BBC type TRFKdwz, 159 MVA (1-phase), 12/144,15/rot3kV, Connected D/y, Uk 12,3%, Vintage 1960
G2-2
G2-3
6,9354
Excitation test
The test is made at V-U. No remarks. G2-1 G2-1 G2-3 973,8 Watt 974,7 978,6
SFRA
3 measures on 3 transformers 9 traces all together What more could You ask for ?
HV HV [open]
LV LV [open]
HV HV [shorted]
Winding Resistance
Transformer G2-1 Connection Measured @ 16 U-V 180,2 mOhm v1-u1 5,15 v2-u2 4,29 v1-u2 v2-u1 5,63 4,29 Calculated @ 20C 183,0 mOhm 5,23 4,37 5,72 4,36 FAT @20 186,5mOhm 4,34 4,34
Transformer G2-2 Connection Measured @ 16 _______ U-V 180,7 182,2 v1-u1 4,29 4,33 v2-u2 4,28 4,31
Transformer G2-3 Connection Measured @ 16 ________ But what about the G2-3 U-V 180,2 183,1 then then? v1-u1 4,27 4,34 No signs at all for a fault v2-u2 4,29 4,36
there
Touch-up paint with lower emissivity factor fooled the thermographer to believe there were hot-spots on G2-3.