Air source, water source and brine source heat pumps optimized for geothermal applications

From environment the energy to protect it.

2010

From

environment
the energy to protect it.

Climaveneta introduces Prana, the heat pumps range developed in order to emulate with the highest sustainability and efficiency the heating requirements of residential, small and medium office buildings, employing renewable energy directly from nature, such as air, water or ground

A range that stems from the awareness of the growing attention to costs and environmental impact of heating solutions, combined with Climaveneta's thirty years experience in comfort and air-conditioning. In fact, heat pumps work very similarly to chillers, transferring thermal energy from a source to the rooms where it is required, using water as exchange fluid. External air, water courses or underground water or simply ground, are from this point of view, huge energy sources, available all the year round, for free and with no environmental impact.

Prana heat pumps, thanks to the advanced technological choices featuring them, are designed to get from these sources the energy necessary for heating, ensuring also in particularly harsh climates, and efficiency and sustainability unconceivable for traditional gas-boiler systems.

This solutions blends harmony with environment and cutting edge technology for comfort and system design in order to assure concrete advantages such as:
Integration with other renewable or existing system using always the most efficient. All models can be integrated with the existing heating system, with thermal or photovoltaic solar systems, and with biomasses systems. Free domestic hot water. All units supply domestic hot water as priority. DHW models, thanks to the exclusive total heat recovery system supply free domestic hot water. Tremendous and practical form of renewable energy All Prana units are electrically supplied with no emissions, no gas or fossil fuel usage.

Index
Prana i-NRG
pg. 06

Prana WWR MTD

pg. 16

Prana BWR MTD

pg. 24

Reversible heat pump with inverter compressor, total heat recovery, air source for indoor/outdoor installation 17,8 kW

Reversible heat pump, water source 7,2 43,8 kW

Reversible heat pump, geothermal source 5,4 33,3 kW

Prana AWR DHW

pg. 08

Prana Slim WWR HT

pg. 18

Prana Slim BWR HT

pg. 26

Reversible heat pump, total heat recovery, air source for outdoor installation 7,7 33,5 kW

Reversible heat pump, water source, high water temperature with buffer tank 8,3 14,1 kW

Reversible heat pump, geothermal source, high water temperature with buffer tank 6,2 10,6 kW

Prana AWR MTD 1


Reversible heat pump, air source for outdoor installation 6,9 17,4 kW

pg. 10

Prana Cube WWR HT

pg. 20

Prana Cube BWR HT

pg. 28

Reversible heat pump, water source, high water temperature 8,3 35,9 kW

Reversible heat pump, geothermal source, high water temperature 6,2 27,0 kW

Prana AWR MTD XE

pg. 12

High efficiency reversible heat pump, air source for outdoor installation 6,3 17,9 kW

Prana WWR DHW

pg. 22

Prana BWR DHW


Reversible heat pump, total heat recovery, geothermal source 4,5 29,7 kW

pg. 30

Reversible heat pump, total heat recovery, water source 6,0 40,5 kW

Prana AW HT
Heat pump, air source for outdoor installation, high water temperature 10,4 19,7 kW

pg. 14

Air source solutions

Range overview

2010
Prana HT
High temperature units optimized for heating and domestic hot water supply as priority. Air / Water units assure hot water production at 65C, can be employed with ideal results also with radiant plates heating systems and down to -20C external air temperature. Water source solutions produce water up to 60C, are available with integrated boiler (Slim model) or without boiler (Cube model). They are reversible, being therefore a great solution also for air conditioning during summer.

Prana air source heat pumps transfer the heat from the external air using water as exchange fluid. Simplified installation.

AW HT
High temperature air source heat pump for water heating up to 65C, and operating limits down to -20 external air temperature

Prana MTD
Reversible medium temperature units for hot water production up to 55C and domestic hot water as priority. Ideal for heating and cooling with one single unit, they are particularly suitable for radiant systems. Available as both water source, or geothermal, models (Water), and air source models (Air), with operating limits down to -15C external air temperature.

AWR MTD 1
Medium temperature air source reversible heat pump for water heating up to 55C

AWR MTD XE
Medium temperature air source reversible heat pump for water heating up to 55C and operating limits down to -15C external air temperature

Prana DHW
Reversible units supplying simultaneous heating, or cooling, and domestic hot water. Total heat recovery system assures free domestic hot water supply during summer mode. DHW units are available both as air source models (Air) and water source, or geothermal, models (Water). They are provided with integrated valves, circulator and heat exchangers, for a simplified installation and a significant reduction of the plant costs.

AWR DHW
Air source reversible heat pump with domestic hot water supply with total heat recovery.

Reversible heat pump with inverter compressor, total heat recovery, air source for indoor/outdoor installation

Water source solutions


Prana water source heat pumps use water from aquifer. Highest energy efficiency

Geothermal solutions
Prana geothermal heat pumps transfer the heat from the earth through horizontal or vertical probes. Highest energy efficiency Lowest environmental impact

WWR HT Slim
High temperature heat pump, water source for water heating up to 60C, reversible

BWR HT Slim
High temperature heat pump, geothermal source, for water heating up to 60C, reversible

WWR HT Cube
High temperature heat pump, water source for water heating up to 60C, reversible

BWR HT Cube
High temperature heat pump, geothermal source, for water heating up to 60C, reversible

WWR MTD
High temperature air source heat pump for water heating up to 65C, and operating limits down to -20 external air temperature

BWR MTD
Medium temperature geothermal reversible heat pump for water heating up to 55C

WWR DHW
Water source reversible heat pump with domestic hot water supply with total heat recovery

BWR DHW
Geothermal reversible heat pump with domestic hot water supply with total heat recovery

i-NRG

Versions
i-NRG Reversible heat pump with inverter compressor, total heat recovery, air source for indoor/outdoor installation

Unit description
The new i-NRG heat pump provides exactly the energy required by the system, perfectly following the real load of the building, thanks to the modulation of the DC inverter fan. One single unit for the highest efficiency, sustainability and huge savings, thanks to the advantages of DC frequency driven fans and circulating pumps (inverter) for both plant and domestic hot water circuits. i-NRG is the new generation heat pump for all year round operation in any operating mode: single cycle (air conditioning, heating, domestic hot water) as well as combined cycle (domestic hot water together with heating or cooling). Domestic hot water production is guaranteed by the dedicated exchanger for heat recovery: total, for free domestic hot water production, or partial. Domestic hot water is stored in a properly dimensioned storage tank. The unit can be installed indoor or outdoor, thus ensuring complete flexibility.

Commands
Electronic control provides great application flexibility. The remote keyboard kit wired indoor and outdoor temperature sensors allow dynamic control of delivery temperature water, optimizing comfort in the room and increasing the energy efficienty. The electronic board allows you to manage: - a zone of direct heating for radiator, floor heating or fan coil - zone with mix valve for floor heating - outdoor temperature sensor for water plant side modular set point compensation - electrical heating element for possible integration and anti-legionellosis cycle for cylinder - boiler in substitution or in additional - integration by solar panels with extension module (accessorie) - several solutions through appropriate configurations of the controller and use of dedicated extension modules (accessories)

Features
Structure and base in hot galvanised epoxy powder coated steel. Stainless steel (AISI 316) with high efficiency and low pressure drop plate to plate exchanger (at the domestic hot water side). It is positioned next after the compressor, it ensures the domestic hot water production. That can work either in full recovery or in part, with the constant optimization of efficiency through logic advanced adjusting controller Exchangers plant side plate of stainless steel AISI 316 with high efficiency and low pressure drop meets the supply of both hot or cold water for the facility, regardless of the domestic hot water DC inverter scroll compressor with self-adaptive capacity adjustment. Electronic expansion valve Finned coils made with copper pipes and aluminium fins with large exchange surface area (100% fully quality tested) Axial electric fan in continuous current housed in aerodynamic conveyor profile with safety grill. Low external air temperature device: continuous fan speed regulation with pressure switch The water circuit comes complete with: - Variable flow circulating pump in continuous current, plant side. - Variable flow circulating pump in continuous current, hot water side. - Expansion tank. - Safety valve. - Pressure gauge. - Manual filling assembly.

Main accessories
Room terminal with temperature probe Wall temperature sensor Wall humidity sensor Expansion module for plant circuits additional Expansion module for solar thermal collector Buffer tank 35,100,200 liters Hot water cylinder 300,500 liters 300 litres thermal store for domestic hot water, for kit DOMH2O 300, 500, 1000 litres thermal store for domestic hot water with solar heat exchanger, for kit DOMH2O DOMH2O15 e DOMH2O24 kit for domestic hot water with external heat exchanger plate-to-plate and pump Removable metal mesh water filter kit

Reversible heat pump with inverter compressor, total heat recovery, air source for indoor/outdoor installation 17,8 kW

r HFC R-410A
AXIAL

i-NRG
Nominal heating power Total absorbed power COP EN 14511 Cooling capacity Total absorbed power EER EN 14511 Cooling capacity with total recovery Total absorbed power Recovery heating capacity Compressor type N. Compressors Refrigerant N. fans Plant side pump type Recovery side pump type Electrical power supply DIMENSION L L H P Operational weight (8) (9) mm mm mm mm kg (5) (5) V-Ph~Hz N. N. (4) kW kW kW (3) (2) kW kW (1) (2) kW kW

0061
17,8 4,46 3,93 20 5,44 3,64 19 5,5 24,1 SCROLL INVERTER DC 1 R410A 1 i-Ci i-Ci 230-1~50 750 1535 1600 1050 320

Note
I-NRG

(1) Water in-out 30/35C (plant side), outdoor air temperature 7C b.s./ 6C b.u. (2) Total input is obtained from compressor input and fan input. (3) Water in-out 23/18C (plant side), outdoor air temperature 35C b.s. (4) Water in-out 23/18C (plant side), water in-out 45/50C (total recovery side) (5) i-Ci= Circolatore inverter corrente continua

(6) Sound power level according to ISO 9614 and Eurovent 8/1 (7) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the outside dimensions of the unit. (8) Indoor installation (9) Outdoor installation

P L (8) L (9)

AWR DHW

Versions
AWR DHW Air source reversible heat pump with domestic hot water supply with total heat recovery.

AWR DHW - SL Air source reversible heat pump with domestic hot water supply with total heat recovery.

Unit description
PRANA DHW is the heat pump new generation able to operate throughout the year in any operating mode: either a single cycle (cooling, heating, hot water) and combined cycle (hot water along with air conditioning or heating). Energy efficiency is highest during the summer cycle, when, thanks to the full recovery of the heat, the production of hot water is free. During the combined use, the DHW exchanger uses the temperature of the discharge gases to gets inside the accumulation sanitary water as high as 65 C. The advanced electronic regulation developed by Climaveneta ensures the highest operational flexibility, fast working condition a significant increase in the overall COP, which go hand in hand with electricity and space reduction. Advantages, combined with the possibility of completely eliminating the traditional boiler, making heat pumps PRANA DHW the ideal solution for energy saving applications in residential, hotel and small sector.

Commands
AWR-DHW heats water stored in the tank as energy storage. It also comes with a state-of-the-art electronic unit, which independently controls the modes of operation. The appliance can operate throughout the year in any mode, both with single cycle (cooling, heating, hot water) and with combined cycle (hot water together with cooling or hot water together heating).During the summer cycle there is maximum energy saving through total heat recovery. This energy is completely free of charge with regard to the production of hot water.

