Download as pdf or txt
Download as pdf or txt
You are on page 1of 84

MOULDED CASE CIRCUIT BREAKERS

DS Page
Fixed Overload & Fixed Short-circuit
release with Normal Breaking Capacity
Technical Data 2/9,2/10
l-t Characteristic Curves 2/26
MCCB Ordering Data 2/36
Accessories Ordering Data 2/45
Overall Dimensions 2/56,2/57
DTH..E Page
Fixed Overload & Fixed Short-circuit
release with High Breaking Capacity
Technical Data 2/11
l-t Characteristic Curves 2/27
MCCB Ordering Data 2/36
Accessories Ordering Data 2/46
Overall Dimensions 2/58
DG Page
Adjustable Overload & Fixed Short-circuit
release with Normal Breaking Capacity
Technical Data 2/12
l-t Characteristic Curves 2/28
MCCB Ordering Data 2/37
Accessories Ordering Data 2/47
Overall Dimensions 2/59,2/60
DH Page
Adjustable Overload & Fixed
Short-circuit release with
Standard Breaking Capacity
Technical Data 2/13,2/14
l-t Characteristic Curves 2/29
MCCB Ordering Data 2/38
Accessories Ordering Data 2/48
Overall Dimensions 2/61,2/62
DL Page
Adjustable Overload & Fixed
Short-circuit release with
High Breaking Capacity
Technical Data 2/15
l-t Characteristic Curves 2/30
MCCB Ordering Data 2/39
Accessories Ordering Data 2/49
Overall Dimensions 2/63,2/64
DTH Page
Adjustable Overload & Fixed Short-circuit
release (Conventional MCCBs) with
High Breaking Capacity
Technical Data 2/16,2/17
l-t Characteristic Curves 2/31
MCCB Ordering Data 2/40
Accessories Ordering Data 2/50
Overall Dimensions 2/65,2/66

DX..S Page
Adjustable Overload & adjustable Short-
circuit with standard Breaking Capacity
3 & 4 Pole
Technical Data 2/18,2/19
l-t Characteristic Curves 2/32-2/34
MCCB Ordering Data 2/41
Accessories Ordering Data 2/51,2/52
Overall Dimensions 2/67-2/71
DX..H Page
Adjustable Overload & adjustable Short-
circuit with high Breaking Capacity 3 & 4
Pole
Technical Data 2/20-2/22
l-t Characteristic Curves 2/32-2/35
MCCB Ordering Data 2/42
Accessories Ordering Data 2/51-2/53
Overall Dimensions 2/67-2/75
DM Page
Motor protection MCCBs
Technical Data 2/23
MCCB Ordering Data 2/43
Accessories Ordering Data 2/54
Overall Dimensions 2/76,2/77
Type 2 Co-ordination Chart 2/83
DTH Instantaneous Page
lnstantaneous MCCBs
Technical Data 2/24
MCCB Ordering Data 2/44
Accessories Ordering Data 2/55
Overall Dimensions 2/78
DF Page
Fuse Monitoring device
Technical Data 2/25
Ordering Data 2/44
Accessories Ordering Data 2/55
Overall Dimensions 2/79
Wiring Diagram 2/79
MOULDED CASE CIRCUIT BREAKERS

MOULDED CASE CIRCUIT BREAKERS


L&T was the first company to introduce Moulded case circuit Breakers (MCCBs)" in lndia. Over the years, it has developed &
enhanced the products to growing requirements of market conditions.
L&T MCCBs use latest technologies for circuit interruption under faults. These MCCBs comply with standards lS 13947, lEC 60947
and EN 60947-2 and are certified at independent and approved test authorities.
L&T offers a wide range of MCCBs with current ratings from 0.63A to 1600A in 3-Pole & 4-Pole versions & breaking capacity from
6kA to 100kA. These MCCBs are available with Thermal-Magnetic as well as with Electronic release (above 125A in DX range).
These MCCBs are available in Fixed or Drawout versions. They are also available in utilisation category `A` or `B`.
L&T MCCBs are complemented with a wide variety of internal and external accessories.
APPLICATIONS
Distribution Feeders ldeally suited for incoming and outgoing feeder circuits on distribution boards.
Transformers Provide effective protection to distribution transformers as outgoing breakers on the LT side.
DG Sets Used for protection and control of diesel generating sets against overloads and short circuits.
APFC Systems Suitable for controlling LT capacitors for power factor corrections.
DC Loads Suitable for both AC as well as DC applications. Hence find application in protecting rectifier panels.
UPS Used for UPS & Electronic equipment protection.
Motors Specially designed MCCBs for Motor back-up protection provide Type-2 co-ordination (as per lEC 60947)
in conjunction with suitably rated contactors and relays.
Furnaces Suitable for high frequency systems upto 400Hz and can be used for control of high frequency furnaces.
Also used in induction furnaces along with semiconductor fuses.
WORKING PRINCIPLE
L&T`s new range of MCCBs operate on Current limiting" principle. This
helps in very fast clearance (less than 10 mS) of short-circuit faults. This is
achieved by
1. Quick opening of main contacts.
2. Guiding the arc rapidly away from the contacts into the arcing chamber.
3. Quick quenching of arc by using effective arc quenching devices.
As a result peak short circuit current (l
p
) is limited to cut-off current (l
c
).
Thus, l
2
t let through (proportional to the shaded area) is considerably
reduced, resulting in lower thermal stresses in downstream equipments
and connecting cables.

MOULDED CASE CIRCUIT BREAKERS


PRODUCT HIGHLIGHTS
1. Operating mechanism is quick-make, quick-break and trip free. lt is independent of manual speed of operation. Contacts cannot be
`teased` into position, nor can the breaker be held closed under fault conditions.
2. Clear indication of `ON`, `OFF` & `TPlP` position.
3. Suitable for both AC & DC applications.
4. Terminals suitable for both copper & aluminium terminations.
5. Push to trip" facility to verify healthiness of mechanism.
6. Wide range of site fittable accessories.
7. Low let through energy.
8. No load line bias in new range of MCCBs.
9. Potary operating mechanism has door interlock facility with an option of defeating interlock by an authorized person.
10. Housing is made of heat resistant insulating material.
11. Silver alloy contacts have long electrical life. The mechanism is so designed there is no arcing on the current carrying part of the
contact. The strong wipe action" of the contact system keeps the contact surface clear of oxide films.
MOUNTING POSITION
L&T`s new range of MCCB`s can be mounted up to 90
0
in any direction.
MCCBs FOR MOTOR BACK-UP PROTECTION
MCCBs are increasingly being used in motor application as
a back- up protection device due to following advantages:
Low down time
Peduced running cost
No risking of single phasing
Availability of various accessories
TYPICAL MOTOR FEEDER
A typical motor protection scheme comprises a starter (contractor and thermal overload relay) and a short circuit protective device(SCPD)
e.g.MCCB.
Thermal overload relay provides close protection to the motor against single phasing and moderate overloads like stalling etc. Protection
against higher overcurrents, beyond capability of the starter including short circuit faults is offered by MCCB.
lt is necessary to have proper discrimination between thermal overload relay and SCPD for any effective protection scheme. Type DM
MCCBS are hence designed with instantaneous release to ensure proper discrimination.
FUSE MONITORING DEVICE
L&T`s range of MCCBs also includes the Fuse Monitoring Device type `DF`, designed to monitor the operation of fuse.
ln the motor feeders, where Switch Disconnector Fuse units are used for motor backup protection, there is every possibility of only one of
the three fuses blowing due to a fault, resulting in single phasing. This can be avoided by using Fuse Monitoring Device along with Switch
Disconnector Fuse units of any fuse ratings (refer page 2/79 for connection diagram).
!

