformers
Rating :

Over
Up to
Voltage : Up to

3.15 MVA
1500 MVA
1500 kV
14

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


8 66

Distribution Transformers
1) Oil Type
2) Dry Type / Cast Resin

Oil Type

15

Oil Type

16

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


9 66

Dry Type / Cast Resin

17

Power Transformers

18

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


10 66

850/1100 MVA Generator Transformer

19

20

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


11 66

21

Cooling
O

Oil

Air

Natural

Forced

1) ONAN Oil Natural Air Natural


( OA )
22

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


12 66

2)

ONAF
( FA )
30
ONAN

Oil Natural
Air Forced ( Fan )

40 /
ONAF 1

Natural 1st Set Fans

63 MVA
ONAF 2
2nd Set Fans
23

Ratings

VA rated
kVA , MVA
Primary voltages VP ( L-L Voltage )
Secondary voltages VS ( L-L Voltage )
Vector Group
% Impedance
Core Losses
Load Losses at Full Load P.F. 100%
24

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


13 66

Example 2
A 3-phase Transformer with the Rating of 50 MVA,
115 kV / 22 kV, Dy 1 , % Z = 10

1) In ( 115 kV ) =

50106
= 251 A
3115103

2) In ( 22 kV )

50106
322103

= 1312 A
25

3) If Connect to Infinite Bus


3 Phase Short Circuit Secondary Current is
Is ( 22 kV ) =

100 In
10

10 X 1.312 kA

13.12 kA
26

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


14 66

Tap Change
Adjust Secondary Voltage to Primary
Voltage Change , Loads

MR Motor Drive ED 100 S

Gas-Insulated on-Load tap changer


27

Selection of on-load tap changers from the MR produce range

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547

28


15 66

AT Nominal Tap
100 % / 100 %

AT Negative Tap
- 2.5 %
If 100 % Voltage on Primary
1
Secondary Voltage = 100% 0.975
= 102.56 %
Secondary Voltage Will Rise by 2.56 %
29

Distribution Sub-station
EEPW 0424 Electrical Power System Protection
9 Transformer Protections
2 2547

30


16 66

( Transformer Protection )

9.1





2

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


17 66

9.1 (...)





EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


18 66

9.2
( Nature and Effects of Transformer Faults )

( Source )
(Neutral Earthing Impedance)
( Leakage Reactance )
( Fault Voltages )

5

1. secondary Y ( Neutral )

2. Y (Neutral)
3. secondary
4. ( Phase-to-Phase Faults )
5. ( Interturn Faults )
6. ( Core Faults )
7. ( Tank Faults )
8.
9. ( Inrush Current )

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


19 66

Y ( Neutral )

Primary

Secondary



IP

R
IF

Primary

Secondary

IP
R
IF

PERCENTAGE OF RESPECTIVE MAXIMUM


SINGLE-PHASE EARTH FAULT CURRENT

100
90
80
70
60
50
40
30
20
10
0

FAULT CURRENT (IF)

PRIMARY CURRENT (IP)


10 20 30 40 50 60 70 80 90 100
DISTANCE OF FAULT FROM NEUTRAL
(percentage of winding)

9.1 Y (Neutral)

30% (Neutral) Primary
8

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


20 66

Y ( Neutral )
c
Va

a
kV a

Source Side

a
IF

b
c

No Source
Side

 ( Leakage Reactance )


 Fault

9

CURRENT (per unit)

20
15
FAULT CURRENT

10
5

PRIMARY CURRENT

10 20 30 40 50 60 70 80 90 100

DISTANCE OF FAULT FROM NEUTRAL


(percentage of winding)
9.2 Y ( Neutral )

10

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547

100
90
80
70
60
50
40
30
20
10
0

20
FAULT CURRENT (IF)

PRIMARY CURRENT (IP)


10 20 30 40 50 60 70 80 90 100
DISTANCE OF FAULT FROM NEUTRAL
(percentage of winding)

CURRENT (per unit)

PERCENTAGE OF RESPECTIVE MAXIMUM


SINGLE-PHASE EARTH FAULT CURRENT

21 66

15
FAULT CURRENT

10
5
0

PRIMARY CURRENT
10 20 30 40 50 60 70 80 90 100

DISTANCE OF FAULT FROM NEUTRAL


(percentage of winding)


Y

11

Delta
Delta
(Voltage to
Earth) 50%

Y

12

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


22 66

Delta ()

Secondary

IF
2 3

IP
IF =
2

V
3Z

IF

V
3

ET
ZE

Fault Current IF (p.u.)

