Professional Documents
Culture Documents
Enatel Limited - Product Catalogue 2010 v1.0
Enatel Limited - Product Catalogue 2010 v1.0
power design
Offering a range of solutions from small standalone systems for applications like access nodes to medium systems for radio base stations for mobile networks and larger systems for central ofce power applications. Our knowledge and experience of the global marketplace, along with our talented team, enable us to create power supply solutions that meet each customers unique specications no matter what volume they require.
We not only create our own suite of products, we also offer a comprehensive contract manufacturing service. Our highly exible environment allows us to specialize in small to medium volume as well as highly repetitive production.
MONITORING................................................................................................ 45
SM36 SUPERVISORY MODULE....................................................................... 46 SM35 SUPERVISORY MODULE....................................................................... 47 SM32 SUPERVISORY MODULE....................................................................... 48 SM31 SUPERVISORY MODULE....................................................................... 49 SM11 SUPERVISORY MODULE....................................................................... 50 FAN CONTROLLER BOARD............................................................................. 50 BATTERY CONDITION MONITOR.................................................................... 51 AC MAINS MONITOR. ....................................................................................... 51
MODULAR RECTIFIERS.............................................................................. 24
RM3048 3.0kW 48V DC MODULAR RECTIFIER. .............................................. 25 RM3048/24 3.0kW 48V DC / 1.7kW 24V DC MODULAR RECTIFIER. .............. 26 RM3060/48 3.0kW 60/48V DC MODULAR RECTIFIER.................................... 27 RM2324 2.3kW 24V DC MODULAR RECTIFIER. .............................................. 28 RM2048XP 2.0KW 48V DC MODULAR RECTIFIER. ......................................... 29 RM2048/24 2.0kW 48V DC / 1.0kW 24V DC MODULAR RECTIFIER. .............. 30 RM1860/48 1.8kW 60/48V DC MODULAR RECTIFIER.................................... 31 RM1048 1.0kW 48V DC MODULAR RECTIFIER. .............................................. 32 RM848 800W 48V DC MODULAR RECTIFIER. ................................................. 33
INDUSTRIAL SOLUTIONS.......................................................................... 56
2U ULTRA COMPACT SYSTEM 3.0 - 6.0kW 110V DC.................................... 57 WALL MOUNT BATTERY CHARGER 3.0kW 110V DC..................................... 58 RM30110 3.0KW 110V DC MODULAR RECTIFIER.......................................... 59 SM34 SUPERVISORY MODULE....................................................................... 60 SM33 SUPERVISORY MODULE....................................................................... 61
ENATEL | 2010 PRODUCT CATALOGUE | 3
DC Output Nominal Voltage: Rated System Output Power: Polarity: DC Distribution: Load: Battery: 2x 10A, 2x 20A load circuit breakers. 2x 30A battery circuit breakers. Electronic fail detection on both load and battery breakers.
Supervisory Module
-48V 2400W max. (50A @ -48V; 44.4A @ -54.0V) Positive earth. (negative earth available to special order).
48 2.4
RM848 RM848 RM848
kW
SM36
6mm push-in spring cage. 55A power-pole plug-in connectors. 50A battery LVD (magnetically latching) fitted as standard.
Mechanical Dimensions, W,H,D: Weight: 482.6mm (standard 19 module), also fits ETSI 515mm mounting cabinet, 44.45mm (1U, 1.75), 285mm (11.6) 5kg (excluding rectifier modules)
Shipping Dimensions, W,H,D: 540mm, 95mm, 400mm Weight: 6kg (excluding rectifier modules)
Various monitoring options are available via the Enatel SM35/36 series of control & supervisory modules. Standard features include full temperature compensation, automated and manual battery testing/ equalisation, 6x general purpose inputs and 6x voltage-free relay alarm outputs. For further details, refer to the SM35/36 series of brochures.
Accessories ACA-BC08P2: 2m, 8mm battery cable kit. (other lengths available to special order)
Actual part numbers will vary with configuration. Micro compact system, 2x 800W 48V rectifiers, 6x load 2x battery MCBs, front termination, SM35 supervisory module. Micro compact system, 2x 800W 48V rectifiers, 6x load 2x battery MCBs, front termination, SM36 supervisory module. Micro compact system, 3x 800W 48V rectifiers, 4x load 2x battery MCBs, front termination, SM35 supervisory module. Micro compact system, 3 x 800W 48V rectifiers, 4x load 2x battery MCBs, front termination, SM36 supervisory module.
ENATEL | 2010 PRODUCT CATALOGUE |
48 4.0
nominal output voltage.
Single phase. (refer to RM series brochures for full details) 45-66Hz >0.99 (full load) Single phase, 10mm L, N, E tunnel terminals.
DC Output Nominal Voltage: Rated System Output Power: Polarity: DC Distribution: Load: 1x 63A load circuit breaker. (1x 50A load circuit breaker. Low power option.) 1x 63A battery circuit breaker. (1x 50A battery circuit breaker. Low power option.) Electronic fail detection on both load and battery breakers. Tunnel terminals, 10mm. 80A battery LVD fitted as standard. (50A battery LVD fitted as standard. Low power option.) -48V (+24V available to special order) 4000W @ -48V (2000W @ -48V. Low power option.) Positive earth. (negative earth available to special order)
kW
Supervisory Module
Battery:
SM32
Load
Battery
compact
ULTRA
Mechanical Dimensions, W, H, D: Weight: 482.6mm (standard 19 module), 44.45mm (1U, 1), 350mm (13) 5kg (excluding rectifier modules)
Shipping Dimensions, W, H, D: 540mm, 95mm, 400mm Weight: 6kg (excluding rectifier modules)
Various monitoring options are available via the Enatel SM30 series of control & supervisory modules. Standard features include full temperature compensation, automated and manual battery testing/equalisation and three voltage-free relay alarm outputs. Options include extension I/O PCBs that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free relay outputs. For further details, refer to the SM30 series of brochures.
Part Numbers: PSC04020110-000: PSC04020111-000: PSC04020120-000: PSC04020121-000: PSC02020110-000: PSC02020111-000: PSC02020120-000: PSC02020121-000:
| ENATEL | 2010 PRODUCT CATALOGUE
Actual part numbers will vary with configuration. 1U Ultra Compact System including standard SM31 supervisory module. 1U Ultra Compact System including standard SM31 supervisory module and I/O expansion card. 1U Ultra Compact System including standard SM32 supervisory module. 1U Ultra Compact System including standard SM32 supervisory module and I/O expansion card. Low Power 1U Ultra Compact System including standard SM31 supervisory module. Low Power 1U Ultra Compact System including standard SM31 supervisory module and I/O expansion card. Low Power 1U Ultra Compact System including standard SM32 supervisory module. Low Power 1U Ultra Compact System including standard SM32 supervisory module and I/O expansion card.
DC Output Nominal Voltage: Rated System Output Power: Polarity: DC Distribution: Load: 3x 20A load circuit breakers. (3x 10A load circuit breakers. Low power option.) 2x 30A battery circuit breakers. (2x 20A battery circuit breakers. Low power option.) Electronic fail detection on both load and battery breakers.
Supervisory Module
-48V, -60V (+24V available to special order) 4000W @ -48V (2000W @ -48V. Low power option.) Positive earth. (negative earth available to special order)
Battery:
48 4.0
SM32
kW
compact
ULTRA
Tunnel terminals, 6mm Tunnel terminals, 6mm 80A battery LVD fitted as standard. (50A battery LVD fitted as standard. Low power option.)
Mechanical Dimensions, W, H, D: Weight: 482.6mm (standard 19 module), 44.45mm (1U, 1), 350mm (13) 5kg (excluding rectifier modules)
Shipping Dimensions, W, H, D: 540mm, 95mm, 400mm Weight: 6kg (excluding rectifier modules)
Various monitoring options are available via the Enatel SM30 series of control & supervisory modules. Standard features include full temperature compensation, automated and manual battery testing/equalisation and three voltage-free relay alarm outputs. Options include extension I/O PCBs that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free relay outputs. For further details, refer to the SM30 series of brochures.
Part Numbers: PSC04020110-100: PSC04020111-100: PSC04020120-100: PSC04020121-100: PSC02020110-100: PSC02020111-100: PSC02020120-100: PSC02020121-100:
Actual part numbers will vary with congifuration. 1U Ultra Compact System including standard SM31 supervisory module. 1U Ultra Compact System including standard SM31 supervisory module and I/O expansion card. 1U Ultra Compact System including standard SM32 supervisory module. 1U Ultra Compact System including standard SM32 supervisory module and I/O expansion card. Low Power 1U Ultra Compact System including standard SM31 supervisory module. Low Power 1U Ultra Compact System including standard SM31 supervisory module and I/O expansion card. Low Power 1U Ultra Compact System including standard SM32 supervisory module. Low Power 1U Ultra Compact System including standard SM32 supervisory module and I/O expansion card.
ENATEL | 2010 PRODUCT CATALOGUE |
48 6.0
nominal output voltage.
AC Input: Frequency Range: Power Factor: Termination: DC Output Nominal Voltage: Rated System Output Power: Polarity: DC Distribution: Load: Battery:
Three phase or single phase. (refer to RM series brochures for full details) 45-66Hz >0.99 (full load) Three phase, 6mm L1, L2, L3, N, E tunnel terminals. (Single phase by linking L1, L2, L3 terminals)
-48V, -60V (+24V available to special order) 6000W @ -48V (3000W @ -48V. Low power option) Positive earth. (negative earth available to special order) 2x 10A, 2x 20A, 2x 32A load circuit breakers. (2x 6A, 2x 10A, 2x 20A load circuit breakers. Low power option.) 2x 63A battery circuit breakers. (2x 63A battery circuit breakers. Low power option.) Electronic fail detection on both load and battery breakers. Tunnel terminals, 16mm (rear connected) Tunnel terminals, 35mm (rear connected) 125A battery LVD fitted as standard. (magnetically latching contactor) (80A battery LVD fitted as standard. Low power option)
kW
1 Load 2
Supervisory Module
3 Load 4
SM32
5 Load 6
1 Battery 2
compact
ULTRA
Mechanical Dimensions, W, H, D: Weight: Weight: Monitoring & Control: Part Numbers: PSC06030210-000: PSC06030211-000: PSC06030220-000: PSC06030221-000: PSC03030210-000: PSC03030211-000: PSC03030220-000: PSC03030221-000:
| ENATEL | 2010 PRODUCT CATALOGUE
482.6mm (standard 19 module), 89mm (2U, 3), 350mm (13) (390mm with cable strain relief) 9kg (excluding rectifier modules) 10.5kg (excluding rectifier modules) Various monitoring options are available via the Enatel SM30 series of control & supervisory modules. Standard features include full temperature compensation, automated and manual battery testing/equalisation and three voltage-free relay alarm outputs. Options include extension I/O PCBs that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free relay outputs. For further details, refer to the SM30 series of brochures. Actual part numbers will vary with congifuration. 2U Ultra Compact System including standard SM31 supervisory module. 2U Ultra Compact System including standard SM31 supervisory module and I/O expansion card. 2U Ultra Compact System including standard SM32 supervisory module. 2U Ultra Compact System including standard SM32 supervisory module and I/O expansion card. Low Power 2U Ultra Compact System including standard SM31 supervisory module. Low Power 2U Ultra Compact System including standard SM31 supervisory module and I/O expansion card. Low Power 2U Ultra Compact System including standard SM32 supervisory module. Low Power 2U Ultra Compact System including standard SM32 supervisory module and I/O expansion card.
Three phase or single phase. (refer to RM series brochures for full details) 45-66Hz >0.99 (full load) Three phase, 6mm L1, L2, L3, N, E tunnel terminals. (Single phase by linking L1, L2, L3 terminals)
-48V, -60V (+24V available to special order) 6000W @ -48V (3000W @ -48V. Low power option.) Positive earth. (negative earth available to special order)
48 6.0
1 Battery 2
SM32
kW
compact
ULTRA
10A, 6mm tunnel terminals. 20A & 30A, 10mm tunnel terminals. (6A & 10A, 6mm tunnel terminals. 20A, 10mm tunnel terminals. Low power option.) 100A, 35mm tunnel terminals. (50A, 16mm tunnel terminals. Low power option.) 125A battery LVD fitted as standard. (80A battery LVD fitted as standard. Low power option.)
Mechanical Dimensions, W, H, D: Weight: Weight: Monitoring & Control: Part Numbers: PSC06030210-100: PSC06030211-100: PSC06030220-100: PSC06030221-100: PSC03030210-100: PSC03030211-100: PSC03030220-100: PSC03030221-100: 482.6mm (standard 19 module), 89mm (2U, 3), 350mm (13) (390mm with cable strain relief) 9kg (excluding rectifier modules) 10.5kg (excluding rectifier modules) Various monitoring options are available via the Enatel SM30 series of control & supervisory modules. Standard features include full temperature compensation, automated and manual battery testing/equalisation and three voltage-free relay alarm outputs. Options include extension I/O PCBs that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free relay outputs. For further details, refer to the SM30 series of brochures. Actual part numbers will vary with congifuration. 2U Ultra Compact System including standard SM31 supervisory module. 2U Ultra Compact System including standard SM31 supervisory module and I/O expansion card. 2U Ultra Compact System including standard SM32 supervisory module. 2U Ultra Compact System including standard SM32 supervisory module and I/O expansion card. Low Power 2U Ultra Compact System including standard SM31 supervisory module. Low Power 2U Ultra Compact System including standard SM31 supervisory module and I/O expansion card. Low Power 2U Ultra Compact System including standard SM32 supervisory module. Low Power 2U Ultra Compact System including standard SM32 supervisory module and I/O expansion card.