ACCESSORIES
INTERNAL
Note : For ordering information, refer pages 2/45 - 2/55
UNDER VOLTAGE RELEASE
The under voltage release is used for protecting the installation against low voltage
situation. The under voltage release is designed to operate when the voltage
drops below a tripping threshold. This can also be used for remote tripping &
electrical interlocking purpose.
The tripping threshold is :
35% to 70% of rated in AC
35% to 70% of rated in DC
Circuit breaker closing is possible only if the voltage exceeds 85% of the rated
voltage.
AUXILIARY CONTACT BLOCK
The auxiliary contact block is used for remote signaling and control purposes.
This consists of one or more than one potential free change-over contacts. lt
indicates the circuit breaker status- whether open or closed.
TRIP ALARM CONTACT
The trip alarm contact gives tripping indication once the MCCB trips. The potential
free change- over contacts can be used for indication or for control circuit.
SHUNT RELEASE
The shunt release provides remote tripping of the circuit breaker. The coil of
shunt release is designed for short time as well as continuous operation (`DX`
range).
The operation voltage is :
85% to 110% of the rated voltage in AC
75% to 125% of the rated voltage in DC
Shunt release coil is short time rated, micro-switch is provided in the release to
cut off the supply. Once the MCCB trips, this prevents burning of coil even if the
supply to shunt coil is continuously fed.
"

ACCESSORIES
FOR 'DX' RANGE
ANNUNCIATION UNIT
Annunciation unit indicates the differential remote and local operating states
like
- Tripping by Overload release
- Tripping be Short-circuit release
- Early-alarm in the event that the Overload release setting is about to be
exceeded.
Annunciation unit has 1NO+1NC.
RESIDUAL CURRENT OPERATED RELAYS
These are factory fitted with adjustable rated fault current and delay time.
MECHANICAL INTERLOCK
For mechanical interlocking of Two or Three MCCBs with Toggle or Potary
drive in the same distribution panel.
PARALLELING MECHANISM
For simultaneous operation of two MCCBs mounted side by side, using a
Potary drive.
SIDE WALL OPERATOR
This is to be used for actuating the Breaker from the side of the control
panel or for changing the Potary movement by 90o
WITHDRAWABLE UNIT
Three position Withdrawable units are available for 3 and 4 PoleMCCBs
(250A and above).
PLUG-IN ADAPTORS
3 pole `DX` range of MCCBs (upto 250A) are also available with plug-in
adaptor modules.
EXTERNAL
PAPALLELlNG MECHANlSM
ELECTPlCAL & MECHANlCAL lNTEPLOCK
ADAPTOR TERMINAL WITH SHROUD / SPREADER
LINKS WITH BARRIERS
Adaptor terminals / Spreader links can be connected to basic MCCBs to facilitate
termination of higher size of cables / links.
The barrier is made of material with high dielectric strength. lt is used to ensure
the electrical clearance between breaker terminals. lt also prevents troubles
caused by contact of conductive material to the terminals.
Shrouds are used on both the sides of MCCB to provide additional safety and
are made of superior insulating material with good mechanical & electrical
properties. The shrouds are designed for click-fit fixing & thus do not need any
fixing hardware. Shroud prevents accidental contact to bare terminals.
ADAPTOP TEPMlNAL
SHPOUD
Note : For ordering information, refer pages 2/45 - 2/55
#

ACCESSORIES
EXTERNAL
ROTARY OPERATING MECHANISM
The circuit breaker has a toggle handle operating mechanism, which also serves
as swtiching position indicator ON, OFF, TPlP. But when the circuit breaker is
installed in switchgear cubicles or distribution boards, it requires to be operated
outside of the switchgear cubicles or distribution boards. The mechanism is
designed for direct attachment to the MCCB and transforms the toggle handle
movement into a rotation. lt facilitates operation of MCCB when the panel door is
closed.
IT'S FEATURES
Easy operation
Door interlock mechanism. lt doesn`t allow the circuit breaker to be ON"
when the door of switchgear cubicles or distribution boards is open thus
prevents the operator from an unsafe condition.
Door interlock defeat facility. This enables only authorized personnel to open
the door with MCCB in ON condition for the purpose of inspection.
FOR 'DX' RANGE
REMOTE OPERATOR (MOTORISED)
For remote `ON` and `OFF` of circuit breakers. Local switching by hand also
possible.
Note : For ordering information, refer pages 2/45 - 2/55
$

EARTH FAULT MODULES (Type GF1, GF2, GF11)


Protection against earth faults
Built-in CBCT solid state design (GF11 to be used with external C.T.)
10 50% adjustable current setting
100 / 200 mS selectable trip time delay
Suitable for both 3 phase 3 wire & 3 phase 4 wire7 systems.
Built in test facility.
Potential free NO contact to trip MCCB through shunt trip.
Manual reset for positive fault acknowledgment
(for Technical / Dimensional Details, refer page 2/80 and 2/81)
EXTERNAL
ACCESSORIES
S. S. ENCLOSURE
Enclosure is made of CPCA material with superior quality paint for better
adherence and to enhance weather resistance.
MCCB mounted in Enclosure is ideally suited to be used as fuseless mains.
Features of EncIosure
lsolable neutral
Earthing terminal
Positive indication of breaker position
Door lock and additional lock on enclosure prevents accidental switching of
MCCB.
(for Dimensional Details, refer page 2/82)
GF11
Note : For ordering information, refer pages 2/45 - 2/55
GF2
GF1
%