Features
Structure and base in hot galvanised epoxy powder coated steel. Stainless steel (AISI 316) with high efficiency and low pressure drop plate to plate exchanger (at the domestic hot water side). It is positioned next after the compressor, it ensures the domestic hot water production. That can work either in full recovery or in part, with the constant optimization of efficiency through logic advanced adjusting controller. Exchangers plant side plate of stainless steel AISI 316 with high efficiency and low pressure drop meets the supply of both hot or cold water for the facility, regardless of the domestic hot water Hermetic scroll type compressors, equipped with the crankcase heater and thermal protection Finned coils made with copper pipes and aluminium fins with large exchange surface area (100% fully quality tested) Axial electric fans, external rotor, electric motor with a 6-pole fitted with thermal protection, housed in aerodynamic conveyor profile with safety grill Low external air temperature device: continuous fan speed regulation with pressure switch Coil protection grille Soft starter for 230V units /ms and 400V units /ts The water circuit comes complete with: - Variable flow circulator for 00210025 models and multistage centrifugal variable flow pump for models 00410101, plant side - Domestic hot water side water pump - Expansion tank - Safety valve - Manual filling assembly - Pressure gauge - Air vent valve Comando accessibile dallesterno con dispositivo antimanomissione

Main accessories
Buffer tank 35,100,200 liters Hot water cylinder 300,500 liters 300 litres thermal store for domestic hot water, for kit DOMH2O 300,500,1000 litres thermal store for domestic hot water with solar heat exchanger, for kit DOMH2O DOMH2O15 e DOMH2O24 kit for domestic hot water with external heat exchanger plate-to-plate and pump Remote keyboard Rubber anti-vibration mounting kit Removable metal mesh water filter kit Condensate collecting tray for models 00650101

Reversible heat pump, total heat recovery, air source for outdoor installation 7,7 33,5 kW

r HFC R-407C
AXIAL

AWR DHW
Nominal heating power Total absorbed power COP Cooling capacity Total absorbed power EER Cooling capacity with total recovery Total absorbed power Recovery heating capacity Heating capacity Total absorbed power COP Cooling capacity Total absorbed power EER Compressor type N. Compressors Refrigerant N. fans Plant side pump type Recovery side pump type Electrical power supply Start-up current Sound power Sound pressure level DIMENSION L H P Operational weight mm mm mm kg (8) (9) (7) (7) V-Ph~Hz A dB(A) dB(A) N. N. (6) (2) (5) (2) (4) (3) (2) (1) (2) kW kW * kW kW * kW kW kW kW kW * kW kW *

0021m
7,70 2,30 3,35 7,60 2,40 3,17 7,40 2,30 9,60 7,60 2,90 2,66 5,40 2,40 2,25

0025m
9,10 2,70 3,37 8,90 2,70 3,30 8,50 2,70 11,0 9 3,40 2,68 6,30 2,70 2,33

0041m 0021ms 0025ms 0041ms


13 3,70 3,51 12,7 3,80 3,34 11,8 4 15,5 12,8 4,60 2,78 9,10 3,70 2,46 7,70 2,30 3,35 7,60 2,40 3,17 7,40 2,30 9,60 7,60 2,90 2,66 6,40 2,40 2,25 9,10 2,70 3,37 8,90 2,70 3,30 8,50 2,70 11,0 9 3,40 2,68 7,30 2,70 2,33 13 3,70 3,51 12,7 3,80 3,34 11,8 4 15,5 12,8 4,60 2,78 11,2 3,80 2,46

0025t
9,10 2,70 3,37 8,90 2,70 3,30 8,40 2,60 10,9 9,10 3,40 2,68 6,30 2,70 2,33 1

0041t
13 3,70 3,51 12,7 3,80 3,34 11,9 4 15,6 12,9 4,60 2,81 9,00 3,60 2,50

0065t
21,3 5,60 3,80 21,1 5,80 3,64 18,2 6,10 23,9 20,9 7 2,99 15,1 5,40 2,80

0101t
33,5 8,50 3,94 33 9,40 3,51 33,1 9,40 42,0 32,6 10,3 3,17 23,7 9,00 2,63

0025ts
9,10 2,70 3,37 8,90 2,70 3,30 8,40 2,60 10,9 9,10 3,40 2,68 7,30 2,70 2,33

0041ts
13 3,70 3,51 12,7 3,80 3,34 11,9 4 15,6 12,9 4,60 2,81 11,2 3,80 2,50

0065ts
21,3 5,60 3,80 21,1 5,80 3,64 18,2 6,10 23,9 20,9 7 2,99 17 5,90 2,80

0101ts
33,5 8,50 3,94 33 9,40 3,51 33,1 9,40 42,0 32,6 10,3 3,17 27,7 9,50 2,63

SCROLL R407C 2 Ci Ci 230-1~50 61 68 53 1125 1125 370 144 2 Ci Ci 230-1~50 78 69 54 1125 1125 370 144 2 Ce Ci 230-1~50 114 70 55 1250 1125 420 168 2 Ci Ci 230-1~50 29 68 53 1125 1125 370 144 2 Ci Ci 230-1~50 34 69 54 1125 1125 370 144 2 Ce Ci 230-1~50 45 70 55 1250 1125 420 168 2 Ci Ci 40 69 54 1125 1125 370 144 2 Ce Ci 50 70 55 1250 1125 420 168 1 Ce Ci 101 76 60 1700 1200 650 295 2 Ce Ci 127 77 61 1700 1700 650 378 2 Ci Ci 22 69 54 1125 1125 370 144 2 Ce Ci 28 70 55 1250 1125 420 168 1 Ce Ci 56 76 60 1700 1200 650 295 2 Ce Ci 70 77 61 1700 1700 650 378

400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50

AWR DHW SL
Nominal heating power Total absorbed power COP Cooling capacity Total absorbed power EER Cooling capacity with total recovery Total absorbed power Recovery heating capacity Heating capacity Total absorbed power COP Cooling capacity Total absorbed power EER Compressor type N. Compressors Refrigerant N. fans Plant side pump type Recovery side pump type Electrical power supply Start-up current Sound power Sound pressure level DIMENSION L H P Operational weight mm mm mm kg (8) (9) (7) (7) V-Ph~Hz A dB(A) dB(A) N. N. (6) (2) (5) (2) (4) (3) (2) (1) (2) kW kW * kW kW * kW kW kW kW kW * kW kW *

0065t
21,3 5,60 3,80 21,1 5,80 3,64 18,2 6,10 23,9 21 7,10 2,97 15,2 5,30 2,87 SCROLL 1 R407C 2 Ce Ci 400-3N~50 101 73 57 1700 1200 650 295

0101t
33,5 8,50 3,94 33 9,40 3,51 33,1 9,40 42,0 32,9 10,5 3,15 23,9 8,80 2,72 SCROLL 1 R407C 3 Ce Ci 400-3N~50 127 74 58 1700 1700 650 378

0065ts
21,3 5,60 3,80 21,1 5,80 3,64 18,2 6,10 23,9 21 7,10 2,97 15,2 5,30 2,87 SCROLL 1 R407C 2 Ce Ci 400-3N~50 56 73 57 1700 1200 650 295

0101ts
33,5 8,50 3,94 33 9,40 3,51 33,1 9,40 42,0 32,9 10,5 3,15 23,9 8,80 2,72 SCROLL 1 R407C 3 Ce Ci 400-3N~50 70 74 58 1700 1700 650 378

Note
AWR DHW

(1) Water in-out 30/35C (plant side), outdoor air temperature 7C b.s./ 6C b.u. (2) Total input is obtained from compressor input and fan input (3) Water in-out 23/18C (plant side), outdoor air temperature 35C b.s. (4) Water in-out 23/18C (plant side), water in-out 45/50C (total recovery side) (5) Water in-out 40/45C (plant side), outdoor air temperature 7C b.s./ 6C b.u. (6) Water in-out 12/7C (plant side), outdoor air temperature 35C b.s.

(7) Ci=Circolatore; Ce=Centrifuga (8) Sound power level according to ISO 9614 and Eurovent 8/1 (9) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the outside dimensions of the unit. * secondo Eurovent

P L

AWR MTD1

Versions
AWR MTD1 Medium temperature air source reversible heat pump for water heating up to 55C

Unit description
Heat pumps AWR-MTD1 are reversible outdoor units with axial fans, hermetic scroll compressors and Full Floating technology. Full Floating is advanced electronics which has been developed by CLIMAVENETA in order to meet the needs of typical residential small size and small/medium tertiary sector, thanks to the accumulation. Another advantage that, together with the Hydraulic module components it make extremely simple the installation of heat pump: simply by connecting the unit to water plant and electricity so that it can be put into operation.

Commands
The new generation electronic controller allows to manage the heat pump by using the Full Floating technology, designed by Climaveneta for improving the systems efficiency for the fans (Floating Fans), for the circulating pump (Floating Flow) and finally for the working temperature (Floating Setpoint). This also allows to achieve all the following benefits: chiller operation even with larger operating limits, improvement of efficiency in both standard and extreme conditions, much lower operating noise in part load conditions, lower installation time, lower time for system set-up, broader operating limits, faster transient after defrosts. The electronic menu allows to manage: - domestic hot water production by external three-way valve (accessory) - a zone of direct heating - outdoor temperature sensor for water plant side modular set point compensation - electrical heating element for possible integration and anti-legionellosis cycle for cylinder - boiler or electric heater management

Features
Structure and base in hot galvanised epoxy powder coated steel. High efficiency and low pressure drop stainless steel (AISI 316) water exchangers complete with closedcell insulation with vapour barrier,antifreeze heating element and differencial pressure switch Hermetic scroll type compressors, equipped with the crankcase heater and thermal protection Finned coils made with copper pipes and aluminium fins with large exchange surface area (100% fully quality tested) Axial electric fans, external rotor, electric motor with a 6-pole fitted with thermal protection, housed in aerodynamic conveyor profile with safety grill Low external air temperature device: - continuous fan speed regulation with pressure switch Condensate collecting tray Coil protection grille Soft starter for 230V/1/50Hz units The water circuit comes complete with: - Variable flow circulator for all models - Water side differential pressure switch - Expansion tank - Safety valve - Manual filling assembly - Pressure gauge - Air vent valve Control with foolproof device accessible from the outside

Main accessories
Three-way valve for domestic hot water Buffer tank 35,100,200 liters Hot water cylinder 300,500 liters 300 litres thermal store for domestic hot water, for kit DOMH2O 300,500 litres thermal store for domestic hot water with solar heat exchanger, for kit DOMH2O Kit boiler control DOMH2O15 e DOMH2O24 kit for domestic hot water with external heat exchanger plate-to-plate and pump 1,2,3 kw single-phase electric heater kit External buffer tank and hydronic connecting kit Removable metal mesh water filter kit Rubber anti-vibration mounting kit HSW11 Remote keyboard

10

Reversible heat pump, air source for outdoor installation 6,9 17,4 kW

r HFC R-410A
AXIAL

AWR MTD1
Nominal heating power Total absorbed power COP Eurovent Cooling capacity Total absorbed power EER Eurovent Heating capacity Total absorbed power COP Eurovent Cooling capacity Total absorbed power EER Eurovent ESEER Compressor type N. Compressors Refrigerant N. fans Plant side pump type Electrical power supply Start-up current Sound power Sound pressure level DIMENSION L H P Operational weight mm mm mm kg (7) (8) (6) V-Ph~Hz A dB(A) dB(A) N. N. (5) (2) (4) (2) (3) (2) (1) (2) kW kW * kW kW * kW kW * kW kW *