Primary

ZE = 0

4
3

Z E = 1.0 p.u.

2
1

ZE = 3.0 p.u.
0

50

100

Distance x of Fault From End of Winding (%)


b) Typical fault current va lues

a) Approximate method for calculating fault current

... Transformer fault current for Delta winding

13

( Phase-to-Phase Faults )


1

14

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


23 66

( Interturn Faults )

( Stress )

15

( Interturn Faults )


( Impulse Voltage )
( dv/dt)

( Winding Partial
Flash-Over )
70-80%
16

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


24 66

( Interturn Faults )

Overhead Line

x
v (x)

100

10
FAULT CURRENT IN
SHORT CIRCUITED TURNS

80
60

8
6

PRIMARY INPUT
CURRENT

40

20

10

15

20

PRIMARY CURRENT (multiples of rated current)

FAULT CURRENT (multiples of rated current)

17

25

TURNS SHORT-CIRCUITED
(percentage of winding)

9.3 ( Interturn Faults )

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547

18


25 66

( Core Faults )

( Eddy- Current )

( Primary Current )




 ( Buchholz )
19

( Tank Faults )


 ( Overheating )

 ( Sludge )

20

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


26 66

( Tank Faults )

21

Bushing Flashovers
 (Bushing)
(Protection Zone)
 (Bushing Flashover)
(Surge)
 Ground Fault
 Transformer Protective
Schemes
22

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


27 66

23


1)
( Copper Loss )

2)

( IF pu. )2

24

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


28 66

Overload Region and Through Fault Region


25

9.1
Transformer Impedance
Fault Current
Permitted Fault Duration
(%)
(Multiple of Rating)
(Seconds)
4

25

20

16.6

14.2

Note: IEC 60076 (2000)


26

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


29 66

Table - : Transformer Failure Statistics 1975 - 1982

Failure Cause Classification


1. Winding Failures
2. Tap Changer Failures
3. Bushing Failures
4. Terminal Board Failures
5. Core Failures
6. Miscellaneous Failures
Total

Failure 1975-1982 (%)


51
19
9
6
2
13
100

Note: IEEE Power Engineering Society (1999)

27

3) ( Overvoltage )
2

1. Transient Surge Voltage


(Lightning) ( Switching )

- Rod Gap
- ( Lightning Arrester )
28

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


30 66

Protective Gap & Lightning Arrester

29

2. Power Frequency Overvoltage

= K f Bm A f N

E
Kf
Bm
A
f
N

RMS (V)
(From Factor)
(T)
(m2)
(Hz)
(turn)
30

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


31 66

2. Power Frequency Overvoltage ()


 ( Bm )

 Power Frequency Overvoltage

31

4)

(B)
 E/f
1.1

32

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


32 66

( Inrush Current )

(Magnetising Inrush)

Inrush Current
Transient Condition Fault
33

Transformer Magnetising Inrush

34

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


33 66

9.4
35

( .. )





 ( Residual Flux )

36

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


34 66

9.2

% ( Fundamental )

63.0

26.8

5.1

4.1

3.7

2.4
37

9.3 ( Transformer Protection )




- ( Overheating rotection )
- ( Overfluxing Protection )
- (Leakage to Frame Protection )
- ( Gas Detection Protection )
- ( Overcurrent Protection )
- ( Earth Fault Protection )
- ( Differential Protection )

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547

38


35 66

9.4 ((Overheating
Overheating Protection
Protection))


2

() IEC 60354

 6 0C
80 - 140 0C
39

Overheating Protection ( )
( Hot Spot Temperature ) 980C

Relative Rate of Using Life

100
10
1.0
0.1
H ot Sp ot Tem p.

80

90 100 110 120 130 140

oC

9.5

40

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


36 66

Overheating Protection ( )

Overheating
Thermal Image Technique

Alarm Trip
Contacts (Indicator)

Silistor ( Heat Sensitive Sillicon Resestor )


Pump
Cooling
41

9.5
( Overfluxing Protection )



 1 - 2 ()


X Bolts
X
42

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


37 66

43

9.5 Overfluxing Protection (..)

( 9.1 )
E/f

= K Ef

(9.1)


VT


E/f
E/f 1.1
44

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


38 66

9.5 Overfluxing Protection (..)



2 Contact
2-5 s Alarm
Contact

2 Trip
5-30 s


45

9.6
( Leakage to Frame Protection )

Tank Leakage
Relay
CT

OC


CT

OC

Check Relay

C.R.

T.L.R.