ACCESSORIES RANGE
DS DTH..E DG DH DL DTH DX..S DX..H DM DF
Auxiliary Contacts
Standard
Early make - - - - - - - -
General Trip alarm
Contact alarm - - - - - - - -
Separate contact alarm - - - - - - - -
Under voltage release
Non-delayed -
Off-delayed - - - - - - - -
Shunt release
Without early make aux. Contact
With early make aux. Contact - - - - - - - -
Pemote operator - - - - - - - -
Potary operating mechanism -
Paralleling mechanism - - - - - - - -
Mechanical interlock - - - - - - - -
Castell lock - - - - - - - -
Earth-fault module -
Earth-leakage module - - - - - - - -
Plug-in module - - - - - - - -
Withdrawable module - - - - - - - -
Adaptor terminals - - - - - - -
Spreader terminals - - - - -
Enclosure - - - - - - -
Available; Not Available
Note : Accessories mounting / location as per page 2/45 to 2/55
&

ACCESSORIES FOR MCCB


SHUNT PELEASE
TPlP ALAPM
CONTACT
AUXlLlAPY CONTACT
BLOCK
POTAPY OPEPATlNG
MECHANlSM
Uv PELEASE
Note : Except `DX` Pange
'

TECHNICAL DATA - DS
Type Designation DS 100 DS 125 DS 160
Pated Uninterrupted current
at 40
o
C. - lth (AC/DC) A 100 125 160
Pated impulse withstand voltage - Uimp kv 8 8 8
Pated operational voltage - Ue v AC 415 415 415
v DC 250 250 250
Frequency Hz 50/60 50/60 50/60
Pated insulation voltage - Ui v 690 690 690
Operating Temperature C -5 to +55 -5 to +55 -5 to +55
Overvoltage category / pollution degree lll/3 lll/3 lll/3
Pated Short-circuit making capacity - lcm kA 17 17 32
Pated ultimate S.C. breaking capacity - lcu
at 415v ac kA 10 10 16
Pated Service S.C. breaking capacity - lcs
at 415v ac kA 50% 50% 50%
Utilisation category A A A
Mechanical life
Electrical life
Pelease Type Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic
Overload release setting Fixed Fixed Fixed
Short Circuit release setting (+/- 20%) 9*ln 9*ln 8*ln
Weight kg 1.7 1.7 1.7
Terminal capacity Cables mm
2
50 70 95
Links mm 16 22 22
Accessories
Auxiliary contacts (1NO+1NC) (1NO+1NC) (1NO+1NC)
Shunt release y y y
Under voltage release y y y
Trip alarm contacts y y y
Earth fault module y y y
Potary operating mechanism y y y
As per standard lS 13947-2 / lEC 60947-2

TECHNICAL DATA - DS
Type Designation DS 200 DS 250 DS 400
Pated Uninterrupted current
at 40
o
C. - lth (AC/DC) A 200 250 400
Pated impulse withstand voltage - Uimp kv 8 8 8
Pated operational voltage - Ue v AC 415 415 415
v DC 250 250 250
Frequency Hz 50/60 50/60 50/60
Pated insulation voltage - Ui v 690 690 690
Operating Temperature C -5 to +55 -5 to +55 -5 to +55
Overvoltage category / pollution degree lll/3 lll/3 lll/3
Pated Short-circuit making capacity - lcm kA 32 52.5 52.5
Pated ultimate S.C. breaking capacity - lcu
at 415v ac kA 16 25 25
Pated Service S.C. breaking capacity - lcs
at 415v ac kA 50% 50% 50%
Utilisation category A A A
Mechanical life
Electrical life
Pelease Type Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic
Overload release setting Fixed Fixed Fixed
Short Circuit release setting (+/- 20%) 6*ln 6*ln 6*ln
Weight kg 2.4 5 5
Terminal capacity Cables mm
2
150 300 300
Links mm 30 40 40
Accessories
Auxiliary contacts (1NO+1NC) (2NO+2NC) (2NO+2NC)
Shunt release y y y
Under voltage release y y y
Trip alarm contacts y y y
Earth fault module y y y
Potary operating mechanism y y y
As per standard lS 13947-2 / lEC 60947-2

TECHNICAL DATA - DTH...E


Type Designation DTH 200E DTH 250E DTH 400E DTH 630E DTH 800E
Pated Uninterrupted current
at 40
o
C. - lth (AC/DC) A 200 250 400 630 800
Pated impulse withstand voltage - Uimp kv 8 8 8 8
Pated operational voltage - Ue v 415 415 415 415 415
v DC 250 250 250 250 250
Frequency Hz 50/60 50/60 50/60 50/60 50/60
Pated insulation voltage - Ui v 600 600 600 600 600
Operating Temperature C -5 to +55 -5 to +55 -5 to +55 -5 to +55 -5 to +55
Overvoltage category / pollution degree lll/3 lll/3 lll/3 lll/3 lll/3
Pated Short-circuit making capacity - lcm kA 105 105 105 105
Pated ultimate S.C. breaking capacity - lcu
at 660v ac kA 10 10 10 10
at 550v ac kA 25 25 25 25
at 500v ac kA 35 35 35 35
at 415v ac kA 35 50 50 50 50
at 380v ac kA 50 50 50 50
at 240v ac kA 60 60 60 60
Pated Service S.C. breaking capacity - lcs
at 415v ac kA 50% 50% 50% 50%
DC Breaking capacity at 250 v, L/P <= 15mS kA 20 20 20 20 20
Capacitor rating at 415 v, 50 Hz kvAP 70 100 160 240 240
Utilisation category A A A A A
Mechanical life (As per standard) Ops. 8000 8000 8000 8000 8000
Electrical life (As per standard) Ops. 2000 2000 1200 1200 1200
Pelease Type Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic
Overload release setting Fixed Fixed Fixed Fixed Fixed
Short Circuit release setting (+/- 20%) 8*ln 3-8*ln 3-8*ln 3-8*ln 3-8*ln
Weight kg 3 10 10 10 10
Terminal capacity Cables mm
2
185 2*240 2*240 2*240 2*240
Links mm 36 40 (Max. 15 thk.) 40 (Max. 15 thk.) 40 (Max. 15 thk.) 40 (Max. 15 thk.)
Accessories
Auxiliary contacts 1 NO + 1 NC 2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC
Shunt release y y y y y
Under voltage release y y y y y
Earth fault module y y y y y
Potary operating mechanism y y y y y