ENATEL | 2010 PRODUCT CATALOGUE |
48 8.0
nominal output voltage.
Three phase or single phase. (refer to RM series brochures for full details) 45-66Hz >0.99 (full load) Three phase, 10mm L1, L2, L3, N tunnel terminals, 16mm E tunnel terminal. (Single phase by linking L1, L2, L3 terminals)
DC Output Nominal Voltage: Rated System Output Power: Polarity: DC Distribution: -48V, -60V (+24V available to special order) 8000W @ -48V Positive earth. (negative earth available to special order)
kW
Supervisory Module
SM32
1 Load 2
3 Load 4
1 Battery 2
compact
ULTRA
Load: Battery:
2x 20A, 2x 63A load circuit breakers. 2x 100A battery circuit breakers. Electronic fail detection for load breakers. Auxiliaries for battery MCB fail detection.
Tunnel terminals, 16mm (rear connected) Tunnel terminals, 35mm (rear connected) 150A battery LVD fitted as standard. (magnetically latching contactor)
Mechanical Dimensions, W, H, D: Weight: 482.6mm (standard 19 module), 89mm (2U, 3), 350mm (13) (390mm with cable strain relief) 9kg (excluding rectifier modules)
Shipping Dimensions, W, H, D: 483mm, 88.9mm, 350mm Weight: 10.5kg (excluding rectifier modules)
Various monitoring options are available via the Enatel SM30 series of control & supervisory modules. Standard features include full temperature compensation, automated and manual battery testing/equalisation and three voltage-free relay alarm outputs. Options include extension I/O PCBs that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free relay outputs. For further details, refer to the SM30 series of brochures.
Actual part numbers will vary with congifuration. 2U Ultra Compact System including standard SM31 supervisory module. 2U Ultra Compact System including standard SM31 supervisory module and I/O expansion card. 2U Ultra Compact System including standard SM32 supervisory module. 2U Ultra Compact System including standard SM32 supervisory module and I/O expansion card.
DC Output Nominal Voltage: Rated System Output Power: Polarity: DC Distribution: -48V, -60V (+24V available to special order) 6000W @ -48V Positive earth. (negative earth available to special order)
48 6.0
3U Compact System 1 2 3 5 6 7 8 9 10 11 12 1 Battery 2 Load Load 4
Supervisory Module
kW
Load: Battery:
4x 10A, 4x 20A, 4x 32A load circuit breakers. 2x 100A battery circuit breakers.
SM32
16mm tunnel terminals. 35mm tunnel terminals. 125A battery LVD fitted as standard.
Mechanical Dimensions, W, H, D: Weight: 482.6mm (standard 19 module), 133.3mm (3U, 5), 350mm (13) (390mm with cable strain relief) 11kg (excluding rectifier modules)
Shipping Dimensions, W, H, D: 540mm, 200mm, 435mm Weight: 14kg (excluding rectifier modules)
Various monitoring options are available via the Enatel SM30 series of control & supervisory modules. Standard features include full temperature compensation, automated and manual battery testing/equalisation and three voltage-free relay alarm outputs. Options include extension I/O PCBs that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free relay outputs. For further details, refer to the SM30 series of brochures.
Actual part numbers will vary with congifuration. 3U Compact System including standard SM31 supervisory module. 3U Compact System including standard SM31 supervisory module and I/O expansion card. 3U Compact System including standard SM32 supervisory module. 3U Compact System including standard SM32 supervisory module and I/O expansion card.
ENATEL | 2010 PRODUCT CATALOGUE | 11
48 6.0
nominal output voltage.
Three phase or single phase. (refer to RM series brochures for full details) 45-66Hz >0.99 (full load) Three phase L1, L2, L3, N, E 6mm2 terminal blocks. (Single phase by linking line terminals) 20A circuit breaker provided per rectifier.
DC Output
kW
-48V, -60V (+24V available to special order) 6000W @ -48V Positive earth. (negative earth available to special order)
Rectifiers
1 2 3 1 2 3
Supervisory Module
4 5 6 7 Load
10 11 12 13 14 15 Load
3U Compact System
AC Input
Battery
Load: Battery:
5x 10A, 4x 20A, 4x 32A load circuit breakers. 2x 100A battery circuit breakers. Electronic fail detection on both load and battery breakers.
Load
8 9
SM32
10A, 6mm tunnel terminals. 32A, 10mm tunnel terminals. 50A, 16mm tunnel terminals. 35mm tunnel terminals. 125A battery LVD fitted as standard.
Battery:
Mechanical Dimensions, W, H, D: Weight: 482.6mm (standard 19 module), 133.3mm (3U, 5), 350mm (13) (390mm with cable strain relief) 11.5kg (excluding rectifier modules)
Shipping Dimensions, W, H, D: 540mm, 200mm, 435mm Weight: 14.5kg (excluding rectifier modules)
Various monitoring options are available via the Enatel SM30 series of control & supervisory modules. Standard features include full temperature compensation, automated and manual battery testing/equalisation and three voltage-free relay alarm outputs. Options include extension I/O PCBs that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free relay outputs. For further details, refer to the SM30 series of brochures.
Actual part numbers will vary with congifuration. 3U Compact System including standard SM31 supervisory module. 3U Compact System including standard SM31 supervisory module and I/O expansion card. 3U Compact System including standard SM32 supervisory module. 3U Compact System including standard SM32 supervisory module and I/O expansion card.
DC Output Nominal Voltage: Rated System Output Power: Polarity: DC Distribution: Load: Battery: 2x 10A, 2x 20A, 4x 32A load circuit breakers. 2x 100A battery circuit breakers. Electronic fail detection on both load and battery breakers.
AC Input
-48V, -60V (+24V available to special order) 8000W @ -48V Positive earth. (negative earth available to special order)
Supervisory Module
48 8.0
SM32
kW
Load
16mm tunnel terminals. 35mm tunnel terminals. 150A battery LVD fitted as standard.
Mechanical Dimensions, W, H, D: Weight: 482.6mm (standard 19 module), 133.3mm (3U, 5), 350mm (13) (390mm with cable strain relief) 11kg (excluding rectifier modules)
Shipping Dimensions, W, H, D: 483mm, 133.35mm, 350mm Weight: 11.5kg (excluding rectifier modules)
Various monitoring options are available via the Enatel SM30 series of control & supervisory modules. Standard features include full temperature compensation, automated and manual battery testing/equalisation and three voltage-free relay alarm outputs. Options include extension I/O PCBs that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free relay outputs. For further details, refer to the SM30 series of brochures.
Actual part numbers will vary with congifuration. 3U Compact System including standard SM31 supervisory module. 3U Compact System including standard SM31 supervisory module and I/O expansion card. 3U Compact System including standard SM32 supervisory module. 3U Compact System including standard SM32 supervisory module and I/O expansion card.
ENATEL | 2010 PRODUCT CATALOGUE | 13
48 14.0
nominal output voltage.
Three phase (refer to RM series brochures for full details) 45-66Hz >0.99 (full load) Three phase L1, L2, L3, N, E 10mm terminal blocks. Surge protection. (40kA 8/20msec)
DC Output Nominal Voltage: Rated System Output Power: Polarity: DC Distribution: -48V, -60V (+24V available to special order) 14000W @ -48V DC Positive earth. (negative earth available to special order)
kW
5U Compact System
AC Input
10
Battery
3 4
Load: Battery:
2x 10A, 6x 32A, 2x 50A load circuit breakers. 4x 100A battery circuit breakers. Electronic fail detection on both load and battery breakers.
Load
Supervisory Module
SM32
16mm tunnel terminals. 35mm tunnel terminals. 300A battery LVD fitted as standard.
Mechanical Dimensions, W, H, D: Weight: 482.6mm (standard 19 module), 222.2mm (5U, 8), 350mm (13) (390mm with cable strain relief) 14kg (excluding rectifier modules)
Shipping Dimensions, W, H, D: 540mm, 350mm, 435mm Weight: 18kg (excluding rectifier modules)
Various monitoring options are available via the Enatel SM30 series of control & supervisory modules. Standard features include full temperature compensation, automated and manual battery testing/equalisation and three voltage-free relay alarm outputs. Options include extension I/O PCBs that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage- free relay outputs. For further details, refer to the SM30 series of brochures.
Actual part numbers will vary with congifuration. 5U Maxi Compact System including standard SM31 supervisory module. 5U Maxi Compact System including standard SM31 supervisory module and I/O expansion card. 5U Maxi Compact System including standard SM32 supervisory module. 5U Maxi Compact System including standard SM32 supervisory module and I/O expansion card.
DC Output Nominal Voltage: Rated System Output Power: Polarity: DC Distribution: Load: Battery: 6x 10A, 4x 20A, 4x 32A, 4x 50A load circuit breakers. 4x 100A battery circuit breakers. Electronic fail detection on both load and battery breakers.
1
-48V, -60V (+24V available to special order) 14000W @ -48V Positive earth. (negative earth available to special order)
48 14.0
5U Compact System
Battery Load 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Supervisory Module
kW
SM32
16mm tunnel terminals. 35mm tunnel terminals. 300A battery LVD fitted as standard. (option 2x LVDs)
Mechanical Dimensions, W, H, D: Weight: 482.6mm (standard 19 module), 222.2mm (5U, 8), 350mm (13) (390mm with cable strain relief) 14kg (excluding rectifier modules)
Shipping Dimensions, W, H, D: 540mm, 350mm, 435mm Weight: 18kg (excluding rectifier modules)
Various monitoring options are available via the Enatel SM30 series of control & supervisory modules. Standard features include full temperature compensation, automated and manual battery testing/equalisation and three voltage-free relay alarm outputs. Options include extension I/O PCBs that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free relay outputs. For further details, refer to the SM30 series of brochures.
Actual part numbers will vary with congifuration. 5U Maxi Compact System including standard SM31 supervisory module. 5U Maxi Compact System including standard SM31 supervisory module and I/O expansion card. 5U Maxi Compact System including standard SM32 supervisory module. 5U Maxi Compact System including standard SM32 supervisory module and I/O expansion card.
ENATEL | 2010 PRODUCT CATALOGUE | 15
48 14.0
nominal output voltage.
Three phase (refer to RM series brochures for full details) 45-66Hz >0.99 (full load) Three phase L1, L2, L3, N, E, 16mm terminal blocks
DC Output Nominal Voltage: Rated System Output Power: Polarity: DC Distribution: -48V, -60V (+24V available to special order) 14000W @ -48V Positive earth (negative earth available to special order)
kW
5U Compact System
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Battery
Load: Battery:
6x 10A, 4x 20A, 6x 32A, 4x 50A load circuit breakers 4x 100A battery circuit breakers Electronic fail detection on both load and battery breakers
AC Input
3 4
Load
Supervisory Module
SM32
16mm tunnel terminals 35mm tunnel terminals 300A battery LVD fitted as standard
Mechanical Dimensions, W, H, D: Weight: 482.6mm (standard 19 module), 222.2mm (5U, 8), 350mm (13) (390mm with cable strain relief) 15kg (excluding rectifier modules)
Shipping Dimensions, W, H, D: 540mm, 350mm, 435mm Weight: 18kg (excluding rectifier modules)
Various monitoring options are available via the Enatel SM30 series of control & supervisory modules. Standard features include full temperature compensation, automated and manual battery testing/equalisation and three voltage-free relay alarm outputs. Options include extension I/O PCBs that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free relay outputs. For further details, refer to the SM30 series of brochures.
Actual part numbers will vary with congifuration. 5U Maxi Compact System including standard SM31 supervisory module. 5U Maxi Compact System including standard SM31 supervisory module and I/O expansion card. 5U Maxi Compact System including standard SM32 supervisory module. 5U Maxi Compact System including standard SM32 supervisory module and I/O expansion card.
DC Output Nominal Voltage: Rated System Output Power: Polarity: DC Distribution: Load: Battery: 2x 20A, 4x 32A, 4x 63A load circuit breakers. 4x 100A battery circuit breakers. Electronic fail detection on both load and battery breakers. -48V, -60V (+24V available to special order) 22000W @ -48V DC Positive earth. (negative earth available to special order)
48 22.0
6U Compact System AC Input
1 2 3 4 5 6 7 8 9 10 Battery Load 1 2 3 4
Supervisory Module
kW
20A, 32A, 63A, 16mm tunnel terminals. 35mm tunnel terminals. 500A battery LVD fitted as standard.
SM32
Mechanical Dimensions, W, H, D: Weight: 482.6mm (standard 19 module), 266.7mm (6U, 10), 350mm (13) (390mm with cable strain relief) 21kg (excluding rectifier modules)
Shipping Dimensions, W, H, D: 540mm, 350mm, 435mm Weight: 30kg (excluding rectifier modules)
Various monitoring options are available via the Enatel SM30 series of control & supervisory modules. Standard features include full temperature compensation, automated and manual battery testing/equalisation and three voltage-free relay alarm outputs. Options include extension I/O PCBs that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free relay outputs. For further details, refer to the SM30 series of brochures.
