Star Delta Calculations
Star Delta Calculations
Star Connection
IL I p
VL 3 V p
Ip
IL Ip IL Ip IL VL Vp VL
Delta Connection
VL VP
IL
IL
Vp
VL
Ip Ip IL
Ip
IL 3 IP
3 Phase Power
P V I p. f (cos )
P 3 VP I P p. f (cos )
In a balanced 3 phase system the total power is equal to three times the power in any one phase
In star and delta, 3 phase power can be calculated using this formula
P 3 V L I L p. f (cos )
A balanced star connected 3 phase load of 10 per phase is supplied from a 400v 50hz mains supply at unity power factor Calculate the phase voltage, the line current and the total power consumed
IL I p
VL 3 V p
VP VL 3
VP
400 3
230 .9V
A balanced star connected 3 phase load of 10 per phase is supplied from a 400v 50hz mains supply at unity power factor Calculate the phase voltage, the line current and the total power consumed
IL I p
V I R VP IL IP RP 230 IL IP 23 A 10
A balanced star connected 3 phase load of 10 per phase is supplied from a 400v 50hz mains supply at unity power factor Calculate the phase voltage, the line current and the total power consumed
P 3 V L I L p. f (cos )
P 3 400 23 1 16 kW
Example 2
A 20kW 400v balanced delta connected load has a power factor of 0.8 Calculate the line current and the phase current
P 3 V L I L p. f (cos )
IL
P 3 V L cos
IL
I L 36 A
Example 2
A 20kW 400v balanced delta connected load has a power factor of 0.8 Calculate the line current and the phase current
I L 36 A
Delta connection therefore
IL 3 IP
IP
IL 3
IP
36 3
I P 20 .78 A