TECHNICAL DATA - DG
Type Designation DG 125 DG 200 DG 250 DG 400
Pated Uninterrupted current
at 40
o
C. - lth (AC/DC) A 125 200 250 400
Pated impulse withstand voltage - Uimp kv 8 8 8 8
Pated operational voltage - Ue v AC 415 415 415 415
v DC 250 250 250 250
Frequency Hz 50/60 50/60 50/60 50/60
Pated insulation voltage - Ui v 690 690 690 690
Operating Temperature C -5 to +55 -5 to +55 -5 to +55 -5 to +55
Overvoltage category / pollution degree lll/3 lll/3 lll/3 lll/3
Pated ultimate S.C. breaking capacity - lcu
at 415v ac kA 10 16 25 25
Pated Service S.C. breaking capacity - lcs
at 415v ac kA 75% 75% 75% 75%
Utilisation category A A A A
Mechanical life
Electrical life
Pelease Type Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic
Overload release setting 80-100% 80-100% 80-100% 80-100%
Short Circuit release setting (+/- 20%) 4*ln 4*ln 4*ln 4*ln
Weight kg 1.8 2.4 5 5
Terminal capacity Cables mm
2
70 150 300 300
Links mm 22 30 40 40
Accessories
Auxiliary contacts (1NO+1NC) (1NO+1NC) (2NO+2NC) (2NO+2NC)
Shunt release y y y y
Under voltage release y y y y
Trip alarm contacts y y y y
Earth fault module y y y y
Potary operating mechanism y y y y
As per standard lS 13947-2 / lEC 60947-2
!

TECHNICAL DATA - DH
Type Designation DH 100 DH 125 DH 160 DH 200
Pated Uninterrupted current
at 40
o
C. - lth (AC/DC) A 100 125 160 200
Pated impulse withstand voltage - Uimp kv 8 8 8 8
Pated operational voltage - Ue v 415 415 415 415
v DC 250 250 250 250
Frequency Hz 50/60 50/60 50/60 50/60
Pated insulation voltage - Ui v 690 690 690 690
Operating Temperature C -5 to +55 -5 to +55 -5 to +55 -5 to +55
Overvoltage category / pollution degree lll/3 lll/3 lll/3 lll/3
Pated Short-circuit making capacity - lcm kA 52.5 73.5 73.5 73.5
Pated ultimate S.C. breaking capacity - lcu
at 660v ac kA 5 7 7 7
at 550v ac kA 12 18 18 18
at 500v ac kA 18 25 25 25
at 415v ac kA 25 35 35 35
at 380v ac kA 25 35 35 35
at 240v ac kA 50 60 60 60
Pated Service S.C. breaking capacity - lcs
at 415v ac kA 100% 75% 75% 50%
DC Breaking capacity at 250 v, L/P <= 15mS kA 10 10 10 10
Capacitor rating at 415 v, 50 Hz kvAP 35 50 70 70
Utilisation category A A A A
Mechanical life
Electrical life
Pelease Type Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic
Overload release setting 80-100% 80-100% 80-100% 80-100%
Short Circuit release setting (+/- 20%) 9*ln 9*ln 8*ln 6*ln
Weight kg 1.7 1.7 1.7 2.4
Terminal capacity Cables mm
2
50 50 95 150
Links mm 16 16 22 30
Auxiliary contacts (1NO+1NC) (1NO+1NC) (1NO+1NC) (1NO+1NC)
Shunt release y y y y
Under voltage release y y y y
Trip alarm contacts y y y y
Earth fault module y y y y
Potary operating mechanism y y y y
As per standard lS 13947-2 / lEC 60947-2
"

TECHNICAL DATA - DH
Type Designation DH 250 DH 400 DH 630
Pated Uninterrupted current
at 40
o
C. - lth (AC/DC) A 250 400 630
Pated impulse withstand voltage - Uimp kv 8 8 8
Pated operational voltage - Ue v 415 415 415
v DC 250 250 250
Frequency Hz 50/60 50/60 50/60
Pated insulation voltage - Ui v 690 690 690
Operating Temperature C -5 to +55 -5 to +55 -5 to +55
Overvoltage category / pollution degree lll/3 lll/3 lll/3
Pated Short-circuit making capacity - lcm kA 73.5 73.5 73.5
Pated ultimate S.C. breaking capacity - lcu
at 660v ac kA 7 7 7
at 550v ac kA 18 18 18
at 500v ac kA 25 25 25
at 415v ac kA 35 35 35
at 380v ac kA 35 35 35
at 240v ac kA 60 60 60
Pated Service S.C. breaking capacity - lcs
at 415v ac kA 75% 75% 75%
DC Breaking capacity at 250 v, L/P <= 15mS kA 20 20 20
Capacitor rating at 415 v, 50 Hz kvAP 100 160 160
Utilisation category A A A
Mechanical life
Electrical life
Pelease Type Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic
Overload release setting 80-100% 80-100% 80-100%
Short Circuit release setting (+/- 20%) 6*ln 6*ln 6*ln
Weight kg 5.5 5.5 6.5
Terminal capacity Cables mm
2
300 300 400
Links mm 40 40 2x40
Auxiliary contacts (2NO+2NC) (2NO+2NC) (2NO+2NC)
Shunt release y y y
Under voltage release y y y
Trip alarm contacts y y y
Earth fault module y y y
Potary operating mechanism y y y
As per standard lS 13947-2 / lEC 60947-2
#

TECHNICAL DATA - DL
Type Designation DL 100 DL 160 DL 250 DL 400
Pated Uninterrupted current
at 40
o
C. - lth (AC/DC) A 100 160 250 400
Pated impulse withstand voltage - Uimp kv 8 8 8 8
Pated operational voltage - Ue v 415 415 415 415
v DC 250 250 250
Frequency Hz 50/60 50/60 50/60 50/60
Pated insulation voltage - Ui v 690 690 690 690
Operating Temperature C -5 to +55 -5 to +55 -5 to +55 -5 to +55
Overvoltage category / pollution degree lll/3 lll/3 lll/3 lll/3
Pated Short-circuit making capacity - lcm kA 105 105 105 105
Pated ultimate S.C. breaking capacity - lcu
at 660v ac kA 10 10 10 10
at 550v ac kA 25 25 25 25
at 500v ac kA 35 35 35 35
at 415v ac kA 50 50 50 50
at 380v ac kA 50 50 50 50
at 240v ac kA 65 50 65 65
Pated Service S.C. breaking capacity - lcs
at 415v ac kA 100% 100% 100% 100%
DC Breaking capacity at 250 v, L/P <= 15mS kA 20 25 25 25
Capacitor rating at 415 v, 50 Hz kvAP 50 70 100 160
Utilisation category A A A A
Mechanical life Ops.
Electrical life
Pelease Type Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic
Overload release setting 80-100% 80-100% 80-100% 80-100%
Short Circuit release setting (+/- 20%) 9*ln 8*ln 6 ln 6 ln
Weight kg 1.7 1.8 5 5
Terminal capacity Cables mm
2
50 95 300 300
Links mm 16 22 40 40
Accessories
Auxiliary contacts (1NO+1NC) (1NO+1NC) (2NO+2NC) (2NO+2NC)
Shunt release y y y y
Under voltage release y y y y
Trip alarm contacts y y y y
Earth fault module y y y y
Potary operating mechanism y y y y
As per standard lS 13947-2 / lEC 60947-2
$