0021ms
6,90 1,70 3,95 6,80 2 3,40 6,80 2,20 3,09 5,10 2 2,55 3,15

0031ms
10,2 2,60 3,94 10,3 3,40 2,98 10,1 3,30 3,06 7,80 3,30 2,36 2,98

0041ms
12,9 3,40 3,82 12,9 4,10 3,06 12,7 4,20 3,02 9,90 3,90 2,54 3,06

0051ms
13,4 3,20 4,14 13,9 4 3,37 13,1 4 3,27 10,5 3,80 2,76 3,37 SCROLL 1 R410A

0041t
13 3,50 3,77 13,4 4,20 3,20 13 4,40 2,95 10,3 4 2,58 3,20

0051t
15,2 3,90 3,88 15,9 4,60 3,25 14,6 4,70 3,11 11,9 4,50 2,64 3,25

0061t
17,4 4,10 4,27 18,4 5,40 3,38 17 5 3,40 13,9 5 2,78 3,38

1 Ci 230-1~50 27 66 52 900 640 370 95

1 Ci 230-1~50 44 66 52 900 940 370 115

2 Ci 230-1~50 45 69 54 900 1240 370 140

2 Ci 230-1~50 45 69 54 900 1240 370 160

2 Ci 400-3N~50 64 69 54 900 1240 370 140

2 Ci 400-3N~50 64 69 54 900 1240 370 160

2 Ci 400-3N~50 74 69 54 900 1390 420 170

Note
AWR MTD 1

(1) Water in-out 30/35C (plant side), outdoor air temperature 7C b.s./ 6C b.u. (2) Total input is obtained from compressor input and fan input (3) Water in-out 23/18C (plant side), outdoor air temperature 35C b.s. (4) Water in-out 40/45C (plant side), outdoor air temperature 7C b.s./ 6C b.u. (5) Water in-out 12/7C (plant side), outdoor air temperature

35C b.s. (6) Ci=Circulator; Ce=Centrifugal (7) Sound power level according to ISO 9614 and Eurovent 8/1 (8) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the outside dimensions of the unit. * secondo Eurovent

H H

P L

11

AWR MTD XE

Versions
AWR MTD XE Medium temperature air source reversible heat pump for water heating up to 55C and operating limits down to -15C external air temperature AWR MTD XE H Medium temperature air source reversible heat pump for water heating up to 55C and operating limits down to -15C external air temperature

Unit description
Heat pumps AWR-MTD-XE reversible units are able to provide heating, cooling and domestic hot water. Particular attention was paid to the winter, thanks to special technological devices is guaranteed beyond the normal limits of traditional units. Prana AWR-MTD-XE Air can be combined with traditional systems or radiant panels, ensuring a high energy efficiency. All units are certified in accordance with the Class A classification Eurovent energy in heating. This makes them particularly suitable for use radiant installations. The installation is greatly simplified through the integration of the group and hydraulic technology Full floating simply by connecting the unit to water plant and electricity so that it can be put into operation.

Commands
The new generation electronic controller allows to manage the heat pump by using the Full Floating technology, designed by Climaveneta for improving the systems efficiency for the fans (Floating Fans), for the circulating pump (Floating Flow) and finally for the working temperature (Floating Setpoint). This also allows to achieve all the following benefits: chiller operation even with larger operating limits, improvement of efficiency in both standard and extreme conditions, much lower operating noise in part load conditions, lower installation time, lower time for system set-up, broader operating limits, faster transient after defrosts. The electronic menu allows to manage: - domestic hot water production by external three-way valve (accessory) - a zone of direct heating - outdoor temperature sensor for water plant side modular set point compensation - electrical heating element for possible integration and anti-legionellosis cycle for cylinder - boiler or electric heater management

Features
Structure and base in hot galvanised epoxy powder coated steel. High efficiency and low pressure drop stainless steel (AISI 316) water exchangers complete with closedcell insulation with vapour barrier,antifreeze heating element and differencial pressure switch Hermetic scroll type compressors, equipped with the crankcase heater and thermal protection Finned coils made with copper pipes and aluminium fins with large exchange surface area (100% fully quality tested) Axial electric fans, external rotor, electric motor with a 6-pole fitted with thermal protection, housed in aerodynamic conveyor profile with safety grill Low external air temperature device: continuous fan speed regulation with pressure switch Electrical resistance modulating antifreeze to the base located between wing and base exchanger to improve and facilitate the flow of water during defrosting Condensate collecting tray Coil protection grille Soft starter for 230V/1/50Hz units Phase sequence control relay The water circuit comes complete with: - Variable flow circulator for all models - Water side differential pressure switch - Expansion tank - Safety valve - Manual filling assembly - Pressure gauge - Air vent valve Control with foolproof device accessible from the outside

Main accessories
Main accessories Three-way valve for domestic hot water Buffer tank 35,100,200 liters Hot water cylinder 300,500 liters 300 litres thermal store for domestic hot water, for kit DOMH2O 300,500 litres thermal store for domestic hot water with solar heat exchanger, for kit DOMH2O Kit boiler control DOMH2O15 e DOMH2O24 kit for domestic hot water with external heat exchanger plate-to-plate and pump 1,2,3 kw single-phase electric heater kit External buffer tank and hydronic connecting kit Removable metal mesh water filter kit Rubber anti-vibration mounting kit HSW11 Remote keyboard

12

High efficiency reversible heat pump, air source for outdoor installation 6,3 17,9 kW

r HFC R-410A
AXIAL

AWR MTD XE
Nominal heating power Total absorbed power COP Eurovent COP EN14511 Cooling capacity Total absorbed power EER Eurovent EER EN 14511 Heating capacity Total absorbed power COP Eurovent Cooling capacity Total absorbed power EER Eurovent ESEER Compressor type N. Compressors Refrigerant N. fans Plant side pump type Electrical power supply Start-up current Sound power Sound pressure level DIMENSION L H P Operational weight mm mm mm kg (7) (8) (6) V-Ph~Hz A dB(A) dB(A) N. N. (5) (2) (4) (2) kW kW * kW kW * (3) (2) kW kW * (1) (2) kW kW *

0011ms
6,30 1,50 4,23 4,13 7,20 1,90 3,79 3,82 6,10 1,90 3,29 5,20 1,70 3,06 3,62

0025ms
7,40 1,80 4,23 4,15 8,30 2,20 3,77 3,82 7,30 2,30 3,24 6,30 2,20 2,86 3,63

0031ms
11,2 2,60 4,26 4,22 12,3 3,30 3,73 3,81 10,8 3,30 3,32 9,20 3,10 2,97 3,52

0041ms
14 3,30 4,19 4,16 15,7 4,10 3,83 3,84 13,6 4,10 3,29 11,7 4,00 2,93 3,46 SCROLL 1 R410A

0031t
10,9 2,60 4,18 4,15 11,7 3,10 3,77 3,84 10,6 3,20 3,28 8,60 3,00 2,87 3,42

0041t
14 3,30 4,19 4,15 15,8 4,20 3,76 3,81 13,8 4,30 3,25 11,9 4,00 2,98 3,65

0051t
15,9 3,80 4,14 4,11 17,7 4,70 3,77 3,81 15,4 4,60 3,35 13,2 4,60 2,87 3,24

0061t
17,9 4,20 4,28 4,25 20,2 5,30 3,81 3,81 17,5 5,20 3,38 15,2 5,00 3,04 3,55

1 Ci 230-1~50 27 69 54 900 1240 420 145

1 Ci 230-1~50 30 69 54 900 1240 420 150

2 Ci 230-1~50 45 71 56 900 1240 420 155

2 Ci 230-1~50 45 71 56 900 1390 420 170

2 Ci 400-3N~50 48 71 56 900 1240 420 155

2 Ci 400-3N~50 64 71 56 900 1390 420 170

2 Ci 400-3N~50 64 71 56 900 1390 420 180

2 Ci 400-3N~50 75 72 57 1550 1200 450 250

AWR MTD XE H
Nominal heating power Total absorbed power COP Eurovent COP EN14511 Cooling capacity Total absorbed power EER Eurovent EER EN 14511 Heating capacity Total absorbed power COP Eurovent Cooling capacity Total absorbed power EER Eurovent ESEER Compressor type N. Compressors Refrigerant N. fans Plant side pump type Electrical power supply Start-up current Sound power Sound pressure level DIMENSION L H P Operational weight mm mm mm kg (7) (8) (6) V-Ph~Hz A dB(A) dB(A) N. N. (5) (2) (4) (2) kW kW * kW kW * (3) (2) kW kW * (1) (2) kW kW *

0011ms
6,30 1,50 4,23 4,13 7,20 1,90 3,79 3,82 6,10 1,90 3,29 5,20 1,70 3,06 3,62

0025ms
7,40 1,80 4,23 4,15 8,30 2,20 3,77 3,82 7,30 2,30 3,24 6,30 2,20 2,86 3,63

0031ms
11,2 2,60 4,26 4,22 12,3 3,30 3,73 3,81 10,8 3,30 3,32 9,20 3,10 2,97 3,52

0041ms
14 3,30 4,19 4,16 15,7 4,10 3,83 3,84 13,6 4,10 3,29 11,7 4,00 2,93 3,46 SCROLL 1 R410A

0031t
10,9 2,60 4,18 4,15 11,7 3,10 3,77 3,84 10,6 3,20 3,28 8,60 3,00 2,87 3,42

0041t
14 3,30 4,19 4,15 15,8 4,20 3,76 3,81 13,8 4,30 3,25 11,9 4,00 2,98 3,65

0051t
15,9 3,80 4,14 4,11 17,7 4,70 3,77 3,81 15,4 4,60 3,35 13,2 4,60 2,87 3,24

0061t
17,9 4,20 4,28 4,25 20,2 5,30 3,81 3,81 17,5 5,20 3,38 15,2 5,00 3,04 3,55

1 Ci 230-1~50 27 69 54 900 1240 420 145

1 Ci 230-1~50 30 69 54 900 1240 420 150

2 Ci 230-1~50 45 71 56 900 1240 420 155

2 Ci 230-1~50 45 71 56 900 1390 420 170

2 Ci 400-3N~50 48 71 56 900 1240 420 155

2 Ci 400-3N~50 64 71 56 900 1390 420 170

2 Ci 400-3N~50 64 71 56 900 1390 420 180

2 Ci 400-3N~50 75 72 57 1550 1200 450 250

Note
AWR MTD XE

(1) Water in-out 30/35C (plant side), outdoor air temperatur 7C b.s./ 6C b.u. (2) Total input is obtained from compressor input and fan input. (3) Water in-out 23/18C (plant side), outdoor air temperature 35C b.s. (4) Water in-out 40/45C (plant side), outdoor air temperature 7C b.s./ 6C b.u. (5) Water in-out 12/7C (plant side), outdoor air temperature

35C b.s. (6) Ci=Circulator; Ce=Centrifugal (7) Sound power level according to ISO 9614 and Eurovent 8/1 (8) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the outside dimensions of the unit. * secondo Eurovent

H H

P L

13

AW HT

Versions
AW HT High temperature air source heat pump for water heating up to 65C, and operating limits down to -20 external air temperature

Unit description
AW HT is an ideal solution for systems with heating radiators, where the water high temperature is needed. The EVI technology compressor with additional steam injection in the compressing cycle assures a water temperature of 65C and operating limits as low as -20C. Neither probes nor connections pipes to wells are needed; the installation is simple, this is a suitable solution for all applications.