9.6

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547

46


39 66

9.7
( Gas Detection Protection )



H2 , CO , C2H4
Oil Conservator


47

( Gas Detection Protection )


1) ( Buchholz Relays )

(a)

(b)

9.7 a) Buchholz Relays


b) Buchholz Relays
48

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


40 66

( Buchholz Relays )

Buchholz Relay

49

( Gas Detection Protection )


2)
( Sudden Pressure Relays )

9.8
50

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


41 66

9.8 ( Overcurrent Protection)


1)



H.R.C.

2) ( Overcurrent Relays )

1.
2.
51

Winding of Transformer
CT

A
CT

B
CT

C
E/F

Overcurrent Relay

9.9
52

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


42 66

9.9 ( Earth Fault Protection )


1) ( Instantaneous )
Winding of Transformer
CT

A
CT

B
CT

C
R
Residual O/C Relay

9.10 53

2)
( Restricted Earth Fault Protection )
CT

A
Winding of Transformer

CT

N
Winding of Transformer

CT

I0
CT

64

ZE

High Impledance Relay


I

IEC 60617 Relay Sy mbol

9.11 ( Restricted Earth Fault Protection )

54

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


43 66

A & B Equipotential Points


R

Relay

CT 1

CT2

A
Relay

9.12 CT ( Neutral )



55

( Earth Fault Protection )


30 s
Earth Fault Relay 15-20 % 30 s 5

LVCB
HVCB Fault
IDMT Timer IDMT 2
15% 5 s LVCB
20% 8 s HVCB

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547

56


44 66

9.10
( Differential Protection )


- 5 MVA
- ( Circulating Current Systems )


1)
8

X
- Harmonics Restraint
57

( 2 5 )

58

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


45 66

2) CT
Primary Secondary
CT

22kV/6.6kV
10MVA

300/5

1500/5

R Diff. Relay

9.13 CT

59

3)
Y - Y 30
Differential Relay

 Delta ( ) CT Star ( Y )
 Star ( Y )

CT Delta ( )
60

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


46 66

P1
S1

P2

A2

S2

B2

A1

a1

a2 P2

b1

b2

c1

c2

P1
S2 S1

B1
C2
C1

Diff. Relay

9.14 CT
61

4) ( Tap Changer )
Tap

(Percentage Differential Relay )

62

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


47 66

9.1
Star - Delta 100 kV /10 kV
15% Setting
CT 1000/1

CT = (1000/1) x (10/100 ) = (100/1)


100 kV/10 kV IO/IR = 0%
+ 15 % IO
= 0.13 A
IR = 0.935 A
IO/IR = 14%
-15 % IO
= 0.18 A
IR = 1.09 A
IO/IR = 16.5%
63

9.1 (..)

 Setting
16.5 % ( )
Setting 30 %
 10 %
Setting 20 %
 20 %
Setting 40 %
 0.020 s 0.060 s
64

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


48 66

9.1 (..)
115kV/10kV
100/1

85kV/10kV

87A

1000/1 1000A

0.87A

1A

100/1 118A

1000/1 1000A

1.18A

1A

R
O

0.18A

0.13A

+15 %

-15 %

100 kV/10 kV
65

5) Interposing Current Transformers


CT Interposing CT
9.3 Turn Input (Primary) Output (Secondary) Interposing CT
Primary
Winding
Taps
1-2
2-3
3-4
4-5
5-6
X-7
7-8
8-9
S1-S2
S3-S4

Number of Turns
Transformer Rating
0.577-1.732/1 A 2.886-8.66/1 A
2.886-8.66/5 A
5
1
1
5
1
1
5
1
1
5
1
1
125
25
25
25
5
5
25
5
5
25
5
5
125
25
125
90
18
90

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547

66


49 66

Removable Jumper

S1

S2

S3

S4

Output to Relay

P1

P2

Input From
Line CTs

Interposing Current Transformer


67

9.2 1-phase Transformer Primary


Secondary 195A 780A
( Current Differential Relay )
CT Ratio Interposing CT

Primary IP = 195 A
CT Ratio Primary 200/5 A
Secondary IS = 780 A
CT Ratio Secondary 1000/5 A
195
ICT(P) = 5
200 = 4.875 A
ICT(S) = 5780 = 3.90 A
1000
CT 2
Interposing CT 3.90 A 4.875 A
68

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


50 66

Interposing CT
Secondary S1-S2 = 25 Turns
4.875
Primary Turns = 25 3.90
= 31.25
CT 31 Turns
31
Error = 31.25
31.25 100% = 0.8 %
IR
IR x 25 = 3.90 x 31
IR