TECHNICAL DATA - DTH


Type Designation DTH 100 DTH 200
Pated Uninterrupted current
at 40
o
C - lth (AC/DC) A 100 200
Pated impulse withstand voltage - Uimp kv
Pated operational voltage - Ue v 415 415
v DC 250 250
Frequency Hz 50/60 50/60
Pated insulation voltage - Ui v 600 600
Operating Temperature C -5 to +55 -5 to +55
Overvoltage category / pollution degree lll/3 lll/3
Pated ultimate S.C. breaking capacity - P1
at 415v ac kA 10 35
DC Breaking capacity at 250 v, L/P <= 15mS kA 5 20
Capacitor rating at 415 v, 50 Hz kvAP 25 70
Mechanical life Ops. 30000 8000
Electrical life Ops. 4500 2000
Pelease Type Thermal-Magnetic Thermal-Magnetic
Overload release setting 70-100% 70-100%
Short Circuit release setting (+/- 20%) 700 A 8*ln
Weight kg 1.35 3
Terminal capacity Cables mm
2
70 185
Links mm 22.5 36
Accessories
Auxiliary contacts - 1 NO + 1 NC
Shunt release - y
Under voltage release - y
Trip alarm contacts - y
Earth fault module y y
Potary operating mechanism y y
%

TECHNICAL DATA - DTH


Type Designation DTH 250 DTH 400 DTH 630 DTH 800
Pated Uninterrupted current
at 40
o
C. - lth (AC/DC) A 250 400 630 800
Pated impulse withstand voltage - Uimp kv 8 8 8 8
Pated operational voltage - Ue v 415 415 415 415
v DC 250 250 250 250
Frequency Hz 50/60 50/60 50/60 50/60
Pated insulation voltage - Ui v 600 600 600 600
Operating Temperature C -5 to +55 -5 to +55 -5 to +55 -5 to +55
Overvoltage category / pollution degree lll/3 lll/3 lll/3 lll/3
Pated Short-circuit making capacity - lcm kA 105 105 105 105
Pated ultimate S.C. breaking capacity - lcu
at 660v ac kA 10 10 10 10
at 550v ac kA 25 25 25 25
at 500v ac kA 35 35 35 35
at 415v ac kA 50 50 50 50
at 380v ac kA 50 50 50 50
at 240v ac kA 60 60 60 60
Pated Service S.C. breaking capacity - lcs
at 415v ac kA 50% 50% 50% 50%
DC Breaking capacity at 250 v, L/P <= 15mS kA 20 20 20 20
Capacitor rating at 415 v, 50 Hz kvAP 100 160 240 240
Utilisation category A A A A
Mechanical life Ops. 8000 8000 8000 8000
Electrical life Ops. 1200 1200 1200 1200
Pelease Type Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic
Overload release setting 70-100% 70-100% 70-100% 70-100%
Short Circuit release setting (+/- 20%) 3-8*ln 3-8*ln 3-8*ln 3-8*ln
Weight kg 10 10 10 10
Terminal capacity Cables mm
2
2*240 2*240 2*240 2*240
Links mm 40 (Max. 15 thk.) 40 (Max. 15 thk.) 40 (Max. 15 thk.) 40 (Max. 15 thk.)
Accessories
Auxiliary contacts 2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC
Shunt release y y y y
Under voltage release y y y y
Trip alarm contacts y y y y
Earth fault module y y y y
Potary operating mechanism y y y y
&

TECHNICAL DATA - DX..S (3/4 POLE)


Type Designation DX 100S DX 125S DX 160S DX 200S
Pated Uninterrupted current
at 40
o
C. - lth (AC/DC) A 100 125 160 200
Pated impulse withstand voltage - Uimp kv 8 8 8 8
Pated operational voltage - Ue v 415 415 415 415
v DC 440 440 440 440
Frequency Hz 50/60 50/60 50/60 50/60
Pated insulation voltage - Ui v 690 690 690 690
Operating Temperature C -5 to +55 -5 to +55 -5 to +55 -5 to +55
Overvoltage category / pollution degree lll/3 lll/3 lll/3 lll/3
Pated Short-circuit making capacity - lcm kA 94.5 94.5 94.5 94.5
Pated ultimate S.C. breaking capacity - lcu
at 690v ac kA 6 6 6 6
at 500v ac kA 12 12 12 12
at 415v ac kA 35 35 35 35
at 230v ac kA 45 45 45 45
Pated Service S.C.
breaking capacity - lcs (of lcu) kA 100% 100% 100% 100%
DC Breaking capacity at 440 v kA 20 20 20 20
Utilisation category A A A A
Pated short-time withstand current lcw (1 Sec)kA - - - -
Mechanical life Ops. 20000 20000 20000 20000
Electrical life (AC3, 400v) Ops. 6000 6000 6000 3500
Pelease Type Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic
Overload release setting 80-100% 80-100% 80-100% 80-100%
Short Circuit release setting 6-12*ln 6-12*ln 6-12*ln 6-12*ln
Mechanical Shock resistance g 20 20 20 20
Weight (3 - Pole) kg 1.7 1.7 1.7 1.7
(4 - Pole) kg 1.7 1.7 1.7 1.7
Accessories
Auxiliary contacts y y y y
Shunt release y y y y
Under voltage release y y y y
Trip indicating auxiliary contacts y y y y
Earth fault module y y y y
Potary operating mechanism y y y y
Pesidual-current protection module y y y y
Pemote operator y y y y
Withdrawable unit - - - -
Plug-in module y y y y
Mechanical interlock y y y y
Paralleling mechanism y y y y
Load monitoring
'

TECHNICAL DATA - DX..S (3/4 POLE)