Commands
Electronic control provides great application flexibility. The remote keyboard kit wired indoor and outdoor temperature sensors allow dynamic control of delivery temperature water, optimizing comfort in the room and increasing the energy efficienty. The electronic board PRO EXTENDED allows you to manage: - domestic hot water production by external three-way valve (accessory) - circulator on system side - a zone of direct heating - outdoor temperature sensor for water plant side modular set point compensation - electrical heating element for possible integration and anti-legionellosis cycle for cylinder - integrated boiler with heat pump - several solutions through appropriate configurations of the controller and use of dedicated extension modules (accessories)

Features
Structure and base in hot-dip galvanised steel with epoxy powder coating finish. High-efficiency plate exchangers in AISI 316 stainless steel with low pressure drops, fitted with heating element for frost protection. High efficiency cycle EVI Hermetic Scroll Compressor (with hot gas direct injection into the compressor) to reach 65 C, with the crankcase heater and thermal protection Finned coils made with copper pipes and aluminium fins with large exchange surface area (100% fully quality tested); sub cooling circuit to prevent the icing at the basement A condense collecting tray within water discharge Coil protection grille Soft starter for 230V/1/50Hz units The water circuit comes complete with: - Circulating pump for all models - Expansion tank - Safety valve - Manual filling assembly - Pressure gauge - Air vent valve - Outside air sensor wired

Main accessories
Three-way valve for domestic hot water Buffer tank 35,100,200 liters Hot water cylinder 300,500 liters 300 litres thermal store for domestic hot water, for kit DOMH2O 300,500 litres thermal store for domestic hot water with solar heat exchanger, for kit DOMH2O DOMH2O15 e DOMH2O24 kit for domestic hot water with external heat exchanger plate-to-plate and pump Control kit for heat pump with boiler 1,2,3 kw single-phase electric heater kit Radiant panels or radiator management kit Second zone Control kit for underfloor heating with hydronic components Removable metal mesh water filter kit Rubber anti-vibration mounting kit Room unit wired Room thermostat wired based

14

Heat pump, air source for outdoor installation, high water temperature 10,4 19,7 kW

r HFC R-407C
AXIAL

AW HT
Nominal heating power Total absorbed power COP EN14511 Heating capacity Total absorbed power COP EN14511 Heating capacity Total absorbed power COP EN 14511 Heating capacity Total absorbed power COP EN 14511 Compressor type N. Compressors Refrigerant N. fans Plant side pump type Electrical power supply Start-up current Sound power Sound pressure level DIMENSION L H P Operational weight mm mm mm kg (7) (8) (6) V-Ph~Hz A dB(A) dB(A) N. N. (5) (2) kW kW (4) (2) kW kW (3) (2) kW kW (1) (2) kW kW

0031ms
10,4 2,50 4,10 10,4 3 3,30 9,10 2,50 3,44 7,80 3,80 1,97

0041ms
14,9 3,50 4,12 14,3 4 4,48 12,5 3,30 3,66 11,4 5,40 2,06

0041t
14,1 3,30 4,14 14,3 4 3,48 12,5 3,30 3,66 11,4 5,40 2,06

0061t
19,7 4,70 4,12 19,7 5,60 3,45 17,5 4,60 3,72 14,8 7,60 1,91

0041ts
14,1 3,30 4,14 14,3 4 3,48 12,5 3,30 3,66 11,4 5,40 2,06

0061ts
19,7 4,70 4,12 19,7 5,60 3,45 17,5 4,60 3,72 14,8 7,60 1,91

SCROLL EVI 1 R407C 2 Ci 230-1~50 44 70 55 900 1240 420 150 230-1~50 45 70 55 900 1390 420 160 400-3N~50 64 70 55 900 1390 420 160 400-3N~50 101 71 56 900 1390 420 170 400-3N~50 35 70 55 900 1390 420 160 400-3N~50 55 71 56 900 1390 420 170

Note
AW-HT

(1) Water in-out 30/35C (plant side), outdoor air temperature 7C b.s./ 6C b.u. (2) Total input is obtained from compressor input and fan input. (3) Water in-out 40/45C (plant side), outdoor air temperature 7C b.s./ 6C b.u. (4) Water in-out 30/35C (plant side), outdoor air temperature 2C b.s./ 1C b.u. (5) Water 65C, outdoor air temperature -7C b.s./ 1C b.u.

(6) Ci=Circulator; Ce=Centrifugal (7) Sound power level according to ISO 9614 and Eurovent 8/1 (8) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the outside dimensions of the unit.

P L

15

WWR MTD

Versions
WWR MTD High temperature air source heat pump for water heating up to 65C, and operating limits down to -20 external air temperature

Unit description
The MTD water-cooled heat pump are reversible units for heating, cooling and domestic hot water by external three-way valve (accessory). Both heat pumps MTD are suitable for traditional heating systemsand radiant panels. The latter, working with water at lower temperatures, ensure a higher yield and are a particularly appreciated for new buildings with low energy consumption that point on using renewable energy resources. The installation is greatly simplified through the integration of the group and hydraulic technology Full floating simply by connecting the unit to water plant and electricity so that it can be put into operation.

Commands
User interface unit on board, accessible from the outside with a not touch system Floating Set Once ever y 3 minutes an algorithm automatically optimises the water set point in relation to the compressor operating time and the temperatures of the water in the system. he water storage tank is no longer indispensable because it is compensated by the Floating Set function, with resulting reduction in: size; weight; installation times; system setting-up times. Floating Flow The controller manages the modulation of the active components (pump and electronic flow valve) through pressure transducers and temperature sensors. The performance of the unit may thus be optimised for different operating conditions, such as traditional fan coil system and panel heating system, ensuring: broader operating limits; easier start-up of installations with both high and low water temperatures; faster system setup. The electronic menu allows to manage: - domestic hot water production by external three-way valve (accessory) - a zone of direct heating - circulator on system side and modulating valve - outdoor temperature sensor for water plant side modular set point compensation (accessory)

Features
Structure and base in hot galvanised epoxy powder coated steel. High-efficiency plate exchangers in AISI 316 stainless steel with low pressure drops, fitted with heating element for frost protection. Hermetic scroll type compressors, equipped with the crankcase heater and thermal protection Case panels are insulated within low noise material for further improvement of silence Rubber vibration damper. Soft starter for 230V/1/50Hz units /ms Phase sequence control relay The water circuit comes complete with: Variable flow circulator for 00110031 models and multistage centrifugal variable flow pump for models 00710121, plant side - Modulating valve to reduce water consumptions, source side - Safety valve. - Expansion tank. - Manual filling assembly - Pressure gauge. - Air vent valve. - Drain valve on both plant and source circuits. - Differential pressure switch on source side and system side

Main accessories
HSW12 remote keyboard External temperature sensor (mandatory with HSW12 remote keyboard) Three-way valve for domestic hot water Buffer tank 35,100,200 liters Hot water cylinder 300,500 liters 300 litres thermal store for domestic hot water, for kit DOMH2O 300,500,1000 litres thermal store for domestic hot water with solar heat exchanger, for kit DOMH2O DOMH2O15 e DOMH2O24 kit for domestic hot water with external heat exchanger plate-to-plate and pump 1,2,3 kw single-phase electric heater kit

16

Reversible heat pump, water source 7,2 43,8 kW

r HFC R-410A

WWR MTD
Nominal heating power Total absorbed power COP Cooling capacity Total absorbed power EER Heating capacity Total absorbed power COP Cooling capacity Total absorbed power EER ESEER Compressor type N. Compressors Refrigerant Plant side pump type Electrical power supply Start-up current Sound power Sound pressure level DIMENSION L H P Operational weight mm mm mm kg (7) (8) (6) V-Ph~Hz A dB(A) dB(A) N. (5) (2) (4) (2) (3) (2) (1) (2) kW kW * kW kW * kW kW * kW kW *

0011m
7,20 1,40 5,14 7,10 1,60 4,44 6,80 1,70 4 5,20 1,53 3,47 4,03

0021m
7,80 1,49 5,23 7,60 1,70 4,47 7,50 1,90 3,95 5,60 1,70 3,29 3,73

0025m
9,70 1,81 5,36 9,80 2 4,90 9,20 2,30 4 7,20 2 3,60 4,26

0031m
12,1 2,30 5,26 12 2,50 4,80 11,6 3 3,87 8,80 2,60 3,38 3,95

0041m
15,3 2,88 5,31 15,1 3,30 4,58 14,6 3,60 4,06 11,3 3,20 3,53 3,90

0011ms
7,20 1,40 5,14 7,10 1,60 4,44 6,80 1,70 4 5,20 1,53 3,40 4,03

0021ms
7,80 1,49 5,23 7,60 1,70 4,47 7,50 1,90 3,95 5,60 1,70 3,29 3,73

0025ms
9,70 1,81 5,36 9,80 1,96 5 9,20 2,30 4 7,20 2 3,60 4,26

0031ms
12,1 2,30 5,26 12 2,53 4,74 11,6 3 3,87 8,80 2,60 3,38 3,95

0041ms
15,3 2,88 5,31 15,1 3,27 4,62 14,6 3,60 4,06 11,3 3,20 3,53 3,90

SCROLL 1 R410A Ci 58 52 38 Ci 61 52 38 Ci 82 53 39 Ci 97 53 39 Ci 230-1~50 130 58 44 560 980 575 148 148 150 152 160 148 148 150 152 160 26 52 38 27 52 38 37 53 39 44 53 39 59 58 44 Ci Ci Ci Ci Ci

WWR MTD
Nominal heating power Total absorbed power COP Cooling capacity Total absorbed power EER Heating capacity Total absorbed power COP Cooling capacity Total absorbed power EER ESEER Compressor type N. Compressors Refrigerant Plant side pump type Electrical power supply Start-up current Sound power Sound pressure level DIMENSION L H P Operational weight mm mm mm kg (7) (8) (6) V-Ph~Hz A dB(A) dB(A) N. (5) (2) (4) (2) (3) (2) (1) (2) kW kW * kW kW * kW kW * kW kW *

0021t
7,80 1,40 5,57 7,60 1,60 4,75 7,40 1,90 3,89 5,60 1,60 3,50 3,97

0025t
9,80 1,73 5,66 9,50 1,80 5,28 9,20 2,20 4,18 7,30 1,90 3,84 4,54

0031t
12,1 2,17 5,58 12 2,50 4,80 11,4 2,70 4,22 8,90 2,40 3,71 4,33

0041t
15,9 2,90 5,48 15,7 3,30 4,76 15,3 3,70 4,14 11,8 3,20 3,70 4,08

0051t
18,1 3,40 5,32 18 3,80 4,74 17,1 4,20 4,07 13,2 3,80 3,47 3,92 SCROLL 1 R410A

0061t
21,1 3,70 5,70 21,3 4,10 5,20 20 4,60 4,35 15,7 4 3,93 4,51

0071t
26,2 4,60 5,70 26,9 5,20 5,17 24,8 5,80 4,28 19,8 5,10 3,88 4,40

0091t
30,5 5,20 5,87 30,7 6 5,12 28,8 6,40 4,50 22,9 5,80 3,95 4,61

0101t
35 6 5,83 34,8 7 4,97 33 7,60 4,34 26 6,80 3,82 4,33

0121t
43,8 7,60 5,76 44,8 8,80 5,09 41,7 9,50 4,39 33,4 8,39 3,98 4,37

Ci 32 52 38 560 980 575 148

Ci 35 52 38 560 980 575 150

Ci 48 52 38 560 980 575 152

Ci 64 58 44 560 980 575 160

Ci 400-3N~50 64 58 44 560 980 575 170

Ci 75 59 45 560 980 575 175

Ce 95 66 51 680 1150 780 220

Ce 111 66 51 680 1150 780 230

Ce 118 70 55 680 1150 780 235

Ce 140 70 55 680 1150 780 250

Note
WWR-MTD

(1) Condenser water in-out 30/35C (plant side), Evaporator water in 10C (source side) (2) Total input is obtained from compressor input and fan input. (3) Temperatura acqua impianto 23/18C, temperatura acqua sorgente 30/35C (4) Temperatura acqua impianto 40/45C, temperatura acqua sorgente ingresso 10C (5) Temperatura acqua impianto 12/7C, temperatura acqua sorgente 30/35C

(6) Ci=Circulator; Ce=Centrifugal (7) Sound power level according to ISO 9614 and Eurovent 8/1 (8) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the outside dimensions of the unit. * secondo Eurovent

17

WWR HT Slim

Versions
WWR HT Slim High temperature heat pump, water source for water heating up to 60C, reversible

Unit description
The Prana Slim heat pump is designed for heating, cooling, and domestic hot water. It is an indoor unit with elegant design and thanks to a special sound insulation, the unit is suitable for a living comfort.