Part Numbers: PSC22110610-000: PSC22110611-000: PSC22110620-000: PSC22110621-000: PSC22110610-F00: PSC22110611-F00: PSC22110620-F00: PSC22110621-F00:
Actual part numbers will vary with congifuration. 6U Maxi Compact System including standard SM31 supervisory module. 6U Maxi Compact System including standard SM31 supervisory module and I/O expansion card. 6U Maxi Compact System including standard SM32 supervisory module. 6U Maxi Compact System including standard SM32 supervisory module and I/O expansion card. 6U Front Terminal Maxi Compact System including standard SM31 supervisory module.* 6U Front Terminal Maxi Compact System including standard SM31 supervisory module and I/O expansion card.* 6U Front Terminal Maxi Compact System including standard SM32 supervisory module.* 6U Front Terminal Maxi Compact System including standard SM32 supervisory module and I/O expansion card.* *for front terminal systems a minimum of 3U height above the 6U system is recommended for load and battery cabling.
ENATEL | 2010 PRODUCT CATALOGUE | 17
48 27.0
nominal output voltage.
AC Input AC Input Range: Maximum Input Current: Frequency Range: Power Factor: Style: Surge Protection: In(8/20S): Imax(8/20S): 312-500V AC (full power output) 156-312V AC (reduced output power) 60A/ph (ph-N) 45-66Hz >0.99 (full power) 3-phase neutral and earth. MOV; 3x Ph-N, 1x N-Earth. 20kA 40kA
kW
DC Output Nominal System Output Voltage: Maximum Power Output: Polarity: Load & Battery Distribution: Low Voltage Disconnect Options: LVD Current Rating: -48V 27000W Positive earth. (standard) 16x load positions for 18mm wide circuit breakers, plus 4x battery breakers up to 125A each. May be arranged in different configurations of load and battery breakers. Fuse options also available. (options) Single battery LVD fitted as standard. Up to 2x LVDs with independent control may be fitted on battery or load side. (option) 600A web based viewing & configuration. (option) Door mounted for improved system terminal access. Optional full battery monobloc monitoring. (bloc voltage & string current) 1x fixed alarm - Monitor failed Up to 9x user configurable, 2 of which are pre-programmed: - Non-urgent summary alarm - Urgent summary alarm 7x unassigned, may be assigned to any one of 37 alarm events, (e.g. rectifier fail, mains fail etc.) on an AND or OR basis Contacts rated for 1A at 60V DC
Supervisory & Monitoring Module: SM31 (standard) SM32 TCP/IP enabled for Supervisory Module Mounting: Battery Condition Monitoring: Alarms (voltage free contacts): Environmental Requirements Temperature: Humidity: Altitude: Mechanical Dimensions W, D, H: Weight: Shipping Size L, W, H Shipping weight: Compliances Safety: Part Numbers:
18 | ENATEL | 2010 PRODUCT CATALOGUE
-10C to +70C (max. power de-rated above 50C) 5-95% RH (non-condensing) <2500m, De-rate maximum ambient temperature by 4C per 1000m above sea level.
600mm (23 ) , 19 standard mounting rails 450mm (17 ), 800mm (31 ) providing 15U of rack space. 75kg (approx) 900mm x 700mm x 550mm 80kg (approx)
EN60950 Actual part numbers will vary with congifuration. Contact us for further details on a solution that suits your requirements.
DC Output Nominal System Output Voltage: Maximum Power Output: Polarity: Load Distribution: Priority: Non-Priority: 6x 18mm MCBs. 5x 18mm MCBs, 2x 100A DIN00 fuses, 2x 160A DIN00 fuses. 2x 400A DIN02 fuses. 2x LVDs with independent control on load side. 400A 200A web based viewing & configuration. (option) Door mounted for improved system terminal access. Optional full battery monobloc monitoring. (bloc voltage & string current) 1x fixed alarm Monitor failed Up to 9x user configurable, 2 of which are pre-programmed: - Non-urgent summary alarm - Urgent summary alarm 7x unassigned, may be assigned to any one of 37 alarm events, (e.g. rectifier fail, mains fail etc.) on an AND or OR basis. Contacts rated for 1A at 60V DC -48V 27000W Positive earth. (standard)
48 27.0
kW
Supervisory & Monitoring Module: SM31 (standard) SM32 TCP/IP enabled for Supervisory Module Mounting: Battery Condition Monitoring: Alarms (voltage free contacts): Environmental Requirements Temperature: Humidity: Altitude: Mechanical Dimensions W, D, H: Weight: Shipping Size L, W, H Shipping weight: Compliances Safety: Part Numbers: EN60950 Actual part numbers will vary with congifuration. Contact us for further details on a solution that suits your requirements.
ENATEL | 2010 PRODUCT CATALOGUE | 19
-10C to +70C (max. power de-rated above 50C) 5-95% RH (non-condensing) <2500m, De-rate maximum ambient temperature by 4C per 1000m above sea level.
600mm (23.6), 600mm (23.6), 1600mm (63), providing 33U of rack space. 120kg (approx) 1700mm x 720mm x 830mm 130kg (approx)
48 54.0
nominal output voltage.
AC Input Voltage Range: Maximum Input Current: Frequency Range: Power Factor: Style: Surge Protection: In(8/20S): Imax(8/20S): 312-500V AC (full power output) 156-312V AC (reduced output power) 120A/ph (ph-N) 45-66Hz >0.99 (full power) 3-phase neutral and earth. MOV; 3x Ph-N, 1x N-Earth. 20kA 40kA
kW
DC Output Nominal System Output Voltage: Maximum Power Output: Polarity: Load & Battery Distribution: Low Voltage Disconnect Options: LVD Current Rating: -48V 54000W Positive earth. (standard) 56x positions for 18mm wide DIN rail mount circuit breakers. May be arranged in many configurations of loads and batteries. Fuse options also available. (options) Single battery LVD fitted as standard. Up to 2x LVDs with independent control may be fitted on battery or load side. (option) 1200A for web based viewing & configuration. (option) Door mounted for improved system terminal access. Optional full battery monobloc monitoring. (bloc voltage & string current) 1x fixed alarm Monitor failed Up to 9x user configurable, 2 of which are pre-programmed: - Non-urgent summary alarm - Urgent summary alarm 7x unassigned, may be assigned to any one of 37 alarm events, (e.g. rectifier fail, mains fail etc.) on an AND or OR basis Contacts rated for 1A at 60V DC
Supervisory & Monitoring Module: SM31 (standard) SM32 TCP/IP enabled Supervisory Module Mounting: Battery Condition Monitoring: Alarms (voltage free contacts): Environmental Requirements Temperature: Humidity: Altitude: Mechanical Dimensions W, D, H: Weight: Shipping Size L, W, H Shipping weight: Compliances Safety: EN60950 600mm (23.6), 19 standard mounting rails, 600mm (23.6), 2000mm (78 ) 40U of rack space. 180kg (approx) 2100mm, 720mm, 830mm 195kg (approx) -10C to +70C (max. power de-rated above 50C) 5-95% RH (non-condensing) <2500m, De-rate maximum ambient temperature by 4C per 1000m above sea level.
Part Numbers:
20 | ENATEL | 2010 PRODUCT CATALOGUE
Actual part numbers will vary with congifuration. Contact us for further details on a solution that suits your requirements.
DC Output Nominal System Output Voltage: Maximum Power Output: Polarity: Load & Battery Distribution: -48V 16000W Positive earth. (standard) 24x load positions for 18mm wide circuit breakers, plus 3x battery breakers up to 100A each. May be arranged in different configurations of load and battery breakers. (option) Single battery LVD fitted as standard. Up to 2x LVDs with independent control may be fitted on load side. (option) 400A
48 16.0
kW
Supervisory & Monitoring Module: SM31 (standard) SM32 TCP/IP enabled for web based viewing & configuration. (option) Door mounted for improved system terminal access. RM2048, 48V 2.0kW module.
Environmental Requirements Temperature: Humidity: Altitude: -10C to +70C (max. power de-rated above 50C) 5-95% RH (non-condensing) <2500m, De-rate maximum ambient temperature by 4C per 1000m above sea level.
Mechanical Dimensions W, D, H: Weight: Shipping Size L, W, H Shipping weight: 600mm (23.6), 600mm (23.6),2200mm (86.6) 1000kg when fitted with 4x strings of 180Ahr batteries. (approx) 2400mm x 720mm x 830mm 180kg (no batteries fitted, approx)
Battery Accommodation Battery Trays: Battery Monobloc Size W, D, H: Up to 4x 180Ahr monoblocs of up to 60kg each per tray. (max. of 250kg per tray) 110mm, 555mm, 288mm
Part Numbers:
Actual part numbers will vary with congifuration. Contact us for further details on a solution that suits your requirements.
ENATEL | 2010 PRODUCT CATALOGUE | 21
48 54.0
nominal output voltage.
AC Input Voltage Range: Maximum Input Current: Frequency Range: Power Factor: Style: Surge Protection: In(8/20S): Imax(8/20S): 312-500V AC (full power output) 156-312V AC (reduced output power) 120A/ph (ph-N) 45-66Hz >0.99 (full power) 3-phase neutral and earth. MOV; 3x Ph-N, 1x N-Earth. 20kA 40kA
kW
DC Output Nominal System Output Voltage: Maximum Power Output: Polarity: -48V From 54000W scalable to over 300kW. Positive earth. (standard) Load & Battery Distribution: LVD Options: LVD Current Rating: Monitoring: Environmental Requirements Temperature: Humidity: Altitude: Mechanical Dimensions W, D, H: Weight: Shipping Size L, W, H Shipping weight: Compliances Safety: EN60950 600mm (23.6), 19 standard mounting rails, 600mm (23.6), 2000mm (78 ) 40U of rack space. 180kg (approx) 2100mm, 720mm, 830mm 195kg (approx) -10C to +70C (max. power de-rated above 50C) 5-95% RH (non-condensing) <2500m, De-rate maximum ambient temperature by 4C per 1000m above sea level. 56x positions for 18mm wide DIN rail mount circuit breakers. May be arranged in many configurations of loads and batteries. Fuse options also available. (options) Single battery LVD. Up to 2x LVDs with independent control may be fitted on battery or load side. (option) 1200A SM31 (standard) SM32 TCP/IP enabled for web based viewing & configuration. (option) system terminal access. monitoring. (bloc voltage & string current)
Supervisory Module Mounting: Door mounted for improved Battery Condition Monitoring: Optional full battery monobloc
Frequency Range: Power Factor: Termination: terminals. DC Output Nominal Voltages: Max Rated System Output Power: Polarity: DC Distribution: Load: Battery:
-48V version. 4000W @ -48V DC, 83A max. Positive earth. 1x RM3048 3000W rectifier or 2x RM2048 2000W rectifiers.
+24V version. 2140W @ +24V DC, 80A max. Negative Earth. 1x RM2324 2140W rectifier or 2x RM1848/24 900W rectifiers.
Max 8x 18mm MCB load circuit breakers. Max 2x 18mm MCB load circuit breakers. Electronic fuse fail. (Auxiliaries optional) Live: Direct MCB connections. Common: 16mm tunnel terminals. Common: 35mm tunnel terminals. 80A battery LVD fitted as standard on -48V and 24V systems.
48 4.0 24 2.1
kW
kW
Various monitoring options via the Enatel SM30 series of control & supervisory modules. Standard features include full temperature compensation, automated and manual battery testing/equalisation and three voltage-free relay alarm outputs. Options include extension remote I/O PCBs that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free relay outputs. For further details, refer to the SM30 series of brochures.
Part Numbers: PSW-4204810-000: PSW-4204820-000: PSW-3104810-000: PSW-3104820-000: PSW-2102410-000: PSW-2102420-000: PSW-2202410-000: PSW-2202420-000:
Actual part numbers will vary with congifuration. 48V, 2x 2000W rectifiers, SM31 supervisory module. 48V, 2x 2000W rectifiers, SM32 supervisory module. (Remote communication via SNMP) 48V, 1x 3000W rectifier, SM31 supervisory module. 48V, 1x 3000W rectifier, SM32 supervisory module. (Remote communication via SNMP) 24V, 1x 2140W rectifier, SM31 supervisory module. 24V, 1x 2140W rectifier, SM32 supervisory module. (Remote communications via SNMP) 24V, 2x 900W rectifiers, SM31 supervisory module. 24V, 2x 900W rectifiers, SM32 supervisory module. (Remote communication via SNMP)
ENATEL | 2010 PRODUCT CATALOGUE | 23
MODULAR RECTIFIERS
- Force cooled. - Microprocessor controlled. - Power factor corrected. - Thermally protected. - Input/output voltage and current protected. - Serial alarm and control interface. These rectiers are designed for integration into systems that require intelligent features and remote control. With efciencies in excess of 92% and power factors of greater than 0.98 these rectiers will save operating costs, and reduce heat dissipation. Suitable for powering a wide range of telecommunications and data networking applications including wireless, access networks and central ofce switching environments. If you are looking for modular, plug and play rectiers with some of the highest power densities in the market you have come to the right place.