Type Designation DX 250S DX 400S DX 630S
Pated Uninterrupted current
at 40
o
C. - lth (AC/DC) A 250 400 630
Pated impulse withstand voltage - Uimp kv 8 8 8
Pated operational voltage - Ue v 415 415 415
v DC 440
Frequency Hz 50/60 50/60 50/60
Pated insulation voltage - Ui v 690 690 690
OperatingTemperature C -5 to +55 -5 to +55 -5 to +55
Overvoltage category / pollution degree lll/3 lll/3 lll/3
Pated Short-circuit making capacity - lcm kA 94.5 220 220
Pated ultimate S.C. breaking capacity - lcu
at 690v ac kA 6 25 25
at 500v ac kA 12 42 42
at 415v ac kA 35 65 65
at 230v ac kA 45 100 100
Pated Service S.C.
breaking capacity - lcs (of lcu) kA 100% 50% 50%
DC Breaking capacity at 440 v kA 20 - -
Utilisation category A A / B A / B
Pated short-time withstand current lcw (1 Sec) kA - 8 8
Mechanical life Ops. 20000 20000 20000
Electrical life (AC3, 400v) Ops. 3500 1250 1250
Pelease Type Thermal-Magnetic Electronic Electronic
Overload release setting 80-100% 50-100% 50-100%
Short Circuit release setting 6-12*ln 2-12*ln 2-12*ln
Mechanical Shock resistance g 20 20 20
Weight (3 - Pole) kg 1.7 9.1 9.1
(4 - Pole) kg 1.7 11.9 11.9
Accessories
Auxiliary contacts y y y
Shunt release y y y
Under voltage release y y y
Trip indicating auxiliary contacts y y y
Earth fault module y y y
Potary operating mechanism y y y
Pesidual-current protection module y y y
Pemote operator y y y
Withdrawable unit - y y
Mechanical interlock y y y
Paralleling mechanism y y y
Load monitoring

Type Designation DX 100H DX 125H DX 160H DX 200H


Pated Uninterrupted current
at 40

C. - lth (AC/DC) A 100 125 160 200


Pated impulse withstand voltage - Uimp kv 8 8 8 8
Pated operational voltage - Ue v 415 415 415 415
v DC 440 440 440 440
Frequency Hz 50/60 50/60 50/60 50/60
Pated insulation voltage - Ui v 690 690 690 690
Operating Temperature C -5 to +55 -5 to +55 -5 to +55 -5 to +55
Overvoltage category / pollution degree lll/3 lll/3 lll/3 lll/3
Pated Short-circuit making capacity - lcm kA 220 550 220 220
Pated ultimate S.C. breaking capacity - lcu
at 690v ac kA 8 8 8 8
at 500v ac kA 20 20 20 20
at 415v ac kA 65 65 65 65
at 230v ac kA 100 100 100 100
Pated Service S.C.
breaking capacity - lcs (of lcu) kA 75% 75% 75% 75%
DC Breaking capacity at 440 v kA 25 25 25 25
Utilisation category A A A A
Pated short-time withstand current lcw (1 Sec) kA - - - -
Mechanical life Ops. 20000 20000 20000 20000
Electrical life (AC3, 400v) Ops. 6000 6000 6000 3500
Pelease Type Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic
Overload release setting 80-100% 80-100% 80-100% 80-100%
Short Circuit release setting 6-12*ln 6-12*ln 6-12*ln 6-12*ln
Mechanical Shock resistance g 20 20 20 20
Weight (3 - Pole) kg 1.7 1.7 1.7 1.7
(4 - Pole) kg 1.7 1.7 1.7 1.7
Accessories
Auxiliary contacts y y y y
Shunt release y y y y
Under voltage release y y y y
Trip indicating auxiliary contacts y y y y
Earth fault module y y y y
Potary operating mechanism y y y y
Pesidual-current protection module y y y y
Pemote operator y y y y
Withdrawable unit - - - -
Plug-in module y y y y
Mechanical interlock y y y y
Paralleling mechanism y y y y
Load monitoring
TECHNICAL DATA - DX..H (3/4 POLE)

TECHNICAL DATA - DX..H (3/4 POLE)


Type Designation DX 250H DX 400H DX 630H DX 800H
Pated Uninterrupted current
at 40

C. - lth (AC/DC) A 250 400 630 800


Pated impulse withstand voltage - Uimp kv 8 8 8 8
Pated operational voltage - Ue v 415 415 415 415
v DC 440
Frequency Hz 50/60 50/60 50/60 50/60
Pated insulation voltage - Ui v 690 690 690 690
Operating Temperature C -5 to +55 -5 to +55 -5 to +55 -5 to +55
Overvoltage category / pollution degree lll/3 lll/3 lll/3 lll/3
Pated Short-circuit making capacity - lcm kA 220 440 440 275
Pated ultimate S.C. breaking capacity - lcu
at 690v ac kA 8 30 30 25
at 500v ac kA 20 65 65 45
at 415v ac kA 65 100 100 65
at 230v ac kA 100 200 200 100
Pated Service S.C.
breaking capacity - lcs (of lcu) kA 75% 50% 50% 75%
DC Breaking capacity at 440 v kA 25 - - -
Utilisation category A A / B A B
Pated short-time withstand current lcw (1 Sec) kA - 8 8 15 (0.3 S)
Mechanical life Ops. 20000 20000 20000 2500
Electrical life (AC3, 400v) Ops. 3500 5000 5000 500 (AC1)
Pelease Type Thermal-Magnetic Electronic Electronic Electronic
Overload release setting 80-100% 50-100% 50-100% 50-100%
Short Circuit release setting 6-12*ln 2-12*ln 2-12*ln 2-12*ln
Mechanical Shock resistance g 20 20 20 20
Weight (3 - Pole) kg 1.7 9.1 9.1 20.4
(4 - Pole) kg 1.7 11.9 11.9 26.4
Accessories
Auxiliary contacts y y y y
Shunt release y y y y
Under voltage release y y y y
Trip indicating auxiliary contacts y y y y
Earth fault module y y y y
Potary operating mechanism y y y y
Pesidual-current protection module y y y -
Pemote operator y y y y
Withdrawable unit - y y y
Mechanical interlock y y y y
Paralleling mechanism y y y -
Load monitoring y

TECHNICAL DATA - DX..H (3/4 POLE)


Type Designation DX 1000H DX 1250H DX 1600H
Pated Uninterrupted current
at 40

C. - lth (AC/DC) A 1000 1250 1600


Pated impulse withstand voltage - Uimp kv 8 8 8
Pated operational voltage - Ue v 415 415 415
Frequency Hz 50/60 50/60 50/60
Pated insulation voltage - Ui v 690 690 690
Operating Temperature C -5 to +55 -5 to +55 -5 to +55
Overvoltage category / pollution degree lll/3 lll/3 lll/3
Pated Short-circuit making capacity - lcm kA 275 275 275
Pated ultimate S.C. breaking capacity - lcu
at 690v ac kA 25 25 45
at 500v ac kA 45 45 65
at 415v ac kA 65 65 85
at 230v ac kA 100 100 125
Pated Service S.C.
breaking capacity - lcs (of lcu) kA 75% 75% 75%
Utilisation category B B B
Pated short-time withstand current lcw (1 Sec) kA 15 (0.3 S) 15 (0.3 S) 20 (0.3 S)
Mechanical life Ops. 2500 2500 2500
Electrical life (AC3, 400v) Ops. 500 (AC1) 500 (AC1) 500 (AC1)
Pelease Type Electronic Electronic Electronic
Overload release setting 50-100% 50-100% 50-100%
Short Circuit release setting 2-12*ln 2-12*ln 2-12*ln
Mechanical Shock resistance g 20 20 20
Weight (3 - Pole) kg 20.4 20.4 20.4
(4 - Pole) kg 26.4 26.4 26.4
Accessories
Auxiliary contacts y y y
Shunt release y y y
Under voltage release y y y
Trip indicating auxiliary contacts y y y
Earth fault module y y y
Potary operating mechanism y y y
Pesidual-current protection module - - -
Pemote operator y y y
Withdrawable unit y y y
Side wall operator - - -
Mechanical interlock y y y
Load monitoring y y y
!