Commands
Electronic control provides great application flexibility. The remote keyboard kit wired indoor and outdoor temperature sensors allow dynamic control of delivery temperature water, optimizing comfort in the room and increasing the energy efficienty. The electronic board PRO EXTENDED allows you to manage: - domestic hot water production by three-way valve - circulator on system side - a zone of direct heating - zone with mix valve for floor heating - outdoor temperature sensor for water plant side modular set point compensation - integration by solar panels - several solutions through appropriate configurations of the controller

Features
Structure and base in hot galvanised epoxy powder coated steel. 180-litre tank with built-in coil for domestic hot water, with fittings for connecting solar panels or hightemperature fixtures (e.g. fan coils) High-efficiency plate exchangers in AISI 316 stainless steel with low pressure drops, fitted with heating element for frost protection. High-efficiency single-and three-phase SCROLL compressor to allow water up to 60 C to be produced. Also suitable for traditional radiator systems. The compressor and plate heat exchangers are housed in a suitably insulated enclosure to limit vibrations and noise. This enclosure can be removed from the unit to make maintenance easier Case panels are insulated within low noise material for further improvement of silence Rubber vibration damper. Soft starter for 230V/1/50Hz units Phase sequence control relay The water circuit comes complete with: - Circulator on system side - Three-way valve for domestic hot water - Safety valve - 180Xlt domestic hot water storage tank - Expansion tank built into the heat pumps tank - Manual filling assembly - Pressure gauge - Air vent valve - Drain valve - Differential pressure switch on source side and system side - Outside air sensor wired

Main accessories
Room unit wired Room thermostat wired based Room unit wireless Outside air sensor wireless NTC probe for select plant diagram or solar panel Heating element kit

18

Reversible heat pump, water source, high water temperature with buffer tank 8,3 14,1 kW

r HFC R-407C

WWR HT Slim
Nominal heating power Total absorbed power COP Cooling capacity Total absorbed power EER Heating capacity Total absorbed power COP Cooling capacity Total absorbed power EER Hot water tank Compressor type N. Compressors Refrigerant Plant side pump type Electrical power supply Start-up current Sound power Sound pressure level DIMENSION L H P Operational weight mm mm mm kg (7) (8) (6) V-Ph~Hz A dB(A) dB(A) N. (5) (2) (4) (2) (3) (2) (1) (2) kW kW * kW kW * kW kW * kW kW * l

Z1M6
8,30 1,60 5,19 9,55 1,46 6,54 7,95 2,02 3,94 6,67 1,53 4,36

Z1M9
11,6 2,22 5,23 13,2 2,11 6,25 11,1 2,80 3,96 9,24 2,17 4,26

Z1M11
14,1 2,68 5,26 15,5 2,72 5,71 13,6 3,37 4,02 11,1 2,67 4,16 180 SCROLL 1 R407C

Z1T6
8,20 1,56 5,24 9,36 1,45 6,46 7,87 1,98 3,97 6,58 1,49 4,42

Z1T9
11,4 2,14 5,34 12,9 2,06 6,27 11 2,72 4,04 9,12 2,09 4,36

Z1T11
14 2,61 5,35 15,6 2,64 5,92 13,5 3,27 4,11 11,1 2,59 4,28

Ci 230-1~50 37 42 28

Ci 230-1~50 60 42 28

Ci 230-1~50 68 46 32 600 1940 570

Ci 400-3N~50 32 42 28

Ci 400-3N~50 46 42 28

Ci 400-3N~50 50 46 32

286

293

300

286

293

300

Note
WWR-HT Slim

(1) Condenser water in-out 30/35C (plant side), Evaporator water in 10C (source side) with identical flow rate that in the cooling mode (2) According to Eurovent (3) Evaporator water in-out 23/18C (plant side), Condenser water in-out 30/35C (source side) (4) Condenser water in-out 40/45C (plant side), water in 10C (source side) with identical flow rate that in the cooling mode (5) Evaporator water in-out 12/7C (plant side), Condenser water in-out 30/35C (source side)

(6) Ci=Circulator; Ce=Centrifugal (7) Sound power level according to ISO 9614 and Eurovent 8/1 (8) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the outside dimensions of the unit. * secondo Eurovent

P L

19

WWR HT Cube

Versions
WWR HT Cube High temperature heat pump, water source for water heating up to 60C, reversible

Unit description
The Prana Cube heat pump is designed for heating, cooling, and domestic hot water, with external three-way valve. It is an indoor unit with elegant design and thanks to a special sound insulation, the unit is suitable for a living comfort.

Commands
Electronic control provides great application flexibility. The remote keyboard kit wired indoor and outdoor temperature sensors allow dynamic control of delivery temperature water, optimizing comfort in the room and increasing the energy efficienty. The electronic board PRO EXTENDED allows you to manage: - domestic hot water production by external three-way valve (accessory) - circulator on system side - a zone of direct heating - zone with mix valve for floor heating - outdoor temperature sensor for water plant side modular set point compensation - integration by solar panels - several solutions through appropriate configurations of the controller

Features
Structure and base in hot galvanised epoxy powder coated steel. High-efficiency plate exchangers in AISI 316 stainless steel with low pressure drops, fitted with heating element for frost protection. High-efficiency single-and three-phase SCROLL compressor to allow water up to 60 C to be produced. Also suitable for traditional radiator systems. The compressor and plate heat exchangers are housed in a suitably insulated enclosure to limit vibrations and noise. This enclosure can be removed from the unit to make maintenance easier Case panels are insulated within low noise material for further improvement of silence Rubber vibration damper. Soft starter for 230V/1/50Hz units Phase sequence control relay The water circuit comes complete with: - Circulator on system side - Drain valve - Differential pressure switch on source side and system side - Outside air sensor wired

Main accessories
Room unit wired Room thermostat wired based Room unit wireless Outside air sensor wireless NTC probe for select plant diagram or solar panel Heating element kit Three-way valve for domestic hot water Buffer tank 35,100,200 liters Hot water cylinder 300,500 liters 300 litres thermal store for domestic hot water, for kit DOMH2O 300,500,1000 litres thermal store for domestic hot water with solar heat exchanger, for kit DOMH2O DOMH2O15 e DOMH2O24 kit for domestic hot water with external heat exchanger plate-to-plate and pump

20

Reversible heat pump, water source, high water temperature 8,3 35,9 kW

r HFC R-407C

WWR HT Cube
Nominal heating power Total absorbed power COP Cooling capacity Total absorbed power EER Heating capacity Total absorbed power COP Cooling capacity Total absorbed power EER Compressor type N. Compressors Refrigerant Plant side pump type Electrical power supply Start-up current Sound power Sound pressure level DIMENSION L H P Operational weight mm mm mm kg (7) (8) (6) V-Ph~Hz A dB(A) dB(A) N. (5) (2) (4) (2) (3) (2) (1) (2) kW kW * kW kW * kW kW * kW kW *

Z1M6
8,30 1,60 5,19 9,55 1,46 6,54 7,95 2,02 3,94 6,67 1,53 4,36

Z1M9
11,6 2,22 5,23 13,2 2,11 6,25 11,1 2,80 3,96 9,24 2,17 4,26

Z1M11
14,1 2,68 5,26 15,5 2,72 5,71 13,6 3,37 4,02 11,1 2,67 4,16

Z1T6
8,20 1,56 5,24 9,36 1,45 6,46 7,87 1,98 3,97 6,58 1,49 4,42

Z1T9
11,4 2,14 5,34 12,9 2,06 6,27 11 2,72 4,04 9,12 2,09 4,36

Z1T11
14 2,61 5,35 15,6 2,64 5,92 13,5 3,27 4,11 11,1 2,59 4,28

Z1T13
17,1 3,28 5,22 19 3,76 5,04 16,4 4,07 4,02 13,4 3,38 3,97

Z1T17
22,6 4,30 5,27 24,9 4,95 5,02 21,8 5,39 4,04 17,5 4,53 3,87

Z1T24
31,1 5,84 5,33 34,7 6,14 5,65 29,9 7,28 4,11 24,3 6,01 4,05

Z1T28
35,9 6,59 5,45 40 7 5,71 34,5 8,29 4,16 28,2 6,77 4,16

SCROLL 1 R407C Ci 230-1~50 37 42 28 600 940 570 160 Ci 230-1~50 60 42 28 600 940 570 180 Ci 230-1~50 68 46 32 600 940 570 190 Ci 400-3N~50 32 42 28 600 940 570 160 Ci 400-3N~50 46 42 28 600 940 570 180 Ci 400-3N~50 50 46 32 600 940 570 190 Ci 400-3N~50 66 47 33 600 940 570 200 Ci 400-3N~50 101 51 37 600 940 570 220 Ci 400-3N~50 123 55 41 900 1117 648 240 Ci 400-3N~50 127 55 41 900 1117 648 250

Note
WWR HT Cube

(1) Condenser water in-out 30/35C (plant side), Evaporator water in 10C (source side) with identical flow rate that in the cooling mode (2) According to Eurovent (3) Evaporator water in-out 23/18C (plant side), Condenser water in-out 30/35C (source side) (4) Condenser water in-out 40/45C (plant side), water in 10C (source side) with identical flow rate that in the cooling mode (5) Evaporator water in-out 12/7C (plant side), Condenser water in-out 30/35C (source side)

(6) Ci=Circulator; Ce=Centrifugal (7) Sound power level according to ISO 9614 and Eurovent 8/1 (8) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the outside dimensions of the unit. * secondo Eurovent

P L

21

WWR DHW

Versions
WWR DHW Water source reversible heat pump with domestic hot water supply with total heat recovery

Unit description
PRANA DHW is the heat pump new generation able to operate throughout the year in any operating mode: either a single cycle (air conditioning, heating, hot water) and combined cycle (hot water along with air conditioning or heating). Energy efficiency is highest during the summer cycle, when, thanks to the full recovery of the heat, the production of hot water is free. During the combined use, the DHW exchanger uses the temperature of the hot exhaust gases to gets inside the accumulation sanitary water as high as 65 C. The advanced CLIMAVENETA fully patented electronic ensures the highest flexibility of operation, a rapid speed and a significant increase in the overall COP, which go hand in hand with electricity and space reduction. Advantages, combined with the possibility of completely eliminating the traditional boiler, making heat pumps PRANA DHW the ideal solution for energy saving applications in residential, hotel and small sector.

Commands
User interface unit on board, accessible from the outside with a not touch system WWR-DHW heats water stored in the tank as energy storage. It also comes with a state-of-the-art electronic unit, which independently controls the modes of operation. The appliance can operate throughout the year in any mode, both with single cycle (cooling, heating, hot water) and with combined cycle (hot water together with cooling or hot water together heating).During the summer cycle there is maximum energy saving through total heat recovery. This energy is completely free of charge with regard to the production of hot water.