Error

= 3.90 x (31/25) = 4.836 A


4.836 100%
= 4.875
4.875
= 0.8 %
69

Single phase
transformer

200/5A

195A

1000/5A

780A

4.875
A

X 6
7

S1

3.9A

S2

Differential relay

P1

P2

Interposing current
transformer

1 2
70

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


51 66

9.3
3-phase Transformer 50 MVA , 345kV Y / 34.5kV Short
Term Emergency 60 MVA
( Current Differential Relay ) CT Ratio
Interposing CT
Rated Current
In (HV) =
In (MV) =

60106
= 100.4 A
3 345103
60106
= 1004.1 A
3 34.5 103

MV Side CT Y-Connected
CT Ratio = 1000/5 A
5
Secondary CT 1004
1000 5 A
71

HV Side CT Delta Connected


CT 200/5 A
100.4 = 2.51 A
Secondary Current CT = 5200
Line Current CT = 3 x 2.51 = 4.35 A ( )
345 kV
34.5 kV
4.35 A
5.0 A
Mismatch
Auxiliary CT Interposing CT Autotransformer Y-Connected
Main CT 34.5 kV
CT Turn Ratio = 5.0/4.35 = 1 .15
tap +15 % Autotransformer 4.35 A
72

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


52 66

CT 1000/5A

TR.

CT 200/5A

b
B
C

c
2.6+j3.5=4.36

2.6+j3.5=4.36

1.7-j4
-4.3+j0.5

3 3
73

9.4
3-phase Transformer 30 MVA, 11 kV / 66 kV Y

(Current Differential Relay) CT Ratio (Main CT)


Interposing CT

11 kV

30106
= 1575 A
311103
Main CT 1600/1 A Y-Connected

In ( 11 kV ) =

Secondary CT = 1575/1600 = 0.984 A

66 kV

30106
366103 = 262.5 A
Main CT 300/1 A Y-Connected
74

In ( 66 kV ) =

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


53 66

Secondary CT = 262.5/300 = 0.875 A


Ratio Interposing CT = 0.875/0.984 = 0.889

S1-S2 S3-S4 = 215 Turns Relay


0.984 = 140 Turns
Input Taps = 215
30.875
Tap 2-6: = 5 + 5 + 5 + 125 = 140 Turns

CTs Y-Connected 66 kV ( Transformer
Y-Connected ) Interposing CT Main CT
Y -
75

Ex. 9.4 ( )

TR. 30MVA 11/66kV

1600/1A

300/1A

0.875A
0.984A
D.R.
Ph. A

0.984A

0.568A

D.R.
Ph. B
D.R.
Ph. C

215
S1

S2 S3

S4

X 6

P1

140
N
A

P2

To
differential
relay

S1

S2 S3

S4

X 6

b
S1

S2 S3

S4

P1

To line
CT's

P2
X 6

P1

P2

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547

76


54 66

( 6 ) ( Three Windings Transformer )


Source
CT

CT

OP

Source
CT

B
B

CT

B
OP

( ) , ( )

9.15 77

9.5
3-phase Three Windings Transformer 400 MVA , 500kV Y /
13.45kV /138kV Y 3
( Current
Differential Relay ) 3 CT Ratio
Interposing CT
500/138kV
400MVA

300MVA

13.45kV

100MVA

3 3

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547

78


55 66

13.45 kV
Q I n =

100106
= 4293 A
313.45103

 CT 5000/5 A
5
secondary CT = 4293
5000 = 4.293 A
External Fault
CT Output Circuit Relate Primary I/P MVA Rated Current
Reted Current In(400MVA) =

400 MVA = 17170 A


313.45 kV
13.45 kV , Main CT Y Interposing CT
Y-Y
79

9.5 ()

O/P D.R. S1-S2 S3-S4


= 43/phase

 Turn Tap Error


5 43 = 12.52 = 12 Turns
I/P Turns 5 A = 17.17
17.17 = 4.792 A
Output Winding Current Is = 1243
4.8 A = Rated Current
Matched 500 kV 138 kV
Interposing CTs
80

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


56 66

9.5 ()

Matched 500 kV 138 kV Interposing CTs


S1

S2

S3

S4

5 3

S3

S4

5 3

To relay

B
S

S3

S4

To
13.45kV
M ain CT's

5 3

13.45 kV

Main CT

5000/5 A

12 T
Interposing CT

17170 A
s1
s2
s3
s4

43 T

To D .R.