DC Output Output Ratings: Nominal Voltage: Rated Voltage: Voltage Range: Maximum Current: Line: Load: Constant power output from 50V to 58V 48V 58V 43-60V 60A 0.1% 0.5% (no load to full load) >15ms for 20% output voltage drop. Start up delay 1 second. (varies with AC supply voltage) Walk-in delay 6 seconds at full output. (varies with DC output voltage) Adjustable to 50-100% of maximum rated current. Automatic current turndown, backup shutdown protection. Output fuse with crowbar diode. Adjustable limit. <1mV rms unweighted <1mV rms psophometric <5mV rms unweighted <50mV peak to peak 4000V DC 3500V DC (VDR to chassis removed) 2100V DC
Regulation:
Hold-up Time: Start-up Time: Protection: Current Limit: Over Temperature: Polarity Reversal: Over voltage: Ripple <100Hz: Voice band 100Hz-5KHz: Wide band 5kHz-1MHz: Peak to Peak 0-20MHz: Input to Output: Input to Chassis: Output to Chassis:
48 3.0 60.0
kW
Isolation:
Environmental Requirements Ambient Temperature: Nominal: Range: 25+/-5C -10C to +70C (maximum output power is derated above +50C) -20C to +70C 5-95% RH (non-condensing) <2500m, De-rate maximum ambient temperature by 4C per 1000m above sea level.
Storage Temperature: Humidity: Altitude: Mechanical Dimensions, W, H, D: Weight: Shipping Dimensions W, H, D: Shipping Weight: Cooling: Compliances Safety: Electrostatic Discharge: Radiated Radio Frequency: AC Harmonics: AC Flicker and Fluctuation: Other:
41mm, 220mm, 305mm overall. 2.7kg 52mm, 230mm, 340mm 2.85kg Forced cooled, using dual temperature controlled high reliability fans.
AC Input Nominal: Voltage Range: Frequency Range: Power Factor: Efficiency: Input Fuses: Maximum Input Current: Protection: Input Voltage: Input Inrush: Auto shutdown, auto restart when correct voltage restored. <2x maximum input current. 48V Constant power output from 50V to 60V 48V 58V 43-60V 60A 0.1% 0.5% (no load to full load) >15ms for 20% output voltage drop. Start up delay 1 second. (varies with AC supply voltage) Walk-in delay 6 seconds at full output. (varies with DC output voltage) Adjustable to 50-100% of maximum rated current. Automatic current turndown, backup shutdown protection. Output fuse with crowbar diode. Adjustable limit. <1mV rms unweighted <1mV rms psophometric <5mV rms unweighted <50mV peak to peak 4000V DC 3500V DC (VDR to chassis removed) 2100V DC 24V Current limited to 60A 24V 29V 21-30V 60A 230V 90-300V (reduced power below 175V) 45-65 Hz >0.99 >92% (>45% output power) HRC fuses in phase and neutral. 19A
kW
DC Output - Software Switchable Output Ratings: Nominal Voltage: Rated Voltage: Voltage Range: Maximum Current: Line: Load:
Regulation:
Hold-up Time: Start-up Time: Protection: Current Limit: Over Temperature: Polarity Reversal: Over voltage: Ripple <100Hz: Voice band 100Hz-5KHz: Wide band 5kHz-1MHz: Peak to Peak 0-20MHz: Input to Output: Input to Chassis: Output to Chassis:
kW
Isolation:
Environmental Requirements Ambient Temperature: Nominal: Range: 25+/-5C -10C to +70C (maximum output power is derated above +50C) -20C to +70C 5-95% RH (non-condensing) <2500m, De-rate maximum ambient temperature by 4C per 1000m above sea level.
Storage Temperature: Humidity: Altitude: Mechanical Dimensions, W, H, D: Weight: Shipping Dimensions W, H, D: Shipping Weight: Cooling: Compliances Safety: Electrostatic Discharge: Radiated Radio Frequency: AC Harmonics: AC Flicker and Fluctuation: Other:
26 | ENATEL | 2010 PRODUCT CATALOGUE
41mm, 220mm, 305mm overall. 2.7kg 52mm, 230mm, 340mm 2.85kg Forced cooled, using dual temperature controlled high reliability fans.
DC Output - Software Switchable Output Ratings: Nominal Voltage: Rated Voltage: Voltage Range: Maximum Current:
Regulation: Line: Load: 0.1% 0.5% (no load to full load) >15ms for 20% output voltage drop Start up delay 1 second. (varies with AC supply voltage)
Hold-up Time: Start-up Time: Protection: Current Limit: Over Temperature: Polarity Reversal: Over voltage: Ripple <100Hz: Voice band 100Hz-5KHz: Wide band 5kHz-1MHz: Peak to Peak 0-20MHz: Input to Output: Input to Chassis: Output to Chassis:
kW
Walk-in delay 6 seconds at full output. (varies with DC output voltage) Adjustable to 50-100% of maximum rated current. Automatic current turndown, backup shutdown protection. Output fuse with crowbar diode. Adjustable limit. <1mV rms unweighted <1mV rms psophometric <5mV rms unweighted <50mV peak to peak 4000V DC 3500V DC (VDR to chassis removed) 2100V DC
Isolation:
Environmental Requirements Ambient Temperature: Nominal: Range: 25+/-5C -20C to +70C (maximum output power is derated above +50C) -20C to +70C 5-95% RH (non-condensing) <2500m, De-rate maximum ambient temperature by 4C per 1000m above sea level.
Storage Temperature: Humidity: Altitude: Mechanical Dimensions, W, H, D: Weight: Shipping Dimensions W, H, D: Shipping Weight: Cooling: Compliances Safety: Electrostatic Discharge: Radiated Radio Frequency: AC Harmonics: AC Flicker and Fluctuation: Other:
41mm, 220mm, 305mm overall. 2.8kg 52mm, 230mm, 340mm 2.95kg Forced cooled, using dual temperature controlled high reliability fans.
24 2.3 80.0
nominal output voltage.
AC Input Nominal: Voltage Range: Frequency Range: Power Factor: Efficiency: Input Fuses: Maximum Input Current: Protection: Input Voltage: Input Inrush: Auto shutdown, auto restart when correct voltage restored. <2x maximum input current. 230V 90-300V (reduced power below 150V) 45-65 Hz >0.99 >91% (>45% output power) HRC fuses in phase and neutral. 19A
kW
DC Output Output Ratings: Nominal Voltage: Rated Voltage: Voltage Range: Maximum Current: Line: 0.1% Load: 0.5% (no load to full load) >15ms for 20% output voltage drop. Start up delay 1 second. (varies with AC supply voltage) Walk-in delay 7 seconds at full output. (varies with DC output voltage) Adjustable to 50-100% of maximum rated current. Automatic current turndown, backup shutdown protection. Output fuse with crowbar diode. Adjustable limit. <1mV rms unweighted <1mV rms psophometric <5mV rms unweighted <50mV peak to peak 4000V DC 3500V DC (VDR to chassis removed) 2100V DC Current limited to 80A 24V 29V 21-30V 80A
Regulation:
Hold-up Time: Start-up Time: Protection: Current Limit: Over Temperature: Polarity Reversal: Over voltage: Ripple <100Hz: Voice band 100Hz-5KHz: Wide band 5kHz-1MHz: Peak to Peak 0-20MHz: Input to Output: Input to Chassis: Output to Chassis:
Isolation:
Environmental Requirements Ambient Temperature: Nominal: Range: 25+/-5C -10C to +70C (maximum output power is derated above +50C) -20C to +70C 5-95% RH (non-condensing) <2500m, De-rate maximum ambient temperature by 4C per 1000m above sea level.
Storage Temperature: Humidity: Altitude: Mechanical Dimensions, W, H, D: Weight: Shipping Dimensions W, H, D: Shipping Weight: Cooling: Compliances Safety: Electrostatic Discharge: Radiated Radio Frequency: AC Harmonics: AC Flicker and Fluctuation: Other:
28 | ENATEL | 2010 PRODUCT CATALOGUE
41mm, 220mm, 305mm overall. 2.7kg 52mm, 230mm, 340mm 2.75kg Forced cooled, using dual temperature controlled high reliability fans.
DC Output Output Ratings: Nominal Voltage: Rated Voltage: Voltage Range: Maximum Current: Line: Load: Constant power output from 48V to 58V 48V 58V 43-60V 41.7A 0.1% 0.5% (no load to full load) >15ms for 20% output voltage drop. Start up delay 1 second. (varies with AC supply voltage) Walk-in delay 6 seconds at full output. (varies with DC output voltage) Adjustable to 50-100% of maximum rated current. Automatic current turndown, backup shutdown protection. Output fuse with crowbar diode. Adjustable limit. <1mV rms unweighted <1mV rms psophometric <5mV rms unweighted <100mV peak to peak 4000V DC 3500V DC (VDR to chassis removed) 2100V DC
Regulation:
Hold-up Time: Start-up Time: Protection: Current Limit: Over Temperature: Polarity Reversal: Over voltage: Ripple <100Hz: Voice band 100Hz-5KHz: Wide band 5kHz-1MHz:
48 2.0 41.7
kW
Peak to Peak 0-20MHz: Isolation: Input to Output: Input to Chassis: Output to Chassis:
Environmental Requirements Ambient Temperature: Nominal: Range: 25+/-5C -10C to +70C (maximum output power is derated above +50C) -20C to +70C 5-95% RH (non-condensing) <2500m, De-rate maximum ambient temperature by 4C per 1000m above sea level.
Storage Temperature: Humidity: Altitude: Mechanical Dimensions, W, H, D: Weight: Shipping Dimensions W, H, D: Shipping Weight: Cooling: Compliances Safety: Electrostatic Discharge: Radiated Radio Frequency: AC Harmonics: AC Flicker and Fluctuation: Other:
111.5mm , 44mm (1U), 282mm overall (rack depth 260mm) 1.5kg 120mm, 52mm, 325mm 1.6kg Forced cooled.
AC Input Nominal: Voltage Range: Frequency Range: Power Factor: Efficiency: Input Fuses: Maximum Input Current: Protection: Input Voltage: Input Inrush: Auto shutdown, auto restart when correct voltage restored. <2x maximum input current. 48V Constant power output from 54V to 60V 48V 58V 43-60V 41.7A 0.1% 0.5% (no load to full load) >15ms for 20% output voltage drop. Start up delay 1 second. (varies with AC supply voltage) Walk-in delay 6 seconds at full output. (varies with DC output voltage) Adjustable to 50-100% of maximum rated current. Automatic current turndown, backup shutdown protection. Output fuse with crowbar diode. Adjustable limit. <1mV rms unweighted <1mV rms psophometric <5mV rms unweighted <50mV peak to peak 4000V DC 3500V DC (VDR to chassis removed) 2100V DC 24V Current limited to 41.7A 24V 29V 21-30V 41.7A 230V 90-300V (reduced power below 175V) 45-65 Hz >0.99 >91% (>50% output power) HRC fuses in phase and neutral. 13A
kW
DC Output - Software Switchable Output Ratings: Nominal Voltage: Rated Voltage: Voltage Range: Maximum Current: Line: Load:
Regulation:
Hold-up Time: Start-up Time: Protection: Current Limit: Over Temperature: Polarity Reversal: Over voltage: Ripple <100Hz: Voice band 100Hz-5KHz: Wide band 5kHz-1MHz: Peak to Peak 0-20MHz: Input to Output: Input to Chassis: Output to Chassis:
kW
Isolation:
Environmental Requirements Ambient Temperature: Nominal: Range: 25+/-5C -10C to +70C (maximum output power is derated above +50C) -20C to +70C 5-95% RH (non-condensing) <2500m, De-rate maximum ambient temperature by 4C per 1000m above sea level.
Storage Temperature: Humidity: Altitude: Mechanical Dimensions, W, H, D: Weight: Shipping Dimensions W, H, D: Shipping Weight: Cooling: Compliances Safety: Electrostatic Discharge: Radiated Radio Frequency: AC Harmonics: AC Flicker and Fluctuation: Other:
30 | ENATEL | 2010 PRODUCT CATALOGUE
111.5mm , 44mm (1U), 282mm overall (rack depth 260mm) 1.5kg 120mm, 52mm, 325mm 1.6kg Forced cooled.
DC Output - Software Switchable Output Ratings: Nominal Voltage: Rated Voltage: Voltage Range: Maximum Current: Regulation: Line: Load:
Hold-up Time: Start-up Time: Protection: Current Limit: Over Temperature: Polarity Reversal: Over voltage: Ripple <100Hz: Voice band 100Hz-5KHz: Wide band 5kHz-1MHz: Peak to Peak 0-20MHz: Input to Output: Input to Chassis: Output to Chassis:
kW
Walk-in delay 6 seconds at full output. (varies with DC output voltage) Adjustable to 50-100% of maximum rated current. Automatic current turndown, backup shutdown protection. Output fuse with crowbar diode. Adjustable limit. <1mV rms unweighted <1mV rms psophometric <5mV rms unweighted <50mV peak to peak 4000V DC 3500V DC (VDR to chassis removed) 2100V DC
Isolation:
Environmental Requirements Ambient Temperature: Nominal: Range: 25+/-5C -10C to +70C (maximum output power is derated above +50C) -20C to +70C 5-95% RH (non-condensing) <2500m, De-rate maximum ambient temperature by 4C per 1000m above sea level.