Features
Structure and base in hot galvanised epoxy powder coated steel Case panels are insulated within low noise material for further improvement of silence Rubber vibration damper Hermetic scroll type compressors, equipped with the crankcase heater and thermal protection Stainless steel (AISI 316) with high efficiency and low pressure drop plate to plate exchanger (at the domestic hot water side). It is positioned next after the compressor, it ensures the domestic hot water production. That can work either in full recovery or in part, with the constant optimization of efficiency through logic advanced adjusting controller Exchangers plant side plate of stainless steel AISI 316 with high efficiency and low pressure drop meets the supply of both hot or cold water for the facility, regardless of the domestic hot water High efficiency and low pressure drop stainless steel (AISI 316) source side plate exchanger Soft starter for 230V/1/50Hz units /ms The water circuit comes complete with: - Variable flow circulator for 00110031 models and multistage centrifugal variable flow pump for models 00710121, plant side - Domestic hot water, water side, variable flow pump - Modulating valve to reduce water consumptions, source side - Safety valve - Expansion tank - Drain valve on both plant and source circuits

Main accessories
Buffer tank 35,100,200 liters Hot water cylinder 300,500 liters 300 litres thermal store for domestic hot water, for kit DOMH2O 300,500,1000 litres thermal store for domestic hot water with solar heat exchanger, for kit DOMH2O DOMH2O15 e DOMH2O24 kit for domestic hot water with external heat exchanger plate-to-plate and pump Remote keyboard Removable metal mesh water filter kit

22

Reversible heat pump, total heat recovery, water source 6,0 40,5 kW

r HFC R-407C

WWR DHW
Nominal heating power Total absorbed power COP Cooling capacity Total absorbed power EER Cooling capacity with total recovery Total absorbed power Recovery heating capacity Heating capacity Total absorbed power COP Cooling capacity Total absorbed power EER Compressor type N. Compressors Refrigerant Plant side pump type Recovery side pump type Electrical power supply Start-up current Sound power Sound pressure level DIMENSION L H P Operational weight mm mm mm kg (8) (9) (7) (7) V-Ph~Hz A dB(A) dB(A) N. (6) (2) kW kW (4) (5) (2) (4) kW kW kW kW kW (3) (2) kW kW (1) (2) kW kW

0011m
6 1,30 4,49 7,30 1,30 5,62 6 1,90 7,90 5,70 1,70 3,33 5,10 1,30 3,92

0021m
7,60 1,70 4,48 9,20 1,70 5,41 7,80 2,40 10 7,30 2,20 3,35 6,50 1,70 3,82

0025m
9 2 4,51 11 2 5,50 9,20 2,90 11,9 8,70 2,60 3,37 7,70 2 3,85

0031m
10,5 2,40 4,36 12,5 2,40 5,21 10,3 3,40 13,5 10,1 3,10 3,28 8,90 2,40 3,71

0041m
12,9 2,90 4,50 15,3 2,90 5,28 12,9 4,20 16,8 12,4 3,60 3,40 11 2,90 3,79

0011ms
6 1,30 4,49 7,30 1,30 5,62 6 1,90 7,90 5,60 1,70 3,33 5,10 1,30 3,92

0021ms
7,60 1,70 4,48 9,20 1,70 5,41 7,80 2,40 10 7,20 2,20 3,35 6,50 1,70 3,82

0025ms
9 2 4,51 11 2 5,50 9,20 2,90 11,9 8,50 2,60 3,37 7,70 2 3,85

0031ms
10,5 2,40 4,36 12,5 2,40 5,21 10,3 3,40 13,5 9,90 3,10 3,28 8,90 2,40 3,71

0041ms
12,9 2,90 4,50 15,3 2,90 5,28 12,9 4,20 16,8 12,2 3,60 3,40 11 2,90 3,79

SCROLL 1 R407C Ci Ci 230-1~50 47 52 38 560 980 575 188 Ci Ci 230-1~50 61 52 38 560 980 575 188 Ci Ci 230-1~50 76 53 39 560 980 575 190 Ci Ci 230-1~50 100 53 39 560 980 575 195 Ci Ci 230-1~50 114 58 44 560 980 575 215 Ci Ci 230-1~50 21 52 38 560 980 575 188 Ci Ci 230-1~50 27 52 38 560 980 575 188 Ci Ci 230-1~50 34 53 39 560 980 575 190 Ci Ci 230-1~50 45 53 39 560 980 575 195 Ci Ci 230-1~50 51 58 44 560 980 575 215

WWR DHW
Nominal heating power Total absorbed power COP Cooling capacity Total absorbed power EER Cooling capacity with total recovery Total absorbed power Recovery heating capacity Heating capacity Total absorbed power COP Cooling capacity Total absorbed power EER Compressor type N. Compressors Refrigerant Plant side pump type Recovery side pump type Electrical power supply Start-up current Sound power Sound pressure level DIMENSION L H P Operational weight mm mm mm kg (8) (9) (7) (7) V-Ph~Hz A dB(A) dB(A) N. (6) (2) kW kW (4) (5) (2) (4) kW kW kW kW kW (3) (2) kW kW (1) (2) kW kW

0021t
7,50 1,70 4,55 9,20 1,60 5,75 7,70 2,30 9,90 7,20 2,10 3,41 6,50 1,70 3,82

0025t
8,90 2 4,58 10,9 1,90 5,74 9,10 2,80 11,7 8,60 2,50 3,42 7,70 2 3,85

0031t
10,3 2,30 4,44 12,4 2,30 5,39 10,3 3,30 13,4 9,90 3 3,34 8,80 2,30 3,83

0041t
12,7 2,80 4,57 15,4 2,80 5,50 13,1 4 16,9 12,3 3,50 3,48 10,9 2,80 3,89

0051t
15,6 3,40 4,58 19,1 3,60 5,31 16 4,90 20,6 14,9 4,30 3,50 13,4 3,40 3,94 SCROLL 1 R407C

0061t
18,7 3,90 4,75 22,5 4,10 5,49 18,9 5,70 24,2 17,9 4,90 3,62 16,1 4 4,03

0071t
25,3 5,30 4,73 30,2 5,50 5,49 25,5 7,70 32,7 24 6,80 3,55 21,7 5,40 4,02

0091t
28,4 5,90 4,84 34,4 6,10 5,64 29 8,40 36,9 27,1 7,30 3,69 24,6 5,90 4,17

0101t
32,6 6,90 4,69 38,9 7,30 5,33 32,7 10,2 42,4 31,1 8,70 3,55 28 7 4,00

0121t
40,5 8,80 4,59 49,7 9,30 5,34 41,1 12,8 53,1 38,3 11,1 3,45 34,8 8,90 3,91

Ci Ci 32 52 38 560 980 575 188

Ci Ci 40 52 38 560 980 575 190

Ci Ci 46 52 38 560 980 575 195

Ci Ci 50 58 44 560 980 575 215

Ci Ci 400-3N~50 66 58 44 560 980 575 228

Ce Ci 74 59 45 560 980 575 233

Ce Ci 95 66 51 680 1150 780 260

Ce Ci 111 66 51 680 1150 780 270

Ce Ci 118 70 55 680 1150 780 280

Ce Ci 140 70 55 680 1150 780 305

Note
WWR DHW

(1) Condenser water in-out 30/35C (plant side), Evaporator water in 10C (source side) with identical flow rate that in the cooling mode (2) According to Eurovent (3) Evaporator water in-out 23/18C (plant side), Condenser water in-out 30/35C (source side) (4) Water in-out 23/18C (plant side), water in-out 45/50C (total recovery side) (5) Condenser water in-out 40/45C (plant side), water in 10C (source side) with identical flow rate that in the cooling mode

(6) Evaporator water in-out 12/7C (plant side), Condenser water in-out 30/35C (source side) (7) Ci=Circulator; Ce=Centrifugal (8) Sound power level according to ISO 9614 and Eurovent 8/1 (9) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the outside dimensions of the unit.

23

BWR MTD

Versions
BWR MTD Medium temperature geothermal reversible heat pump for water heating up to 55C

Unit description
The MTD heat pump optimized for geothermal systems are reversible units for heating, cooling and domestic hot water by external three-way valve (accessory). Both heat pumps MTD are suitable for traditional heating systemsand radiant panels. The latter, working with water at lower temperatures, ensure a higher yield and are a particularly appreciated for new buildings with low energy consumption that point on using renewable energy resources. The installation is greatly simplified through the integration of the group and hydraulic technology Full floating simply by connecting the unit to water plant and electricity so that it can be put into operation.

Commands
User interface unit on board, accessible from the outside with a not touch system Floating Set Once ever y 3 minutes an algorithm automatically optimises the water set point in relation to the compressor operating time and the temperatures of the water in the system. he water storage tank is no longer indispensable because it is compensated by the Floating Set function, with resulting reduction in: size; weight; installation times; system setting-up times. Floating Flow The controller manages the modulation of the active components (pump and electronic flow valve) through pressure transducers and temperature sensors. The performance of the unit may thus be optimised for different operating conditions, such as traditional fan coil system and panel heating system, ensuring: broader operating limits; easier start-up of installations with both high and low water temperatures; faster system setup. The electronic menu allows to manage: - domestic hot water production by external three-way valve (accessory) - a zone of direct heating - circulator on system and source side - outdoor temperature sensor for water plant side modular set point compensation (accessory)

Features
Structure and base in hot galvanised epoxy powder coated steel. High-efficiency plate exchangers in AISI 316 stainless steel with low pressure drops, fitted with heating element for frost protection. Hermetic scroll type compressors, equipped with the crankcase heater and thermal protection Case panels are insulated within low noise material for further improvement of silence Rubber vibration damper. Soft starter for 230V/1/50Hz units /ms Phase sequence control relay The water circuit comes complete with: - Variable flow circulator for 00110031 models and multistage centrifugal variable flow pump for models 00710121, plant side - Variable flow circulator for 00110031 models, multistage centrifugal variable flow pump for models 0071-0121 on source side (for geothermal systems, closed vertical or horizontal loops) - Safety valve. - Expansion tank. - Manual filling assembly - Pressure gauge. - Air vent valve. - Drain valve on both plant and source circuits. - Differential pressure switch on source side and system side

Main accessories
HSW12 remote keyboard External temperature sensor (mandatory with HSW12 remote keyboard) Three-way valve for domestic hot water Buffer tank 35,100,200 liters Hot water cylinder 300,500 liters 300 litres thermal store for domestic hot water, for kit DOMH2O 300,500,1000 litres thermal store for domestic hot water with solar heat exchanger, for kit DOMH2O DOMH2O15 e DOMH2O24 kit for domestic hot water with external heat exchanger plate-to-plate and pump 1,2,3 kw single-phase electric heater kit

24

Reversible heat pump, geothermal source 5,4 33,3 kW

r HFC R-410A

BWR MTD
Nominal heating power Total absorbed power COP Cooling capacity Total absorbed power EER Heating capacity Total absorbed power COP Cooling capacity Total absorbed power EER ESEER Compressor type N. Compressors Refrigerant Plant side pump type Source side pump type Electrical power supply Start-up current Sound power Sound pressure level DIMENSION L H P Operational weight mm mm mm kg (7) (8) (6) (6) V-Ph~Hz A dB(A) dB(A) N. (5) (2) (4) (2) (3) (2) (1) (2) kW kW * kW kW * kW kW * kW kW *

0011m
5,40 1,34 4,03 7,10 1,60 4,44 5,20 1,70 3,06 5,20 1,53 3,40 4,03

0021m
5,90 1,50 3,93 7,60 1,70 4,47 5,70 1,90 3 5,60 1,70 3,29 3,73

0025m
7,30 1,82 4 9,80 1,96 5 7,10 2,30 3,09 7,20 2 3,60 4,26

0031m
9,20 2,35 3,92 12 2,53 4,74 9 3 3 8,80 2,60 3,38 3,95

0041m
11,7 2,80 4,18 15,1 3,27 4,62 11,3 3,60 3,14 11,3 3,20 3,53 3,90

0011ms
5,40 1,34 4,03 7,10 1,60 4,44 5,20 1,70 3,06 5,20 1,53 3,40 4,03

0021ms
5,90 1,50 3,93 7,60 1,70 4,47 5,70 1,90 3 5,60 1,70 3,29 3,73

0025ms
7,30 1,82 4 9,80 1,96 5 7,10 2,30 3,09 7,20 2 3,60 4,26

0031ms
9,20 2,35 3,92 12 2,53 4,74 9 3 3 8,80 2,60 3,38 3,95

0041ms
11,7 2,80 4,18 15,1 3,27 4,62 11,3 3,60 3,14 11,3 3,20 3,53 3,90

SCROLL 1 R410A Ci Ci 58 52 38 Ci Ci 61 52 38 Ci Ci 82 53 39 Ci Ci 97 53 39 Ci Ce 230-1~50 130 58 44 560 980 575 148 148 150 152 160 148 148 150 152 160 26 52 38 27 52 38 37 53 39 44 53 39 59 58 44 Ci Ci Ci Ci Ci Ci Ci Ci Ci Ce