TECHNICAL DATA - DM
Type Designation DM 16 DM 100 DM 160 DM 250 DM 400
Pated Uninterrupted current
at 40
o
C. - lth (AC/DC) A 16 70 160 250 400
Pated impulse withstand voltage - Uimp kv 8 8 8 8 8
Pated operational voltage - Ue v 415 415 415 415 415
Frequency Hz 50/60 50/60 50/60 50/60 50/60
Pated insulation voltage - Ui v 690 690 690 690 690
Operating Temperature C -5 to +55 -5 to +55 -5 to +55 -5 to +55 -5 to +55
Overvoltage category / pollution degree lll/3 lll/3 lll/3 lll/3 lll/3
Pated Short-circuit making capacity - lcm kA 105 105 105 105 105
Pated ultimate S.C. breaking capacity - lcu
at 660v ac kA 10 10 10 10 10
at 550v ac kA 25 25 25 25 25
at 500v ac kA 35 35 35 35 35
at 415v ac kA 50 50 50 50 50
at 380v ac kA 50 50 50 50 50
at 240v ac kA 85 85 85 85 85
Pated Service S.C.
breaking capacity - lcs at 415v ac kA 100% 100% 100% 100% 100%
Utilisation category A A A A A
Mechanical life
Electrical life
Pelease Type Magnetic Magnetic Magnetic Magnetic Magnetic
Short Circuit release setting (+/- 20%) 12*ln 12*ln 12*ln 12*ln 12*ln
Weight kg 1 1.65 4.8 5.5 5.5
Terminal capacity Cables mm
2
10 50 185 300 300
Links mm - 16 36 40 40
Accessories
Auxiliary contacts 1 NO + 1 NC 1 NO + 1 NC 1 NO + 1 NC 2 NO + 2 NC 2 NO + 2 NC
Shunt release y y y y y
Under voltage release y y y y
Trip alarm contacts y y y y y
Potary operating mechanism y y y y y
As per standard lS 13947-2 / lEC 60947-2
"

TECHNICAL DATA - DTH 800 INST.


Type Designation DTH 800 lNST.
Pated Uninterrupted current
at 40
o
C. - lth (AC/DC) A 800
Pated impulse withstand voltage - Uimp kv 8
Pated operational voltage - Ue v 415
Frequency Hz 50/60
Pated insulation voltage - Ui v 600
Operating Temperature C -5 to +55
Overvoltage category / pollution degree lll/3
Pated ultimate S.C. breaking capacity - lcu
at 415v ac kA 50
Pated Service S.C. breaking capacity - lcs
at 415v ac (of lcu) kA 50%
Utilisation category A
Mechanical life Ops. 8000
Electrical life Ops. 1200
Pelease Type Magnetic
Short Circuit release setting (+/- 20%) 360A, 550A, 850A, 1050A
Weight kg 10
Terminal capacity Cables mm
2
2*240
Links mm 40 (Max. 15 thk.)
Accessories
Auxiliary contacts y
Shunt release y
Under voltage release y
Trip alarm contacts y
Earth fault module y
Potary operating mechanism y
#

TECHNICAL DATA - DF
Type Designation DF
Pated Uninterrupted current
at 40
o
C. - lth (AC/DC) A 1
Pated impulse withstand voltage - Uimp kv 8
Pated operational voltage - Ue v 415
Frequency Hz 50/60
Pated insulation voltage - Ui v 600
Operating Temperature C -5 to +55
Overvoltage category / pollution degree lll/3
Pated ultimate S.C. breaking capacity - lcu
at 415v ac kA 50
Magnetic Threshold A 2
Mechanical life Ops. 10000
Electrical life Ops. 6000
Overload release setting (Fixed) A 1
Weight kg 0.65
Terminal capacity Without lugs mm
2
4
With lugs mm
2
16
Accessories
Auxiliary contact 1 CO, 5A-250v
Shunt release y
Auxiliary contact y
Trip alarm contacts y
$

I-t CHARACTERISTIC CURVES


MCCB - TYPE DS
Note: Short Circuit tripping values indicated as multiple of rated current
DS 100 DS 125/160
DS 200 DS 250/400
%

I-t CHARACTERISTIC CURVES


MCCB - TYPE DTH...E
Note: Short Circuit tripping values indicated as multiple of rated current
DTH 200E DTH 250E
DTH 400E DTH 630E DTH 800E
&

I-t CHARACTERISTIC CURVES


MCCB - TYPE DG
Note: Short Circuit tripping values indicated as multiple of rated current
DG 125 DG 160
DG 200 DG 250/400
'

I-t CHARACTERISTIC CURVES


MCCB - TYPE DH
Note: Short Circuit tripping values indicated as multiple of rated current
DH 100/125 DH 160
DH 200 DH 250/400/630
!

I-t CHARACTERISTIC CURVES


MCCB - TYPE DL
Note: Short Circuit tripping values indicated as multiple of rated current
DL 100 DL 160
DL 250/400
!

I-t CHARACTERISTIC CURVES


MCCB - TYPE DTH
Note: Short Circuit tripping values indicated as multiple of rated current
DTH 100 DTH 200 DTH 250
DTH 400 DTH 630 DTH 800
!

I-t CHARACTERISTIC CURVES


DX 100-250 S/H (3/4 POLE)
Note: Short Circuit tripping values indicated as multiple of rated current
!!

I-t CHARACTERISTIC CURVES


DX 400 S/H (3/4 POLE)
Note: Short Circuit tripping values indicated as multiple of rated current
# #
!"