Storage Temperature: Humidity: Altitude: Mechanical Dimensions, W, H, D: Weight: Shipping Dimensions W, H, D: Shipping Weight: Cooling: Compliances Safety: Electrostatic Discharge: Radiated Radio Frequency: AC Harmonics: AC Flicker and Fluctuation: Other:
111.5mm , 44mm (1U), 282mm overall (rack depth 260mm) 1.4kg 120mm, 52mm, 325mm 1.5kg Forced cooled.
48 1.0 21.0
nominal output voltage.
AC Input Nominal: Voltage Range: Frequency Range: Power Factor: Efficiency: Input Fuses: Protection: Input Voltage: Input Inrush: Auto shutdown, auto restart when correct voltage restored. <2x maximum input current. 7A 230V 90-300V (reduced power below 175V) 45-65 Hz >0.99 >90% (>50% output power) HRC fuses in phase and neutral.
Maximum Input Current: DC Output Output Ratings: Nominal Voltage: Rated Voltage: Voltage Range: Maximum Current: Line: Load:
kW
Constant power output from 48V to 58V 48V 58V 43-60V 21A 0.1% 0.5% (no load to full load) >15ms for 20% output voltage drop. Start up delay 1 second. (varies with AC supply voltage) Walk-in delay 6 seconds at full output. (varies with DC output voltage) Adjustable to 50-100% of maximum rated current. Automatic current turndown, backup shutdown protection. Output fuse with crowbar diode. Adjustable limit. <1mV rms unweighted <1mV rms psophometric <5mV rms unweighted <50mV peak to peak 4000V DC 3500V DC (VDR to chassis removed) 2100V DC
Regulation:
Hold-up Time: Start-up Time: Protection: Current Limit: Over Temperature: Polarity Reversal: Over voltage: Ripple <100Hz: Voice band 100Hz-5KHz: Wide band 5kHz-1MHz: Peak to Peak 0-20MHz: Input to Output: Input to Chassis: Output to Chassis:
Isolation:
Environmental Requirements Ambient Temperature: Nominal: Range: 25+/-5C -10C to +75C (maximum output power is derated above +50C) -20C to +75C 5-95% RH (non-condensing) <2500m, De-rate maximum ambient temperature by 4C per 1000m above sea level.
Storage Temperature: Humidity: Altitude: Mechanical Dimensions, W, H, D: Weight: Shipping Dimensions W, H, D: Shipping Weight: Cooling: Compliances Safety: Electrostatic Discharge: Radiated Radio Frequency: AC Harmonics: AC Flicker and Fluctuation: Other:
32 | ENATEL | 2010 PRODUCT CATALOGUE
111.5mm , 44mm (1U), 282mm overall (rack depth 260mm) 1.4kg 120mm, 52mm, 325mm 1.5kg Forced cooled
DC Output Output Ratings: Nominal Voltage: Rated Voltage: Voltage Range: Maximum Current: Line: Load: Constant power output from 54V to 58V 48V 58V 43-60V 16.6A 0.1% 0.5% (no load to full load) >15ms for 20% output voltage drop. Start up delay 1 second. (varies with AC supply voltage) Walk-in delay 6 seconds at full output. (varies with DC output voltage) Adjustable to 50-100% of maximum rated current. Automatic current turndown, backup shutdown protection. Output fuse with crowbar diode. Adjustable limit. <1mV rms unweighted <2mV rms psophometric <5mV rms unweighted <50mV peak to peak 4000V DC 3500V DC (VDR to chassis removed) 2100V DC
Regulation:
Hold-up Time: Start-up Time: Protection: Current Limit: Over Temperature: Polarity Reversal: Over voltage: Ripple <100Hz: Voice band 100Hz-5KHz: Wide band 5kHz-1MHz: Peak to Peak 0-20MHz: Input to Output: Input to Chassis: Output to Chassis:
48 800 16.6
Isolation:
Environmental Requirements Ambient Temperature: Nominal: Range: 25+/-5C -20C to +70C (maximum output power is derated above +50C) -20C to +70C 0-98% RH (non-condensing) <3000m, De-rate maximum ambient temperature by 4C per 1000m above sea level.
Storage Temperature: Humidity: Altitude: Mechanical Dimensions, W, H, D: Weight: Shipping Dimensions W, H, D: Shipping Weight: Cooling: Compliances Safety: Electrostatic Discharge: Radiated Radio Frequency: AC Harmonics: AC Flicker and Fluctuation: Other:
55mm , 44mm (1U), 235mm overall (rack depth 260mm) 800g 100mm, 80mm, 300mm 1.0kg Forced cooled.
RF1448 RF1124 220/240V, 50/60Hz 220/240V, 50/60Hz 180-275V AC 180-275V AC (full power output), (full power output), 150-180V AC 150-180V AC (reduced power output) (reduced power output) 45-66Hz >0.93 (full load) RF1448 RF1124 90% 92% 8.5A 8.5A HRC fuses in phase & neutral.
RF748U 110-220V, 50/60Hz 100-275V AC (full power output), 85-100V AC (reduced power output) RF748U 89% 8.5A
RF624U 110-220V, 50/60Hz 100-275V AC (full power output), 85-100V AC (reduced power output) RF624U 87% 8.5A
RF512U 110-220V, 50/60Hz 100-275V AC (full power output), 85-100V AC (reduced power output) RF512U 85% 8.5A
RF348U 110-220V, 50/60Hz 100-275V AC (full power output), 85-100V AC (reduced power output) RF348U 85% 8.5A
Automatic shutdown, restarts automatically when correct voltage restored. <2x maximum input current. RF1448 48V 58V 45-60V 25A RF1124 24V 29V 22-30V 40A RF748U 48V 58V 45-60V 12A RF624U 24V 29V 22-30V 22A RF512U 12V 14.5V 11.5-15V 40A RF348U 48V 58V 45-60V 6A
0.1% 0.5% (no load to full load) >15ms for 20% output voltage drop. Walk-in delay 2 seconds. (depends on AC input voltage) Adjustable to 50-100% of maximum rated current. Automatic current turndown, backup shutdown protection. Output fuse with crowbar diode. Adjustable limit. RF1124 RF748U RF1448 <10mV rms unweighted. <5mV rms unweighted. <10mV rms unweighted. <2mV rms psophometric. <1mV rms psophometric. <2mV rms psophometric. <10mV rms unweighted. <5mV rms unweighted. <10mV rms unweighted. <50mV p-p unweighted. <50mV p-p unweighted. <50mV p-p unweighted. 3000V AC 2500V AC (VDR to chassis removed) 1500V AC 25+/-5C -10 to +50C 5-95% RH (non-condensing.) <2500m de-rate maximum ambient temperature by +4 per 1000m above sea level. 227mm, 44mm (1U), 270mm, (293mm over handle) 1.5kg 377mm, 235mm, 122mm 2.4kg Forced cooled. IEC 320 universal connection. 4 way lumberg macromodule. 2 way lumberg macromodule. RJ45 Mini combicon. Output voltage slope adjustable 0.1 to 0.2%/C (standard) Rectifier enters boost mode at power up. When battery current reduces to float threshold limit (adjustable from 0.1A to 40% MRC), unit reverts to float voltage setting. When in boost but out of current limit, rectifier will automatically switch back to float after approximately four hours. If battery current exceeds the float threshold limit when the rectifier is in float mode it will automatically switch to boost mode. Positive V out, Load share signal (in/out), External shutdown, Open collector off normal alarm, (OSVD, over temp., current limit, fan fail), LVD synchronisation signal (in/out), Temperature compensation input signal, Open collector rectifier fail (via 4k7 resistor), Open collector mains fail, Negative V out. RF1448 RF1124 RF748U RF624U RF512U RF348U 38-48V 19-24V 38-48V 19-24V 9.5-12V 38-48V 25A 40A 12A 22A 40A 6A 4x N.O or N.C (selectable) relay contacts with single common for rectifier fail, off normal, float low, float high. 1x VF changeover relay contact for mains fail. Relay contacts rated at 100V DC 1A. Connections via mini combicon connector accepts 1.5mm dia wire. Green - Mains on. (primary converter operating) Green - Temperature probe connected and within normal limits. Red - Rectifier failed. Green - Rectifier in float mode. Yellow - Rectifier in boost mode. Yellow - Rectifier in current limit. Red - Rectifier off normal. (over temp., OVSD, low output volts) Float voltage. Boost voltage. Over voltage shut down. Current limit. Temperature compensation slope. Auto boost to float threshold limit. Load disconnect voltage. (if fitted) Load disconnect hysteresis voltage. (if fitted) EN60950 CISPR24 CISPR22 EN61000-3-2 EN61000-3-3 Standard Standard Standard Standard with with with with temperature temperature temperature temperature compensation, compensation, compensation, compensation, auto auto auto auto float float float float boost, boost, boost, boost, alarm alarm alarm alarm and and and and control control control control I/F. I/F, low volts disconnect. I/F, alarm card. I/F, low volts disconnect, alarm card.
RF624U <5mV rms unweighted. <1mV rms psophometric. <5mV rms unweighted. <50mV p-p unweighted.
RF512U RF348U <5mV rms unweighted. <5mV rms unweighted. <0.5mV rms psophometric. <0.5mV rms psophometric. <2.5mV rms unweighted. <2.5mV rms unweighted. <50mV p-p unweighted. <50mV p-p unweighted.
110/220V, 50/60Hz 100-275V AC (full power output), 85-100V AC (reduced power output) 45-66Hz >0.99 (full load) RW748U RW624U RW512U 88% 87% 85% 8.5A 8.5A 8.5A HRC fuses in phase & neutral. Automatic shutdown, restarts automatically when correct voltage restored. <2x maximum input current. RW748U 48V 58V 45-60V 12A 700W RW624U 24V 29V 22-30V 22A 600W RW512U 12V 14.5V 11.5-15V 35A
RW324U 87% 4A
RW312U 85% 4A
0.1% 0.5% (no load to full load) >15ms for 20% output voltage drop. Walk-in delay 2 seconds (depends on AC input voltage) Adjustable to 50-100% of maximum rated current. Automatic current turndown, backup shutdown protection. Output fuse with crowbar diode. Adjustable limit. RW748U RW624U RW512U RW348U <10mV rms unweighted. <5mV rms unweighted. <5mV rms unweighted. <10mV rms unweighted. <2mV rms psophometric. <1mV rms psophometric. <0.5mV rms psophometric. <2mV rms psophometric. <10mV rms unweighted. <5mV rms unweighted. <2.5mV rms unweighted. <10mV rms unweighted. <50mV p-p unweighted. <50mV p-p unweighted. <50mV p-p unweighted. <50mV p-p unweighted. 3000V AC. 2500V AC (VDR to chassis removed) 1500V AC 25+/-5C -10 to +50C 5-95% RH (non-condensing) <2500m de-rate maximum ambient temperature by +4 per 1000m above sea level. 311mm, 163mm, 62mm 1.5kg 377mm, 235mm, 122mm 2.4kg Convection cooled. IEC 320 universal connection. 4 way lumberg macromodule. 4 way lumberg macromodule. 2 way lumberg macromodule. RJ45. Mini combicon. Ten segment red LED dot display (standard) Output voltage slope adjustable 0.1 to 0.2%/C (standard) Rectifier enters boost mode at power up. When battery current reduces to float threshold limit (adjustable from 0.1A to 40% MRC), unit reverts to float voltage setting. When in boost but out of current limit, rectifier will automatically switch back to float after approximately four hours. If battery current exceeds the float threshold limit when the rectifier is in float mode it will automatically switch to boost mode. Positive V out, Load share signal (in/out), External shutdown, Open collector off normal alarm (OSVD, over temp. limit), LVD synchronisation signal (in/out) Temperature compensation input signal, Open collector rectifier fail (via 4k7 resistor), Open collector mains fail, Negative V out. RW748U RW624U RW512U RW348U RW324U RW312U 38-48V 19-24V 9.5-12V 38-48V 19-24V 9.5-12V 12A 22A 35A 6A 10A 20A 4x N.O or N.C (selectable) relay contacts with single common for rectifier fail, off normal, float low, float high. 1x VF changeover relay contact for mains fail. Relay contacts rated at 100V DC 1A. Connections via mini combicon connector accepts 1.5mm dia wire. Green - Mains on. (primary converter operating) Green - Temperature probe connected and within normal limits. Red - Rectifier failed. Green - Rectifier in float mode. Yellow - Rectifier in boost mode. Yellow - Rectifier in current limit. Red - Rectifier off normal. (over temp. OVSD, low output volts) Float voltage. Boost voltage. Over voltage shut down. Current limit. Temperature compensation slope. Auto boost to float threshold limit. Load disconnect voltage. (if fitted) Load disconnect hysteresis voltage. (if fitted) EN60950 CISPR24 CISPR22 EN61000-3-2 EN61000-3-3 Standard Standard Standard Standard with with with with temperature temperature temperature temperature compensation, compensation, compensation, compensation, auto auto auto auto float float float float boost, boost, boost, boost, alarm alarm alarm alarm and and and and control control control control I/F. I/F, low volts disconnect. I/F, alarm card. I/F, low volts disconnect, alarm card.