BWR MTD
Nominal heating power Total absorbed power COP Cooling capacity Total absorbed power EER Heating capacity Total absorbed power COP Cooling capacity Total absorbed power EER ESEER Compressor type N. Compressors Refrigerant Plant side pump type Source side pump type Electrical power supply Start-up current Sound power Sound pressure level DIMENSION L H P Operational weight mm mm mm kg (7) (8) (6) (6) V-Ph~Hz A dB(A) dB(A) N. (5) (2) (4) (2) (3) (2) (1) (2) kW kW * kW kW * kW kW * kW kW *

0021t
5,90 1,40 4,21 7,60 1,60 4,75 5,70 1,90 3 5,60 1,63 3,44 3,97

0025t
7,50 1,74 4,31 9,50 1,84 5,16 7 2,20 3,18 7,30 1,90 3,84 4,54

0031t
9,10 2,10 4,33 12 2,50 4,80 8,70 2,70 3,22 8,90 2,41 3,69 4,33

0041t
12,2 2,80 4,36 15,7 3,30 4,76 11,8 3,70 3,19 11,8 3,19 3,70 4,08

0051t
13,7 3,40 4,03 18 3,70 4,86 12,9 4,10 3,15 13,2 3,80 3,47 3,92 SCROLL 1 R410A

0061t
16 3,50 4,57 21,3 4,10 5,20 15,2 4,40 3,45 15,7 4 3,93 4,51

0071t
19,8 4,40 4,50 26,9 5,15 5,22 18,8 5,60 3,36 19,8 5,10 3,88 4,40

0091t
23 4,90 4,69 30,7 5,95 5,16 21,8 6,20 3,52 22,9 5,80 3,95 4,61

0101t
26,5 5,80 4,57 34,8 7 4,97 25,1 7,40 3,39 26 6,80 3,82 4,33

0121t
33,3 7,30 4,56 44,8 8,80 5,09 31,9 9 3,54 33,4 8,40 3,98 4,37

Ci Ci 32 52 38 560 980 575 148

Ci Ci 35 52 38 560 980 575 150

Ci Ci 48 52 38 560 980 575 152

Ci Ce 64 58 44 560 980 575 160

Ci Ce 400-3N~50 64 58 44 560 980 575 170

Ci Ce 75 59 45 560 980 575 175

Ce Ce 95 66 51 680 1150 780 220

Ce Ce 111 66 51 680 1150 780 230

Ce Ce 118 70 55 680 1150 780 235

Ce Ce 140 70 55 680 1150 780 250

Note
BWR MTD

(1) Condenser water in-out 30/35C (plant side), Evaporator water in-out 0/-3C (source side) (2) According to Eurovent (3) Evaporator water in-out 23/18C (plant side), Condenser water in-out 30/35C (source side) (4) Condenser water in-out 40/45C (plant side), Evaporator water in-out 0/-3C (source side) (5) Evaporator water in-out 12/7C (plant side), Condenser water in-out 30/35C (source side)

(6) Ci=Circulator; Ce=Centrifugal (7) Sound power level according to ISO 9614 and Eurovent 8/1 (8) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the outside dimensions of the unit. * secondo Eurovent

25

BWR HT Slim

Versions
BWR HT Slim High temperature heat pump, geothermal source, for water heating up to 60C, reversible

Unit description
The Prana Slim heat pump is designed for heating, cooling, and domestic hot water. It is an indoor unit with elegant design and thanks to a special sound insulation, the unit is suitable for a living comfort.

Commands
Electronic control provides great application flexibility. The remote keyboard kit wired indoor and outdoor temperature sensors allow dynamic control of delivery temperature water, optimizing comfort in the room and increasing the energy efficienty. The electronic board PRO EXTENDED allows you to manage: - domestic hot water production by three-way valve - circulator on system and source side - a zone of direct heating - zone with mix valve for floor heating - outdoor temperature sensor for water plant side modular set point compensation - integration by solar panels - several solutions through appropriate configurations of the controller

Features
Structure and base in hot galvanised epoxy powder coated steel 180-litre tank with built-in coil for domestic hot water, with fittings for connecting solar panels or hightemperature fixtures (e.g. fan coils) High-efficiency plate exchangers in AISI 316 stainless steel with low pressure drops, fitted with heating element for frost protection High-efficiency single-and three-phase SCROLL compressor to allow water up to 60 C to be produced Also suitable for traditional radiator systems The compressor and plate heat exchangers are housed in a suitably insulated enclosure to limit vibrations and noise. This enclosure can be removed from the unit to make maintenance easier Case panels are insulated within low noise material for further improvement of silence Rubber vibration damper Soft starter for 230V/1/50Hz units Phase sequence control relay The water circuit comes complete with: - Circulator on system side - Circulator on source side (for geothermal systems, closed vertical or horizontal loops) - Three-way valve for domestic hot water - 180Xlt domestic hot water storage tank - Safety valve - Expansion tank built into the heat pumps tank - Manual filling assembly - Pressure gauge - Drain valve - Air vent valve - Differential pressure switch on source side and system side - Outside air sensor wired

Main accessories
Room unit wired Room thermostat wired based Room unit wireless Outside air sensor wireless NTC probe for select plant diagram or solar panel Heating element kit

26

Reversible heat pump, geothermal source, high water temperature with buffer tank 6,2 10,6 kW

r HFC R-407C

BWR HT Slim
Nominal heating power Total absorbed power COP Cooling capacity Total absorbed power EER Heating capacity Total absorbed power COP Cooling capacity Total absorbed power EER Hot water tank Compressor type N. Compressors Refrigerant Plant side pump type Source side pump type Electrical power supply Start-up current Sound power Sound pressure level DIMENSION L H P Operational weight mm mm mm kg (7) (8) (6) (6) V-Ph~Hz A dB(A) dB(A) N. (5) (2) (4) (2) (3) (2) (1) (2) kW kW * kW kW * kW kW * kW kW * l

Z1M6
6,21 1,60 3,88 9,55 1,46 6,54 6,04 2,02 2,99 6,67 1,53 4,36

Z1M9
8,66 2,22 3,90 13,2 2,11 6,25 8,41 2,80 3 9,24 2,17 4,26

Z1M11
10,6 2,68 3,96 15,5 2,72 5,71 10,3 3,35 3,08 11,1 2,67 4,16 180 SCROLL 1 R407C

Z1T6
6,04 1,55 3,90 9,36 1,45 6,46 5,89 1,97 2,99 6,58 1,49 4,42

Z1T9
8,43 2,13 3,96 12,9 2,06 6,27 8,20 2,71 3,03 9,12 2,09 4,36

Z1T11
10,5 2,60 4,02 15,6 2,64 5,92 10,2 3,24 3,14 11,1 2,59 4,28

Ci Ci 230-1~50 37 42 28

Ci Ci 230-1~50 60 42 28

Ci Ci 230-1~50 68 46 32 600 1940 570

Ci Ci 400-3N~50 32 42 28

Ci Ci 400-3N~50 46 42 28

Ci Ci 400-3N~50 50 46 32

286

293

300

286

293

300

Note
BWR-HT Slim

(1) Condenser water in-out 30/35C (plant side), Evaporator water in-out 0/-3C (source side) (2) According to Eurovent (3) Evaporator water in-out 23/18C (plant side), Condenser water in-out 30/35C (source side) (4) Condenser water in-out 40/45C (plant side), Evaporator water in-out 0/-3C (source side) (5) Evaporator water in-out 12/7C (plant side), Condenser water in-out 30/35C (source side)

(6) Ci=Circulator; Ce=Centrifugal (7) Sound power level according to ISO 9614 and Eurovent 8/1 (8) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the outside dimensions of the unit. * secondo Eurovent

P L

27

BWR HT Cube

Versions
BWR HT Cube High temperature heat pump, geothermal source, for water heating up to 60C, reversible

Unit description
The Prana Cube heat pump is designed for heating, cooling, and domestic hot water, with external three-way valve. It is an indoor unit with elegant design and thanks to a special sound insulation, the unit is suitable for a living comfort.

Commands
Electronic control provides great application flexibility. The remote keyboard kit wired indoor and outdoor temperature sensors allow dynamic control of delivery temperature water, optimizing comfort in the room and increasing the energy efficienty. The electronic board PRO EXTENDED allows you to manage: - domestic hot water production by three-way valve - circulator on system and source side - a zone of direct heating - zone with mix valve for floor heating - outdoor temperature sensor for water plant side modular set point compensation - integration by solar panels - several solutions through appropriate configurations of the controller

Features
Structure and base in hot galvanised epoxy powder coated steel High-efficiency plate exchangers in AISI 316 stainless steel with low pressure drops, fitted with heating element for frost protection High-efficiency single-and three-phase SCROLL compressor to allow water up to 60 C to be produced Also suitable for traditional radiator systems The compressor and plate heat exchangers are housed in a suitably insulated enclosure to limit vibrations and noise. This enclosure can be removed from the unit to make maintenance easier Case panels are insulated within low noise material for further improvement of silence Rubber vibration damper Soft starter for 230V/1/50Hz units Phase sequence control relay The water circuit comes complete with: - Circulator on system side - Circulator on source side (for geothermal systems, closed vertical or horizontal loops) - Drain valve - Differential pressure switch on source side and system side - Outside air sensor wired

Main accessories
Room unit wired Room thermostat wired based Room unit wireless Outside air sensor wireless NTC probe for select plant diagram or solar panel Heating element kit Three-way valve for domestic hot water Buffer tank 35,100,200 liters Hot water cylinder 300,500 liters 300 litres thermal store for domestic hot water, for kit DOMH2O 300,500,1000 litres thermal store for domestic hot water with solar heat exchanger, for kit DOMH2O DOMH2O15 e DOMH2O24 kit for domestic hot water with external heat exchanger plate-to-plate and pump

28

Reversible heat pump, geothermal source, high water temperature 6,2 27,0 kW

r HFC R-407C

BWR HT Cube
Nominal heating power Total absorbed power COP Cooling capacity Total absorbed power EER Heating capacity Total absorbed power COP Cooling capacity Total absorbed power EER Compressor type N. Compressors Refrigerant Plant side pump type Source side pump type Electrical power supply Start-up current Sound power Sound pressure level DIMENSION L H P Operational weight mm mm mm kg (7) (8) (6) (6) V-Ph~Hz A dB(A) dB(A) N. (5) (2) (4) (2) (3) (2) (1) (2) kW kW * kW kW * kW kW * kW kW *