81

CT 13.45 kV

500 kV
In

400 MVA = 462 A


3 500 kV
CT 500/5 A Y
Secondary CT = 4625 = 4.62 A
500
Interposing CT - Y
= 4.62/2.77
Ratio Interposing CT = 4.62
4.8 3
Interposing Windings
2.7743 = 25.78 = 26 Turns
4.62
Error = 26 25.78 100% = 0.853%
25.78
=

82

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


57 66

Interposing CT Tap 4-6


S1

S 2 S3

S4

a
S1

To relay

X 6 4
A

P2
S2 S 3

S4

X 6 4

P1
B

P2
S1

S2 S 3

S4

X 6 4

To 50 0kV
line C T's

P1
C

P2
P1

CT 500kV

83

138 kV
400MVA
3 138kV = 1673 A
CT 1250/5 A Y
5
Secondary CT = 1673
1250 = 6.69 A
6.69 = 6.69/2.77
Ratio Interposing CT -Y = 4.8
3

In

43
Interposing CT Input Turn = 2.77
6.69 = 17.8 = 18 Turns
17.8 100% = 1.12 %
Error = 1817.8
84

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


58 66

S1

S2

S3

S4

52
A

To relay

S1

S2

S3

S4

52
B

b
S1

S2

S3

S4

To 138kV
line CT's

52
C

CT 138 kV

85

Transformer Full Load


500 kV Side 400 MVA

In =

400MVA = 462 A
3 500kV

5
Secondary CT = 462
500 = 4.62 A
Interposing CT 4.62
2.77 Y -

26 3 = 4.84 A
Relay = 4.6243
86

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


59 66

138 kV 300 MVA


In

300MVA
3 138kV

= 1255 A

ICT ( sec )

12555
1250

= 5.02 A

Interposing CT 2.77
7.0

Relay =

3 5.0218 = 3.64 A
43
87

13.45 kV 100 MVA


In

100MVA
3 13.45kV = 4293 A

ICT ( sec )

42935
5000

= 4.293 A

12 = 1.19 A
Relay = 4.293
43
500 kV

4.84

138 kV
3.64 + 1.19

13.45 kV
4.83

O.K.
88

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


60 66

400M V A / 100M V A / 300M VA


5 0 0 /5 A

5 00 k V

1 3 .4 5 k V

1 3 8 kV

1 2 5 0/ 5 A

21
23
25

21
23
25
4 . 6 2 / 2. 7 7 A

2 . 77 / 7 . 0 A
21
23
25

26 / 43

43 / 18

5 00 0 /5 A

1 7 . 17 / 4 . 8 A
12 / 4 3

89

3 3

9.11

Source

49

51

51N

52

9.16

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547

90


61 66

 Primary Fuse
 Secondary
1. Time Delay Overcurrent Relay ( 51 )
2. Residually Connected Ground Relay ( 51N )
3. Transformer Thermal Relay ( 49 )

91

Utilyty Source 22 kV
52
50
51

50N
51N

49
500 kVA
22 kV / 6.6 kV
50
51

R ES

50N
51N

5 1G

52
6.6 kV

9.17

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547

92


62 66

 Primary Circuit Breaker ( 52 )


 Secondary
1. Instantaneous / Time Delay Overcurrent Relay
( 50, 51 )
2. Residually Connected Ground Relay ( 50N , 51N )
3. Transformer Thermal Relay ( 49 )
4. Neutral Ground Relay ( 51G )
93

 Primary Circuit Breaker ( 52 )


 Secondary
1. Instantaneous / Time Delay Overcurrent Relay ( 50, 51 )
2. Residually Connected Ground Relay ( 50N , 51N )
3. Transformer Thermal Relay ( 49 )
4. Neutral Ground Relay ( 51G )
5. Pressure Switch ( 63 )
6. Differential Protective Relay ( 87T )
94

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


63 66

Utilyty Source 115 kV


52
50
51

50N
51N

49
5000 kVA
115 kV / 22 kV
Surge Arrester
(Optional)

87T

63
R ES

50
51

51G

50N
51N

52
22 kV

9.18

95

Transformer Multifunction Relay

96

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


64 66

97

Single Line Diagram

98

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


65 66

99

100

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547


66 66

9
1.
?
2. (Differential Protection)
?
3.

102

4. 30 MVA , 11 kV/132 kV Delta-Wye

CT Primary Secondary
Transformer Ratio Interposing CT
Percentage Differential Relay

29 2548 .
103

EEPW 0424 Electrical Power System Protection


9 Transformer Protections
2 2547