RW324U <5mV rms unweighted. <1mV rms psophometric. <5mV rms unweighted. <50mV p-p unweighted.
RW312U <5mV rms unweighted. <0.5mV rms psophometric. <2.5mV rms unweighted. <50mV p-p unweighted.
7U Inverter System
Supervisory Module
SM32
IM10230-48
IM10230-48
IM10230-48
IM10230-48
IM10230-48
IM10230-48
IM10230-48
IM10230-48
IM10230-48
DC-AC INVERTERS
Efcient and reliable, these modular rack mount inverters allow for easy paralleling of modules to provide redundancy or higher power outputs. Designed for use in modern telecommunications networks these inverters offer unrivalled power densities. The unique design allows for mounting nine inverters in a 5U x 19 rack space or two inverters in a 1U x 19 rack space. Plug and Play installation allows quick and easy installation and system expansion. These robust, reliable inverters are forced cooled by two speed controlled and monitored high reliability fans. - Pure sine wave. - Hot swapable. - High efciency. - Smart fan speed control. - Wide operation temperature range. - DSP chip designed. - N+X redundancy system. - Lower audible noise. - High power density. - Enatel RCP bus. - 48V DC telecom system application. - CE & RoHS compliant.
AC Output Nominal Output Voltage: Output Voltage Range: Output Voltage Tolerance: Output Voltage Frequency: Output Frequency Tolerance: Total Harmonic Distortion: Turn On Delay: Crest Factor: Efficiency: 110/230V AC (refer to part number table below for model numbers) 110/115/120V AC or 208/220/230/240V AC +/- 2% 50/60Hz selectable. +/- 0.5% <3% on linear loads. <5% for non linear loads. <3 seconds. 3:1 (nominal power) 90%
Output Power Nominal Value: Overload (5 Seconds): Permanent Overload: Admissible Load Power Factor: Isolation: Input/Output: Output/Earth: Input Earth:
(refer to part number table below for model numbers) 1000VA, 800W/ 1500VA, 1200W 2000VA 10% 0 inductive to 0 capacitive (100% load)
2500V AC 2500V AC 1500V AC -40C to +50C, derated to +70C <55dBa @ 1m 3x LEDs, fail, off normal, power on. Enatel SBI interface to SM3X supervisory module.
Mechanical Dimensions, W, H, D: Weight: Shipping Dimensions W, H, D: Shipping Weight: Cooling: 215mm, 43.8mm, 270mm overall. 2.5kg 52mm, 230mm, 340mm 2.65kg Forced cooled.
Compliances Immunity: Emissions: Safety: Other: CISPR24 CISPR22 Class B IEC60950 CE & RoHS compliant.
1U, 48V DC input, 230V AC output, 1.0kVA 800W 1U, 48V DC input, 120V AC output, 1.0kVA 800W 1U, 48V DC input, 230V AC output, 1.5kVA 1200W 1U, 48V DC input, 120V AC output, 1.5kVA 1200W
- Wide operation temperature - Lower audible noise <55dBA. - Emergency power off function embedded. - No-cross connect. - Optional maintenance bypass
220 to 240V AC for 208V AC systems. 233 to 252V AC for 220V AC systems. 244 to 264V AC for 230V AC systems. 254 to 276V AC for 240V AC systems. 117 to127V AC for 110V AC systems. 122 to 132V AC for 115V AC systems. 127 to 138V AC for 120V AC systems.
176 to 198V AC for 208V AC systems. 176 to 209V AC for 220V AC systems. 185 to 218V AC for 230V AC systems. 193 to 228V AC for 240V AC systems. 89 to 105V AC for 110V AC systems. 93 to 110V AC for 115V AC systems. 100 to 114V AC for 120V AC systems. Startup power-on by priority source or alternative.
Output Waveform: Nominal Output Voltage: Permissible Frequency Area: Transfer Time: Rated Current: Operation Methods: Sinusoidal. Same as mains AC or the output of inverter modules. Max. 2.5% (Synchronize area of inverter). 1.5Hz for 60Hz inverter. 1.25Hz for 50Hz inverter. Typical cycle. 50A (All voltage settings). Inverter priority or utility priority (Programmable).
DC-DC CONVERTERS
- Force cooled. - Thermally protected. - Input/output voltage and current protected. These units offer the same high levels of conversion efciency as other Enatel power products, and will provide the same benets to the customer of reduced operating costs and lower levels of heat dissipation. The converters include a relay contact to indicate converter failure, and have a load share input that ensures that all units connected in parallel carry an equal share of the load. - Wide input voltage range. - Serial alarm and control interface. - Microprocessor controlled. These converters offer plug and play operation, and can be easily paralleled to provide higher power outputs.
DC Output Nominal Output Voltage: Output Voltage Range: Maximum Output Current: Maximum Output Power: Efficiency: Regulation: Line: Load:
Start-up Time: Protection: Current Limit: Over Temperature: Polarity Reversal: Over Voltage: Ripple <100Hz: Voice Band 100Hz-5KHz: Wide Band 5kHz-1MHz: Peak to Peak 0-20MHz: Input to Output: Input to Chassis: Output to Chassis:
Isolation:
Environmental Requirements Ambient Temperature: Nominal: Range: +25 +/- 5C -10 to +70C (maximum output power is derated above +50C) -20 to +70C 5-95% RH (non condensing) <2500m, De-rate maximum ambient temperature by +4C per 1000m above sea level.
Storage Temperature: Humidity: Altitude: Mechanical Dimensions W, H, D: Weight: Shipping Dimensions W, H, D: Shipping Weight: Cooling: Compliances Safety: Electostatic Discharge: Radiated Radio Frequency:
111.5mm, 44mm (1U), 282 overall (rack depth 260mm) 1.1kg 170mm, 52mm, 325mm 1.6kg Forced cooled.
Additional Accesories ACM-4T: Part Numbers CM1760-48: CM1748-60: CM1748-48: 1.7kW 48 to 60V DC modular DC-DC converter. 1.7kW 60 to 48V DC modular DC-DC converter. 1.7kW 48 to 48V DC modular DC-DC converter.
ENATEL | 2010 PRODUCT CATALOGUE | 43
Fuse in the positive input with crowbar diode. Converter shuts down when input voltage is out of range, Automatically restarts when correct voltage is restored. CM612-48 12V 11-14V 40A 560W 89%
DC Output CM1048-24 CM1024-48 CM648-24 CM624-48 Nominal Output Voltage: 48V 24V 48V 24V Output Voltage Range: 46-52V 22-26V 46-52V 22-26V Maximum Output Current: 21.6A 43A 13.5A 25A Maximum Output Power: 1040W 1040W 650W 650W 91% 91% Efficiency: 91% 91% Regulation: 0.1% Line: Load: 0.5% (no load to full load) Start-up Time: Walk-in delay 2-8 seconds depending on load and output Protection: Adjustable to 50-100% of maximum rated current. Current Limit: Over Temperature: Auto current turndown, backup shutdown protection. Polarity Reversal: Output fuse in positive with crowbar diode. Over Voltage: Adjustable limit. Noise: (under nominal conditions) Ripple <100Hz: <1mV rms unweighted Voice Band 100Hz-5KHz: <1mV rms psophometric Wide Band 5kHz-1MHz: <5mV rms unweighted Peak to Peak 0-20MHz: <50mV peak to peak Isolation: 4230V DC Input to Output: 2115V DC (VDR to chassis removed) Input to Chassis: Output to Chassis: 2115V DC Environmental Requirements Ambient Temperature: Nominal: Range: Storage Temperature: Humidity: Altitude:
voltage.
+25 +/- 5C -10 to +70C (maximum output power is derated above +50C) -20 to +70C 5-95% RH (non condensing) <2500m, De-rate maximum ambient temperature by +4C per 1000m above sea level.
Mechanical Dimensions W, H, D: 111.5mm, 44mm (1U), 282 overall (rack depth 260mm) Weight: 1.1kg Shipping Dimensions W, H, D: 170mm, 52mm, 325mm Shipping Weight: 1.6kg Cooling: Forced cooled. Compliances Safety: Electostatic Discharge: Radiated Radio Frequency: Other: Additional Accesories ACM-4T: Part Numbers CM1048-24: CM1024-48: CM648-24: CM624-48: CM612-48:
44 | ENATEL | 2010 PRODUCT CATALOGUE
1.0kW 24 to 48V DC modular DC-DC converter. 1.0kW 48 to 24V DC modular DC-DC converter. 650W 24 to 48V DC modular DC-DC converter. 650W 48 to 24V DC modular DC-DC converter. 560W 48 to 12V DC modular DC-DC converter.
MONITORING
Enatel offer a range of supervisory modules and monitoring options, which have been designed to work with our power products. Allowing for easy integration into our complete DC power systems solutions for telecommunications and data networking applications. - Temperature compensation. - LVD control. - Setup from front panel. - Boost control and timer. - LCD display of parameters.
Input Voltage: Current: Interface Display: Communications: Serial: Relay: TCP/IP: LVD: Indicators: 3x LEDs: Audible: Controls: Signal Inputs: Alarms: Alarm Contacts: Default Alarm Map: Relay 1: Relay 2: Relay 3: Relay 4 - 6: Logging Capacity: Periodic Log: Event Log: Battery Mid-point Monitoring: Physical Dimensions, W, H, D: Weight: Connections: Operating Temperature: Storage Temperature: Compliances Radiated Emissions: RF Susceptibility: Optional Accessories ACA-TC3C: ACA-TC7C: ASM-AC3P: ASM-ABM-24: ASM-SM36IO: Voltage Range: Current: Connection: Alarms: Signal Inputs: Operating Temperature: Storage Temperature: Part Numbers SM36-00: SM36-00-1U: SM36-10-1U: SM36-00-PM: SM36-10-PM:
4 line x 16 character multi-lingual alpha numeric display. 1x USB port on front panel for local PC interface. 1x RS232 port, rear mounted for remote serial/modem communications. 6x alarm and control relays, five of which can be mapped for customized alarm settings. (extra available with I/O expansion board) Ethernet interface for communication using SNMP protocol and internal web based configurator. 3x standard or 2x pulse control LVD contacts. (for magnetically latched LVD contactors) Green - power on/monitor OK. Yellow - non urgent alarm. Red - urgent alarm. 90dBA buzzer mappable to user defined conditions. 3x push buttons for parameter setting or viewing on front panel. 2x serial buses for rectifier control and interface to peripheral modules. 10x general purpose inputs. (6x for customer connection, 4x reserved for internal system connection.) 4x battery MCB sensors. (reserved for internal system connection.) 3x current shunt inputs. (reserved for internal system connection.) 1x DC voltage inputs. (reserved for internal system connection.) 6x alarm relays. 0.3A 100V volts free changeover contacts. Monitor fail. (non programmable.) Non-urgent. (programmable.) Urgent. (programmable.) Unassigned. Typically 16000 records. (dependant on number of parameters logged.) Typically 16000 records. (dependant on number of parameters logged.) 3x strings with individual string currents. (more available with shared string currents.) 111.5mm , 44mm (1U), 265mm overall (rack depth 244mm) 365g Relay outputs, mini combicon to accept 1.5mm csa wire. Serial communications to rectifier shelf & peripheral devices - RJ45. USB port - USB mini B. -25 to +55C -50 to +85C EN55022 EN55024 3m temperature sensor and cable. 7m temperature sensor and cable. 3 phase AC voltage and current monitor. Battery condition monitor, 24 blocks. (maximum 4x BCM cards) Standard I/O expansion board (maximum of 4 per supervisory module.) 15-75V DC <150mA maximum Connects via rectifier serial bus, 2x RJ45. Up to 8x alarm and control relays, able to be mapped for customized alarm settings. Up to 6x digital inputs. Up to 6x analogue inputs. -25 to +55C -50 to +85C Standard 1U modular controller, 6x relays, 6x digital inputs. Standard 1U x 19 mounting version controller, 6x relays, 6x digital inputs. Standard 1U x 19 mounting version controller, 6x relays, 6x digital inputs; with standard I/O expansion board. Standard panel mount version controller, 6x relays, 6x digital inputs. Standard panel mount version controller, 6x relays, 6x digital inputs; with standard I/O expansion board.
4 line x 16 character multi-lingual alpha numeric display. 1x USB port on front panel for local PC interface. 6x alarm and control relays, five of which can be mapped for customized alarm settings. 3x standard or 2x pulse control LVD contacts. (for magnetically latched LVD contactors) Green - power on/monitor OK. Yellow - non urgent alarm. Red - urgent alarm. 90dBA buzzer mappable to user defined conditions. 3x push buttons for parameter setting or viewing on front panel. 2x serial buses for rectifier control and interface to peripheral modules. 10x general purpose inputs. (6x for customer connection, 4x reserved for internal system connection.) 4x battery MCB sensors. (reserved for internal system connection.) 3x current shunt inputs. (reserved for internal system connection.) 1x DC voltage inputs. (reserved for internal system connection.) 6x alarm relays. 0.3A 100V volts free changeover contacts. Monitor fail. (non programmable.) Non-urgent. (programmable.) Urgent. (programmable.) Unassigned. Typically 16000 records. (dependant on number of parameters logged.) Typically 16000 records. (dependant on number of parameters logged.) 3x strings with individual string currents. (more available with shared string currents.)
