Professional Documents
Culture Documents
Circuit Breaker Selection
Circuit Breaker Selection
5)
AC Circuit Breakers
A circuit breaker is a mechanical switch capable of interrupting fault currents and of reclosing. Classified as low voltage circuit breakers (< 1500 V) OR power circuit breakers (>1500 V) Different types depending on the medium in which the arc is elongated (air, oil, SF6, vacuum..)
AC Circuit Breakers
Subtransient Period
Transient Period
Subtranient period
XdG
Xdsm
Xdsm
Transient period
XdG
Application Guide for AC High Voltage Circuit Breakers rated on a Symmetrical Current Basis
Application Guide for AC High Voltage Circuit Breakers rated on a Symmetrical Current Basis
Voltage ratings
Rated maximum voltage: Designated the maximum rms line-line operating voltage. Rated low frequency withstand voltage: The maximum rms line to line voltage the circuit breaker can withstand without insulation damage. Rated impulse withstand voltage: The maximum crest voltage of a voltage pulse with standard rise and delay times that the breaker insulation can withstand.
Voltage ratings
Rated voltage range factor K: The range of voltage for which the symmetrical interrupting capability times the operating voltage is constant.
Current ratings
Rated continuous current: The maximum rms current that the breaker can carry continuously while closed without heating. Rated short circuit current: The maximum rms symmetrical current that the breaker can safely interrupt at rated maximum voltage. Rated momentary current: The maximum rms asymmetrical current that the breaker can withstand while closed without damage.
Current ratings
Rated interrupting time: The time in cycles from the instant the trip coil is energized to the instant the fault current is cleared. Rated interrupting MVA: For a three phase circuit breaker, this is 3 times the rated maximum voltage in kV times the rated short circuit current in kA.
For any operating voltage V between Vmin and Vmax the symmetrical interrupting current is
(72.5)(19)
Example 1
The calculated symmetrical fault is 17 kA at a three phase bus where the operating voltage voltage is 64 kV. The X/R ratio at the is unknown. Select a circuit breaker from the given tables for this bus.
Example 1
Consider the next highest available standard voltage from the table. Therefore consider a 69 kV class breaker. At 64 kV, the symmetrical interrupting capability (72.5)(19) of the breaker is = 21.5 kA
64
If X/R is unknown, the calculated fault current should not be more than 80% of the breakers interrupting capability. We need to do this check
Example 1
Calculated fault current = 17 kA Breakers interrupting capability = 21.5 kA
17 Therefore 21.5
So the calculated fault current is not more than 80% of the breakers interrupting capability therefore the chosen 69 kV class breaker is suitable for the application.
Example 2
A 69 kV circuit breaker has a voltage range factor K of 1.21, a continuous current rating of 1.2 kA and a short circuit current rating of 19 kA at a maximum rated voltage of 72.5 kV. Determine the maximum symmetrical interrupting capability of the breaker and determine the voltage range at which the symmetrical interrupting current is lower than the maximum symmetrical interrupting current
Example 2
Maximum symmetrical interrupting capability = K x rated short circuit current = 1.21(19) = 23 kA
Vmin =
( )
72.5 = 1.21
60 kV.
Therefore the voltage range at which the symmetrical interrupting current is lower than the maximum symmetrical interrupting current is 60 kV 72.5 kV
Tutorial Exercises
Tutorial Exercises
Tutorial Exercises