Z1M6
6,21 1,60 3,88 9,55 1,46 6,54 6,04 2,02 2,99 6,67 1,53 4,36

Z1M9
8,66 2,22 3,90 13,2 2,11 6,25 8,41 2,80 3 9,24 2,17 4,26

Z1M11
10,6 2,68 3,96 15,5 2,72 5,71 10,3 3,35 3,08 11,1 2,67 4,16

Z1T6
6,04 1,55 3,90 9,36 1,45 6,46 5,89 1,97 2,99 6,58 1,49 4,42

Z1T9
8,43 2,13 3,96 12,9 2,06 6,27 8,20 2,71 3,03 9,12 2,09 4,36

Z1T11
10,5 2,60 4,02 15,6 2,64 5,92 10,2 3,24 3,14 11,1 2,59 4,28

Z1T13
12,6 3,17 3,96 19 3,76 5,04 12,2 3,94 3,09 13,4 3,38 3,97

Z1T17
16,9 4,14 4,09 24,9 4,95 5,02 16,4 5,24 3,14 17,5 4,53 3,87

Z1T24
23,3 5,74 4,06 34,7 6,14 5,65 22,6 7,12 3,18 24,3 6,01 4,05

Z1T28
27 6,53 4,14 40 7 5,71 26,2 8,12 3,23 28,2 6,77 4,16

SCROLL 1 R407C Ci Ci 230-1~50 37 42 28 600 940 570 160 Ci Ci 230-1~50 60 42 28 600 940 570 180 Ci Ci 230-1~50 68 46 32 600 940 570 190 Ci Ci 400-3N~50 32 42 28 600 940 570 160 Ci Ci 400-3N~50 46 42 28 600 940 570 180 Ci Ci 400-3N~50 50 46 32 600 940 570 190 Ci Ci 400-3N~50 66 47 33 600 940 570 200 Ci Ci 400-3N~50 101 51 37 600 940 570 220 Ci Ci 400-3N~50 123 55 41 900 1117 648 240 Ci Ci 400-3N~50 127 55 41 900 1117 648 250

Note
BWR-HT Cube

(1) Condenser water in-out 30/35C (plant side), Evaporator water in-out 0/-3C (source side) (2) According to Eurovent (3) Evaporator water in-out 23/18C (plant side), Condenser water in-out 30/35C (source side) (4) Condenser water in-out 40/45C (plant side), Evaporator water in-out 0/-3C (source side) (5) Evaporator water in-out 12/7C (plant side), Condenser water in-out 30/35C (source side)

(6) Ci=Circulator; Ce=Centrifugal (8) Sound power level according to ISO 9614 and Eurovent 8/1 (9) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the outside dimensions of the unit. * secondo Eurovent

P L

29

BWR DHW

Versions
BWR DHW Geothermal reversible heat pump with domestic hot water supply with total heat recovery

Unit description
PRANA DHW is the heat pump new generation able to operate throughout the year in any operating mode: either a single cycle (air conditioning, heating, hot water) and combined cycle (hot water along with air conditioning or heating). Energy efficiency is highest during the summer cycle, when, thanks to the full recovery of the heat, the production of hot water is free. During the combined use, the DHW exchanger uses the temperature of the hot exhaust gases to gets inside the accumulation sanitary water as high as 65 C. The advanced CLIMAVENETA fully patented electronic ensures the highest flexibility of operation, a rapid speed and a significant increase in the overall COP, which go hand in hand with electricity and space reduction. Advantages, combined with the possibility of completely eliminating the traditional boiler, making heat pumps PRANA DHW the ideal solution for energy saving applications in residential, hotel and small sector.

Commands
User interface unit on board, accessible from the outside with a not touch system BWR-DHW heats water stored in the tank as energy storage. It also comes with a state-of-the-art electronic unit, which independently controls the modes of operation. The appliance can operate throughout the year in any mode, both with single cycle (cooling, heating, hot water) and with combined cycle (hot water together with cooling or hot water together heating).During the summer cycle there is maximum energy saving through total heat recovery. This energy is completely free of charge with regard to the production of hot water.

Features
Structure and base in hot galvanised epoxy powder coated steel. Case panels are insulated within low noise material for further improvement of silence Rubber vibration damper. Hermetic scroll type compressors, equipped with the crankcase heater and thermal protection Stainless steel (AISI 316) with high efficiency and low pressure drop plate to plate exchanger (at the domestic hot water side). It is positioned next after the compressor, it ensures the domestic hot water production. That can work either in full recovery or in part, with the constant optimization of efficiency through logic advanced adjusting controller Exchangers plant side plate of stainless steel AISI 316 with high efficiency and low pressure drop meets the supply of both hot or cold water for the facility, regardless of the domestic hot water High efficiency and low pressure drop stainless steel (AISI 316) source side plate exchanger Soft starter for 230V/1/50Hz units /ms The water circuit comes complete with: - Variable flow circulator for 00110031 models and multistage centrifugal variable flow pump for models 00710121, plant side - Domestic hot water, water side, variable flow pump - Variable flow circulator for 00110031 models, multistage centrifugal variable flow pump for models 0071-0121 on source side (for geothermal systems, closed vertical or horizontal loops) - Safety valve - Expansion tank - Drain valve on both plant and source circuits

Main accessories
Buffer tank 35,100,200 liters Hot water cylinder 300,500 liters 300 litres thermal store for domestic hot water, for kit DOMH2O 300,500,1000 litres thermal store for domestic hot water with solar heat exchanger, for kit DOMH2O DOMH2O15 e DOMH2O24 kit for domestic hot water with external heat exchanger plate-to-plate and pump Remote keyboard Removable metal mesh water filter kit

30

Reversible heat pump, total heat recovery, geothermal source 4,5 29,7 kW

r HFC R-407C

BWR DHW
Nominal heating power Total absorbed power COP Cooling capacity Total absorbed power EER Cooling capacity with total recovery Total absorbed power Recovery heating capacity Heating capacity Total absorbed power COP Cooling capacity Total absorbed power EER Compressor type N. Compressors Refrigerant Plant side pump type Recovery side pump type Source side pump type Electrical power supply Start-up current Sound power Sound pressure level DIMENSION L H P Operational weight mm mm mm kg (8) (9) (7) (7) (7) V-Ph~Hz A dB(A) dB(A) N. (6) (2) kW kW (4) (5) (2) (4) kW kW kW kW kW (3) (2) kW kW (1) (2) kW kW

0011m
4,50 1,30 3,44 7,30 1,30 5,62 6 1,90 7,90 4,30 1,70 2,60 5,10 1,30 3,92

0021m
5,70 1,60 3,45 9,20 1,70 5,41 7,80 2,40 10 5,50 2,10 2,63 6,50 1,70 3,82

0025m
6,70 1,90 3,48 11 2 5,50 9,20 2,90 11,9 6,60 2,50 2,64 7,70 2 3,85

0031m
7,80 2,30 3,39 12,5 2,40 5,21 10,3 3,40 13,5 7,70 3 2,59 8,90 2,40 3,71

0041m
9,70 2,80 3,51 15,3 2,90 5,28 12,9 4,20 16,8 9,40 3,50 2,69 11 2,90 3,79

0011ms
4,50 1,30 3,44 7,30 1,30 5,62 6 1,90 7,90 4,30 1,70 2,60 5,10 1,30 3,92

0021ms
5,70 1,60 3,45 9,20 1,70 5,41 7,80 2,40 10 5,50 2,10 2,63 6,50 1,70 3,82

0025ms
6,70 1,90 3,48 11 2 5,50 9,20 2,90 11,9 6,60 2,50 2,64 7,70 2 3,85

0031ms
7,80 2,30 3,39 12,5 2,40 5,21 10,3 3,40 13,5 7,70 3 2,59 8,90 2,40 3,71

0041ms
9,70 2,80 3,51 15,3 2,90 5,28 12,9 4,20 16,8 9,40 3,50 2,69 11 2,90 3,79

SCROLL 1 R407C Ci Ci Ci 230-1~50 47 52 38 Ci Ci Ci 230-1~50 61 52 38 Ci Ci Ci 230-1~50 76 53 39 Ci Ci Ci 230-1~50 100 53 39 Ci Ci Ce 230-1~50 114 58 44 560 980 575 188 188 190 195 215 188 188 190 195 215 Ci Ci Ci 230-1~50 21 52 38 Ci Ci Ci 230-1~50 27 52 38 Ci Ci Ci 230-1~50 34 53 39 Ci Ci Ci 230-1~50 45 53 39 Ci Ci Ce 230-1~50 51 58 44

BWR DHW
Nominal heating power Total absorbed power COP Cooling capacity Total absorbed power EER Cooling capacity with total recovery Total absorbed power Recovery heating capacity Heating capacity Total absorbed power COP Cooling capacity Total absorbed power EER Compressor type N. Compressors Refrigerant Plant side pump type Recovery side pump type Source side pump type Electrical power supply Start-up current Sound power Sound pressure level DIMENSION L H P Operational weight mm mm mm kg (8) (9) (7) (7) (7) V-Ph~Hz A dB(A) dB(A) N. (6) (2) kW kW (4) (5) (2) (4) kW kW kW kW kW (3) (2) kW kW (1) (2) kW kW

0021t
5,60 1,60 3,50 9,20 1,60 5,75 7,70 2,30 9,90 5,40 2 2,67 6,50 1,70 3,82

0025t
6,60 1,90 3,51 10,9 1,90 5,74 9,10 2,80 11,7 6,50 2,40 2,67 7,70 2 3,85

0031t
7,70 2,20 3,44 12,4 2,30 5,39 10,3 3,30 13,4 7,50 2,90 2,63 8,80 2,30 3,83

0041t
9,50 2,70 3,56 15,4 2,80 5,50 13,1 4 16,9 9,30 3,40 2,75 10,9 2,80 3,89

0051t
11,4 3,20 3,57 19,1 3,60 5,31 16 4,90 20,6 11,1 4 2,78 13,4 3,40 3,94 SCROLL 1 R407C

0061t
13,9 3,70 3,72 22,5 4,10 5,49 18,9 5,70 24,2 13,3 4,70 2,86 16,1 4 4,03

0071t
18,8 5,10 3,70 30,2 5,50 5,49 25,5 7,70 32,7 17,9 6,50 2,77 21,7 5,40 4,02

0091t
21,2 5,60 3,81 34,4 6,10 5,64 29 8,40 36,9 20,5 7 2,95 24,6 5,90 4,17

0101t
24,4 6,60 3,72 38,9 7,30 5,33 32,7 10,2 42,4 23,5 8,30 2,84 28 7 4,00

0121t
29,7 8,30 3,57 49,7 9,30 5,34 41,1 12,8 53,1 28,4 10,5 2,69 34,8 8,90 3,91

Ci Ci Ci 400-3N~50 32 52 38 560 980 575 188

Ci Ci Ci 400-3N~50 40 52 38 560 980 575 190

Ci Ci Ci 400-3N~50 46 52 38 560 980 575 195

Ci Ci Ce 400-3N~50 50 58 44 560 980 575 215

Ci Ci Ce 400-3N~50 66 58 44 560 980 575 228

Ci Ci Ce 400-3N~50 74 59 45 560 980 575 233

Ce Ci Ce 400-3N~50 95 66 51 680 1150 780 260

Ce Ci Ce 400-3N~50 111 66 51 680 1150 780 270

Ce Ci Ce 400-3N~50 118 70 55 680 1150 780 280

Ce Ci Ce 400-3N~50 140 70 55 680 1150 780 305

Note
BWR DHW

(1) Condenser water in-out 30/35C (plant side), Evaporator water in-out 0/-3C (source side) (2) According to Eurovent (3) Evaporator water in-out 23/18C (plant side), Condenser water in-out 30/35C (source side) (4) Water in-out 23/18C (plant side), water in-out 45/50C (total recovery side) (5) Condenser water in-out 40/45C (plant side), Evaporator water in-out 0/-3C (source side)

(6) Evaporator water in-out 12/7C (plant side), Condenser water in-out 30/35C (source side) (7) Ci=Circolatore; Ce=Centrifuga (8) Sound power level according to ISO 9614 and Eurovent 8/1 (9) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the outside dimensions of the unit.

31