111.5mm , 44mm (1U), 265mm overall (rack depth 244mm) 325g Relay outputs, mini combicon to accept 1.5mm csa wire. Serial communications to rectifier shelf & peripheral devices - RJ45. USB port - USB mini B. -25 to +55C -50 to +85C
EN55022 EN55024
3m temperature sensor and cable. 7m temperature sensor and cable. 3 phase AC voltage and current monitor. Battery condition monitor, 24 blocks. (maximum 4x BCM cards.) Standard I/O expansion board (maximum of 4 per supervisory module.) 15-75V DC <150mA maximum Connects via rectifier serial bus, 2x RJ45. Up to 8x alarm and control relays, able to be mapped for customized alarm settings. Up to 6x digital inputs. Up to 6x analogue inputs. -25 to +55C -50 to +85C
Standard 1U modular controller, 6x relays, 6x digital inputs. Standard 1U x 19 mounting version controller, 6x relays, 6x digital inputs. Standard 1U x 19 mounting version controller, 6x relays, 6x digital inputs; with standard I/O expansion board. Standard panel mount version controller, 6x relays, 6x digital inputs. Standard panel mount version controller, 6x relays, 6x digital inputs; with standard I/O expansion board.
ENATEL | 2010 PRODUCT CATALOGUE | 47
Input Voltage: Current: Interface Display: Communications: Serial: Relay: TCP/IP: LVD: Indicators: 3x LEDs Audible: Controls: Signal Inputs: Alarms: Alarm Contacts: Default Alarm Map: Logging Capacity: Periodic Log: Event Log: Physical Dimensions, W, H, D: Weight: Connections: Operating Temperature: Storage Temperature: Compliances Radiated Emissions: RF Susceptibility: Optional Accessories ACA-TC3C: ACA-TC7C: ASM-AC3P: ASM-ABM-24: ASM-SM3XIO: Voltage Range: Current: Connection: Alarms: Signal Inputs: Operating Temperature: Storage Temperature: Part Numbers SM32-00: SM32-10: SM32-00-1U: SM32-10-1U: SM32-00-PM: SM32-10-PM:
4 line x 16 character multi-lingual alpha numeric display. 1x USB port on front panel for local PC interface. 1x RS232 port, rear mounted for remote serial/modem communications. 3x alarm and control relays, two of which can be mapped for customized alarm settings. (extra available with I/O expansion board) Ethernet interface for communication using SNMP protocol and internal web based configurator. 3x standard or 2x pulse control LVD contacts. (for magnetically latched LVD contactors) Green - power on/monitor OK. Yellow - non urgent alarm. Red - urgent alarm. 90dBA buzzer mappable to user defined conditions. 3x push buttons for parameter setting or viewing on front panel. Serial bus for rectifier control and interface to peripheral modules. Fuse fail. 5x spare digital inputs. 2x temperature sensors. 3x current shunts. 2x DC voltage inputs. 3x alarm relays. 0.3A 100V volts free changeover contacts. Urgent. Non-urgent. Monitor fail. 16384 records. (dependant on number of parameters logged.) 16384 records. (dependant on number of parameters logged.) 111.5mm , 44mm (1U), 282mm overall (rack depth 260mm) 1.5kg Relay outputs, mini combicon to accept 1.5mm csa wire. Serial communications to rectifier shelf & peripheral devices - RJ45. USB port - USB mini B. -25 to +55C -50 to +85C EN55022 EN55024 3m temperature sensor and cable. 7m temperature sensor and cable. 3 phase AC voltage and current monitor. Battery condition monitor, 24 blocks. (maximum 4x BCM cards.) Standard I/O expansion board (maximum of 4 per supervisory module.) 15-75V DC <150mA maximum Connects via rectifier serial bus, 2x RJ45. Up to 8x alarm and control relays, able to be mapped for customized alarm settings. Up to 6x digital inputs. Up to 6x analogue inputs. -25 to +55C -50 to +85C Standard 1U modular controller, 3x relays, 6x digital inputs. Standard 1U modular controller, 3x relays, 6x digital inputs; with standard I/O expansion board mounted onto baseplate metalwork. Standard 1U x 19 mounting version controller, 3x relays, 6x digital inputs. Standard 1U x 19 mounting version controller, 3x relays, 6x digital inputs; with standard I/O expansion board. Standard panel mount version controller, 3x relays, 6x digital inputs. Standard panel mount version controller, 3x relays, 6x digital inputs; with standard I/O expansion board.
4 line x 16 character multi-lingual alpha numeric display. 1x USB port on front panel for local PC interface. 3x alarm and control relays, two of which can be mapped for customized alarm settings. 3x standard or 2x pulse control LVD contacts. (for magnetically latched LVD contactors) Green - power on/monitor OK. Yellow - non urgent alarm. Red - urgent alarm. 90dBA buzzer mappable to user defined conditions. 3x push buttons for parameter setting or viewing on front panel. 2x serial buses for rectifier control and interface to peripheral modules. Fuse fail. 5x spare digital inputs. 2x temperature sensors. 3x current shunts. 2x DC voltage inputs. 3x alarm relays. 0.3A 100V volts free changeover contacts. Urgent. Non-urgent. Monitor fail. 16384 records. (dependant on number of parameters logged.) 16384 records. (dependant on number of parameters logged.)
111.5mm , 44mm (1U), 282mm overall (rack depth 260mm) 1.5kg Relay outputs, mini combicon to accept 1.5mm csa wire. Serial communications to rectifier shelf & peripheral devices - RJ45. USB port - USB mini B. -25 to +55C -50 to +85C
EN55022 EN55024
3m temperature sensor and cable. 7m temperature sensor and cable. 3 phase AC voltage and current monitor. Battery condition monitor, 24 blocks. (maximum 4x BCM cards.) Standard I/O expansion board (maximum of 4 per supervisory module.) 15-75V DC <150mA maximum Connects via rectifier serial bus, 2x RJ45. Up to 8x alarm and control relays, able to be mapped for customized alarm settings. Up to 6x digital inputs. Up to 6x analogue inputs. -25 to +55C -50 to +85C
Standard 1U modular controller, 3x relays, 6x digital inputs. Standard 1U modular controller, 3x relays, 6x digital inputs; with standard I/O expansion board mounted onto baseplate metalwork. Standard 1U x 19 mounting version controller, 3x relays, 6x digital inputs. Standard 1U x 19 mounting version controller, 3x relays, 6x digital inputs; with standard I/O expansion board. Standard panel mount version controller, 3x relays, 6x digital inputs. Standard panel mount version controller, 3x relays, 6x digital inputs; with standard I/O expansion board.
ENATEL | 2010 PRODUCT CATALOGUE | 49
Input Voltage: Current: Interface Display: Communications: Serial: Relay: Indicators: Controls: Signal Inputs: Alarms: Alarm Contacts: Alarm List: Physical Dimensions W, H, D: Weight: Connections: Operating Temperature: Storage Temperature: Versions SM11-12: SM11-24: SM11-48: Accessories Temp Sensor: ACA-TC2U: ACA-TC7U: Rectifier Interface: ACA-Alarm0.5: Current Sensor: ACS-S150:
35-60V DC <85mA maximum. 6 character starburst. Interfaces with up to 6x RF series rectifiers. RS232 serial for downloading configuration files. 7x alarm and control relays. 8x LED. 3x push buttons for parameter setting on front panel. External shutdown. Fuse fail. Rectifier fail. Mains fail. Rectifier off normal. 2x voltmeter. 2x current meter. (100mV) 7x alarm relays. 1A 100V volts free changeover contacts. Off normal. Rectifier fail. Mains fail. Float high. Float low. LVD. (control line for external LVD contactor) 275mm, 44mm (1U), 104mm 0.55kg Mini combicon to accept 1.5mm csa wire. -25 to +55C -50 to +85C 12V 24V 48V
2 metre temp sensor and cable. 7 metre temp sensor and cable. 500mm RJ45 patch cable. 150 Amp 100mV shunt assembly.
The optional fan controller module allows the smart control of four 24V or 48V fans with fan stall detection.
16-75V DC 12V, 24V, 48V & 60V DC 300mA maximum per fan connection. 4x per fan controller module. (8x per system) 2x per system. The range of the SM3X temp sensor. Enatel serial bus interface. Controlled via SM3X fan fail. 90mm, 67mm, 25mm 61g
ASM-FCM4
- Compatible with SM22, SM32 or SM36 supervisory modules. - 26 voltage inputs. - 8 pairs of current inputs. - 4 temperature inputs. - Discharge logging. - Periodic logging. - Ease of installation. - Compact design.
Enatel serial bus interface. Controlled via SM22, SM32 or SM36. Voltage symmetry fault. (based on deviation from average string block measurement) Battery current imbalance. (based on deviation from average string current across all strings in system) Battery temperature high. Battery temperature low. Battery string open. (detects string voltage deviation from system DC bus to conclude battery is disconnected from system) Utilization of supervisory module memory: 15,500 data points. 196,000 data points. Actual number of discharge events stored depends on frequency of discharges, logging interval and parameters measured. 80mm , 145mm, 27mm 100g ASM-ABM-24
AC MAINS MONITOR
The AC mains monitor can be added to the SM range of supervisory modules if AC supply metering is required. - Compatible with SM range of supervisory modules. - Ease of installation. - Compact design.
Communications: Alarms: Mechanical Dimensions, W, H, D: Weight: Part Number AC Mains Mointor: Enatel serial bus interface. Controlled via SM21, SM22, SM31, SM32, SM35 or SM36. Voltage phase high, voltage phase low, voltage phase lost. (separate alarms for each phase). AC phase current high. (common alarm for all phases) Frequency high, frequency low. 145mm, 15mm, 85mm 61.5g ASM-AC3P
ENATEL | 2010 PRODUCT CATALOGUE | 51
nSURE NS300-12
For the SOHO Client Enatels nSURE NS300-12 can provide long term backup for all their communications needs. SOHO (Small Ofce/Home Ofce) clients with security systems will need Enatels nSURE NS300-12 power supply. Couple into this the ONU, Security system, residential gateway and wireless router and it can be business as usual from a laptop during an AC outage. The NS300-12 is wall mountable and convection cooled making it ideal for ofce locations. - 12V, 300W output.
- Mains fail alarm. - Convection cooled. - Wall mountable. - Automatic oat/boost charge cycle. - Power factor corrected. - Thermally protected. - Input/output voltage and current protected.
nSURE NS30-12
To suit the residential needs Enatel offers the nSURE NS30-12 (with integrated battery) for basic autodialer backup functionality. For home owners with alarm auto dialers FTTH means their alarms will not be monitored in the event of an AC Outage. Enatels nSURE NS30-12 provides battery backed power to the ONU even when the lights go out. Security or Nurse call devices will operate as normal. - Telecom grade 12V DC (30W max.) output. - Up to 8 hours* of standby battery backup. - Flexibility of wall or desktop mount. - Easy user replaceable battery without power interruption. - Microprocessor based intelligent control. - Cold start capable. - Local audible and visual indicators with remote alarms. - Optional extended runtime.
- World leading power density. - Fully featured telecom grade rectiers. - Network monitoring available. - Modular 19/515mm ETSI design for ease of installation. - High reliability means less cost of maintenance. - Full remote monitoring available means less site visits and less cost. suit each customers individual needs. - Easily customized and congured to
AC POWER SOLUTIONS
As some FTTX equipment is AC powered Enatel can also offer integrated DC-AC Inverters, this allows for a telecommunications grade UPS (Long backup times) on the entire FTTX system. The Inverters are monitored and controlled through the same controller as the rest of the DC Power system. Enatel can supply the complete solution in a wall mount cabinet or ready to integrate into the OLT/ONU mounting system.
52 | ENATEL | 2010 PRODUCT CATALOGUE
DC Output Nominal Voltage: Rated System Output Power: Polarity: DC Distribution: Load: Battery: 2x 10A, 2x 20A load circuit breakers. 2x 30A battery circuit breakers.
Supervisory Module
-48V 2400W max. (50A @ -48V; 44.4A @ -54.0V) Positive earth. (negative earth available to special order).
48 2.4
SM36
RM848 RM848 RM848
kW
6mm push-in spring cage. 55A power-pole plug-in connectors.. 50A battery LVD (magnetically latching) fitted as standard.
Mechanical Dimensions, W,H,D: Weight: 482.6mm (standard 19 module), also fits ETSI 515mm mounting cabinet, 44.45mm (1U, 1.75), 285mm (11.6) 5kg (excluding rectifier modules)
Shipping Dimensions, W,H,D: 540mm, 95mm, 400mm Weight: 6kg (excluding rectifier modules)
Various monitoring options are available via the Enatel SM35/36 series of control & supervisory modules. Standard features include full temperature compensation, automated and manual battery testing/ equalisation, 6x general purpose inputs and 6x voltage-free relay alarm outputs. For further details, refer to the SM35/36 series of brochures.
Accessories ACA-BC08P2: 2m, 8mm battery cable kit. (other lengths available to special order)
Actual part numbers will vary with configuration. Micro compact system, 2x 800W 48V rectifiers, 6x load 2x battery MCBs, front termination, SM35 supervisory module. Micro compact system, 2x 800W 48V rectifiers, 6x load 2x battery MCBs, front termination, SM36 supervisory module. Micro compact system, 3x 800W 48V rectifiers, 4x load 2x battery MCBs, front termination, SM35 supervisory module. Micro compact system, 3 x 800W 48V rectifiers, 4x load 2x battery MCBs, front termination, SM36 supervisory module.
