Fault Current Calculation
Fault Current Calculation
Fault Current Calculation
Therefore:
X1 = X2 = 0.169(11000 / 11000)2(5000000/2000000) = 0.4225 pu
The reactance of the transformer is already given on the system base, it will not change X = 0.08 pu The per-unit voltage on the low-voltage side of the transformer is Vpu = actual value / base value = 11000 / 11000 = 1 pu
Thevenin equivalent circuit: Vth = 1 pu Zth = j0.29125 pu Short circuit current (pu) Isc = Vth/Zth = 3.433476 pu Base current on the low voltage side: Ibase = 262.4396 A