ENATEL | 2010 PRODUCT CATALOGUE | 53
nSURE NS300-12
12 300
nominal output voltage.
AC Input Nominal: Voltage Range: Frequency Range: Power Factor: Efficiency: Input Fuses: Maximum Input Current: Protection: Input Voltage: Input Rush: DC Output Nominal Voltage: Rated Voltage: Voltage Range: Maximum Current: Regulation: Line: Load: Hold-up Time: Start-up Time: Protection: Current Limit: Over Temp: Polarity Reversal: Over Voltage: Noise: (under nominal conditions) Ripple <100Hz: Voice Band 100Hz to 5KHz: Wide Band 5kHz to 1 MHz: Peak to Peak 0 to 20MHz: Isolation: Input to Output: Input to Chassis: Output to Chassis: Environmental Requirements Nominal Ambient Temperature: Range: Humidity: Altitude: Mechanical Dimensions, W, H, D: Weight: Shipping Dimensions, W, H, D: Shipping Weight: Cooling: Connections: Mains: Output to Load: Output to batteries: Standard Features Auto Float/Boost: Alarm and Indicator Controls: Compliances: Safety: EN60950 Electrostatic Discharge: Radiated Radio Frequency: AC Harmonics: AC Flicker and Fluctuation:
110/220V, 50/60Hz 100-275V AC (full power output), 85-100V AC (reduced power output) 45-66Hz >0.99 (full load) 85% HRC Fuses in phase & neutral. 4A Automatic shutdown, restarts automatically when correct voltage restored. <2x maximum input current.
12V 14.5V 11.5-15V 20A 0.1% 0.5% (no load to full load) >15ms for 20% output voltage drop. Walk-in delay 2 seconds (depends on AC input voltage) Adjustable to 50-100% of maximum rated current. Automatic current turndown, backup shutdown protection. Output fuse with crowbar diode. Adjustable limit. <5mV rms unweighted. <0.5mV rms psophometric. <2.5mV rms unweighted. <50mV p-p unweighted. 3000V AC 2500V AC (VDR to chassis removed.) 1500V AC
25+/-5C -10 to +60C 5-95% RH (non-condensing) <2500m de-rate maximum ambient temperature by +4 per 1000m above sea level.
311mm, 163mm, 62mm 1.5kg 377mm, 235mm, 122mm 2.4kg Convection cooled. IEC 320 universal connection. 4 way lumberg macromodule. 4 way lumberg macromodule.
Rectifier enters boost mode at power up. When battery current reduces to float threshold limit (adjustable from 0.1A to 40% MRC), unit reverts to float voltage setting. When in boost but out of current limit, rectifier will automatically switch back to float after approximately four hours. If battery current exceeds the float threshold limit when the rectifier is in float mode it will automatically switch to boost mode. Open collector rectifier fail (via 4k7 resistor), Open collector mains fail.
nSURE NS30-12
Input Nominal Input Voltage: Voltage Range: Frequency Range: Plug Type: IEC inlet. 120V AC/230V AC 80-260V AC 45Hz-65Hz
Output Output Power (Max): Normal Voltage: Output Voltage Range: Line Mode Efficiency: 30W/2.2A 12V DC 10.5-13.8V DC >80%
12 30
Battery Type/Rating: Discharge Prevention: Rated Charging Voltage: Recharge Time (Internal Battery): Charge Current: Hot Swappable Battery: 12V/7Ah x 1pc (12V/9Ah option) 10.5V 0.5V 13.7V 0.25 4 hours to 90% without load after discharge. 2.5A maximum. Yes.
Indicators AC Mode: Backup Mode: Battery Low: Battery Replace: Battery Missing: Fault: Battery Self Test: Solid green LED. Solid yellow LED. Flashing yellow LED. Flashing red LED. Flashing red LED. Flashing red LED. Flashing green LED.
Audible Alarm Backup Mode: Battery Low: Battery Replace: Battery Missing: Fault: Mute Function: 5 seconds. 1 second. 2 seconds. Continuous. Continuous. Switch. (on/off)
Environment Operating Temperature: Operating Humidity: Operating Elevation: 0 to 40C 0 to 90% 0 to 3000m
INDUSTRIAL SOLUTIONS
- World leading power density. - Fully featured telecom grade rectiers. Systems are congured using Enatels state of the art high frequency switch mode rectier modules, intelligent network capable controllers, AC & DC distribution modules, and cabinets, and can be customized and congured to meet individual customer requirements. For details on a Enatel power system that meets your requirements contact us. - Network monitoring available. - Modular 19 design for ease of installation. - Includes AC surge protection. - More room for revenue creating equipment. to higher power. of maintenance. means less site visits and less cost. - Upgrade existing systems - High reliability means less cost - Full remote monitoring available - Cost competitive. - Suitable for more harsh environments. Based on our proven range of modular telecom power solutions, we have developed a range of solutions for use in 110V DC industrial applications.
DC Output Nominal Voltage: Rated Voltage: Rated System Output Power: Polarity: 121.5V 80-155V DC
Supervisory Module
110 6.0
SM34
kW
AC Input
Load
Battery
compact
ULTRA
HV
DC Distribution: Load: 1x 63A 2 pole load MCB (breaks +ve & -ve) 35mm tunnel terminals at rear. 1x 63A 2 pole battery MCB (breaks +ve & -ve) 35mm tunnel terminals at rear. Auxiliaries on both load and battery breakers. Configurable via software, factory set at 25mA
Battery:
Mechanical Dimensions, W, H, D: Weight: 482.6mm (standard 19 module), 89mm (1U, 3.5), 415mm (16.3) 7.5kg (excluding rectifier modules)
Shipping Dimensions, W, H, D: 530mm, 154mm, 430mm Weight: 9kg (excluding rectifier modules)
Various monitoring options are available via the Enatel SM33/34 series of control & supervisory modules. Standard features include full temperature compensation, automated and manual battery testing/equalisation and three voltage-free relay alarm outputs.
Actual part numbers will vary with configuration. 2U HV Ultra Compact Power System including standard SM33 supervisory module. 2U HV Ultra Compact Power System including standard SM34 supervisory module.
ENATEL | 2010 PRODUCT CATALOGUE | 57
110 3.0
nominal output voltage. maximum output power.
AC Input:
Single phase with surge protection and input 32A MCB (refer to rectifier brochure for full details) 45-66Hz >0.99 (full load) Single phase. Direct MCB termination for L. 10mm N, E tunnel terminals.
Frequency Range: Power Factor: Termination: Max Rated System Output Power: Polarity:
kW
110V (80-155V DC) 3000W @ 120V DC, 27A max. Isolated output. 1x RM30110 3000W rectifier.
DC Distribution: Load: Battery: 1x 63A 2 pole MCB. 1x 63A 2 pole MCB. Auxiliaries. Live: Direct MCB connections.
Weight: Dimensions, D, H, W:
Various monitoring options via the Enatel SM30 series of control & supervisory modules. Standard features include full temperature compensation, automated and manual battery testing/equalisation and three voltage-free relay alarm outputs. For further details, refer to the SM30 series of brochures.
Actual part numbers will vary with congifuration. Wall mount charger including standard SM33 supervisory module. Wall mount charger including standard SM34 supervisory module.
230V 90-300V (reduced power below 175V) 45-65 Hz >0.99 >92% (>45% output power) HRC fuses in phase and neutral. 19A Auto shutdown, auto restart when correct voltage restored. <2x maximum input current.
DC Output Output Ratings: Constant Current: 80-110V DC (27.3A) Constant Power: 110-155VD C (3.0kW) Nominal Voltage: 120V Rated Voltage: 145V Voltage Range: 80-155V Maximum Current: 27.3A Regulation: Line: 0.1% 0.5% (no load to full load) Load: Hold-up Time: >15ms for 20% output voltage drop. Start-up Time: Start up delay 1 second. (varies with AC supply voltage) Walk-in delay 6 seconds at full output. (varies with DC output voltage) Protection: Current Limit: Adjustable to 50-100% of maximum rated current. Automatic current turndown, backup shutdown protection. Over Temperature: Polarity Reversal: Output fuse with crowbar diode. Over voltage: Adjustable limit. Noise: (under nominal conditions) Ripple <100Hz: <1mV rms unweighted. Voice band 100Hz-5KHz: <2mV rms psophometric. Wide band 5kHz-1MHz: <5mV rms unweighted Peak to Peak 0-20MHz: <200mV peak to peak. Isolation: Input to Output: 4000V DC Input to Chassis: 3500V DC (VDR to chassis removed) Output to Chassis: 2100V DC Environmental Requirements Ambient Temperature: Nominal: Range: Storage Temperature: Humidity: Altitude:
kW
25+/-5C -10C to +70C (maximum output power is derated above +50C) -20C to +70C 5-95% RH (non-condensing) <2500m, De-rate maximum ambient temperature by 4C per 1000m above sea level.
Mechanical Dimensions, W, H, D: 41mm, 220mm, 305mm overall. Weight: 2.8kg Shipping Dimensions W, H, D: 52mm, 230mm, 340mm Shipping Weight: 2.95kg Cooling: Forced cooled, using dual temperature controlled high reliability fans. Compliances Safety: Electrostatic Discharge: Radiated Radio Frequency: AC Harmonics: AC Flicker and Fluctuation: Other:
Input Voltage: Current: Interface Display: Communications: Serial: Relay: TCP/IP: LVD: 1x USB port on front panel for local PC interface. 1x RS232 port, rear mounted for remote serial/modem communications. 3x alarm and control relays, two of which can be mapped for customized alarm settings. Ethernet interface for communication using SNMP protocol and internal web based configurator. 3x standard or 2x pulse control LVD contacts. (for magnetically latched LVD contactors) Green - power on/monitor OK. Yellow - non urgent alarm. Red - urgent alarm. 90dBA buzzer mappable to user defined conditions. 3x push buttons for parameter setting or viewing on front panel. Serial bus for rectifier control and interface to peripheral modules. Fuse fail. 5x spare digital inputs. 2x temperature sensors. 3x current shunts. 2x DC voltage inputs. 3x alarm relays. 0.3A 100V volts free changeover contacts or 0.15A 160V volts free changeover contacts. Urgent. Non-urgent. Monitor fail. 16384 records. (dependant on number of parameters logged.) 16384 records. (dependant on number of parameters logged.) 4 line x 16 character multi-lingual alpha numeric display. 80-160V DC <50mA maximum.
Indicators: 3x LEDs Audible: Controls: Signal Inputs: Alarms: Alarm Contacts: Default Alarm Map: Logging Capacity: Periodic Log: Event Log:
Physical Dimensions, W, H, D: Weight: Connections: Operating Temperature: Storage Temperature: Compliances Radiated Emissions: RF Susceptibility: Optional Accessories ACA-TC3C: ACA-TC3C: ASM-AC3P110: ASM-ABM-24: Part Numbers SM34-00: SM34-00-1U: SM34-00-PM:
60 | ENATEL | 2010 PRODUCT CATALOGUE
111.5mm , 44mm (1U), 282mm overall (rack depth 260mm) 1.5kg Relay outputs, mini combicon to accept 1.5mm csa wire. Serial communications to rectifier shelf & peripheral devices - RJ45. USB port - USB mini B. -25 to +55C -50 to +85C
EN55022 EN55024
3m temperature sensor and cable. 7m temperature sensor and cable. 3 phase AC voltage and current monitor. Battery condition monitor, 24 blocks. (maximum 4x BCM cards.)
Standard 1U modular controller, 3x relays, 6x digital inputs. Standard 1U x 19 mounting version controller, 3x relays, 6x digital inputs. Standard panel mount version controller, 3x relays, 6x digital inputs.
Indicators: 3x LEDs Audible: Controls: Signal Inputs: Alarms: Alarm Contacts: Default Alarm Map: Logging Capacity: Periodic Log: Event Log:
Physical Dimensions, W, H, D: Weight: Connections: Operating Temperature: Storage Temperature: Compliances Radiated Emissions: RF Susceptibility: Optional Accessories ACA-TC3C: ACA-TC7C: ASM-AC3P110: ASM-ABM-24: Part Numbers SM33-00: SM33-00-1U: SM33-00-PM: Standard 1U modular controller, 3x relays, 6x digital inputs. Standard 1U x 19 mounting version controller, 3x relays, 6x digital inputs. Standard panel mount version controller, 3x relays, 6x digital inputs.
ENATEL | 2010 PRODUCT CATALOGUE | 61
111.5mm , 44mm (1U), 282mm overall (rack depth 260mm) 1.5kg Relay outputs, mini combicon to accept 1.5mm csa wire. Serial communications to rectifier shelf & peripheral devices - RJ45. USB port - USB mini B. -25 to +55C -50 to +85C
EN55022 EN55024
3m temperature sensor and cable. 7m temperature sensor and cable. 3 phase AC voltage and current monitor. Battery condition monitor, 24 blocks. (maximum 4x BCM cards.)
Copyright Enatel Limited 2010. Due to product development specications are subject to change without prior notice. Pictures may be representative, actual products may differ.