I-t CHARACTERISTIC CURVES


DX 630 S/H (3/4 POLE)
Note: Short Circuit tripping values indicated as multiple of rated current
!#

I-t CHARACTERISTIC CURVES


DX 800-1600 H (3/4 POLE)
Note: Short Circuit tripping values indicated as multiple of rated current
DX 800 H DX 1000 H
DX 1250 H DX 1600 H
!$

ORDERING DATA - DS RANGE


MCCB Pating Current Breaking Overload Short-Circuit Std. Catalogue No. Ordering
(A) Pating (A) Capacity, lcu(kA) Setting (A) Setting Pack Suffix
DS 100 100 16 10 16 9*ln 12 SL97917 OOOO
20 10 20 9*ln 12 SL97918 OOOO
25 10 25 9*ln 12 SL97919 OOOO
32 10 32 9*ln 12 SL97920 OOOO
40 10 40 9*ln 12 SL97921 OOOO
50 10 50 9*ln 12 SL97922 OOOO
63 10 63 9*ln 12 SL97923 OOOO
80 10 80 9*ln 12 SL97924 OOOO
100 10 100 9*ln 12 SL97925 OOOO
DS 125 125 125 10 125 9*ln 12 SL97929 OOOO
DS 160 160 160 16 160 9*ln 12 SL97930 OOOO
DS 200 200 200 16 200 6*ln 12 SL97931 OOOO
DS 250 250 250 25 250 6*ln 1 SL94541 OOOO
DS 400 320 320 25 320 6*ln 1 SL94542 OOOO
400 400 25 400 6*ln 1 SL94543 OOOO
ORDERING DATA - DTH...E RANGE
MCCB Pating Current Breaking Overload Short-Circuit Std. Catalogue No. Ordering
(A) Pating (A) Capacity, lcu(kA) Setting (A) Setting Pack Suffix
DTH 200E 200 200 35 200 8*ln 1 ST 30513 OOOO
DTH 250E 250 250 50 250 3-8*ln 1 ST 30543 OOOO
DTH 400E 400 400 50 400 3-8*ln 1 ST 30545 OOOO
DTH 630E 630 630 50 630 3-8*ln 1 ST 30514 OOOO
DTH 800E 800 800 50 800 3-8*ln 1 ST 30546 OOOO
!%

ORDERING DATA - DG RANGE


MCCB Pating Current Breaking Overload Short-Circuit Std. Catalogue No. Ordering
(A) Pating (A) Capacity, lcu(kA) Setting (A) Setting Pack Suffix
DG 125 125 16 10 12 - 16 6*ln 1 SL97941 OOOO
20 10 16 - 20 6*ln 1 SL97942 OOOO
25 10 20 - 25 6*ln 1 SL97943 OOOO
32 10 25 - 32 6*ln 1 SL97944 OOOO
40 10 32 - 40 6*ln 1 SL97945 OOOO
50 10 40 - 50 6*ln 1 SL97946 OOOO
63 10 50 - 63 4*ln 1 SL97947 OOOO
80 10 63 - 80 4*ln 1 SL97948 OOOO
100 10 80 - 100 4*ln 1 SL97949 OOOO
125 10 100 - 125 4*ln 1 SL97950 OOOO
DG 200 200 160 16 128 - 160 4*ln 1 SL97951 OOOO
200 16 160 - 200 4*ln 1 SL97953 OOOO
DG 250 250 250 25 200 - 250 4*ln 1 SL97957 OOOO
DG 400 400 320 25 250 - 320 4*ln 1 SL97958 OOOO
400 25 320 - 400 4*ln 1 SL97959 OOOO
!&

ORDERING DATA - DH RANGE


MCCB Pating Current Breaking Overload Short-Circuit Std. Catalogue No. Ordering
(A) Pating (A) Capacity, lcu(kA) Setting (A) Setting Pack Suffix
DH 100 100 16 25 12 - 16 9*ln 1 SL 97201 OOOO
20 25 16 - 20 9*ln 1 SL 97202 OOOO
25 25 20 - 25 9*ln 1 SL 97203 OOOO
32 25 25 - 32 9*ln 1 SL 97204 OOOO
40 25 32 - 40 9*ln 1 SL 97205 OOOO
50 25 40 - 50 9*ln 1 SL 97206 OOOO
63 25 50 - 63 9*ln 1 SL 97207 OOOO
80 25 63 - 80 9*ln 1 SL 97208 OOOO
100 25 80 - 100 9*ln 1 SL 97209 OOOO
DH 125 125 16 35 12 - 16 9*ln 1 SL 98556 OOOO
20 35 16 - 20 9*ln 1 SL 98557 OOOO
25 35 20 - 25 9*ln 1 SL 98558 OOOO
32 35 25 - 32 9*ln 1 SL 98559 OOOO
40 35 32 - 40 9*ln 1 SL 98560 OOOO
50 35 40 - 50 9*ln 1 SL 98561 OOOO
63 35 50 - 63 9*ln 1 SL 98562 OOOO
80 35 63 - 80 9*ln 1 SL 98563 OOOO
100 35 80 - 100 9*ln 1 SL 98564 OOOO
125 35 100 - 125 9*ln 1 SL 98555 OOOO
DH 160 160 160 35 128 - 160 8*ln 1 SL 98566 OOOO
DH 200 200 200 35 160 - 200 6*ln 1 SL 97869 OOOO
DH 250 250 200 35 160 - 200 6*ln 1 SL 97881 OOOO
250 35 200 - 250 6*ln 1 SL 97882 OOOO
DH 400 400 320 35 250 - 320 6*ln 1 SL 97883 OOOO
400 35 320 - 400 6*ln 1 SL 97884 OOOO
DH 630 630 500 35 400 - 500 6*ln 1 SL 94531 OOOO
630 35 500 - 630 6*ln 1 SL 94532 OOOO
!'

ORDERING DATA - DL RANGE


MCCB Pating Current Breaking Overload Short-Circuit Std. Catalogue No. Ordering
(A) Pating (A) Capacity, lcu(kA) Setting (A) Setting Pack Suffix
DL 100 100 16 50 12 - 16 9*ln 1 SL 97801 OOOO
20 50 16 - 20 9*ln 1 SL 97802 OOOO
25 50 20 - 25 9*ln 1 SL 97803 OOOO
32 50 25 - 32 9*ln 1 SL 97804 OOOO
40 50 32 - 40 9*ln 1 SL 97805 OOOO
50 50 40 - 50 9*ln 1 SL 97806 OOOO
63 50 50 - 63 9*ln 1 SL 97807 OOOO
80 50 63 - 80 9*ln 1 SL 97808 OOOO
100 50 80 - 100 9*ln 1 SL 97809 OOOO
DL 160 160 100 50 80 - 100 8*ln 1 SL97128 OOOO
125 50 100 - 125 8*ln 1 SL 97129 OOOO
160 50 128 - 160 8*ln 1 SL 97130 OOOO
DL 250 250 200 50 160 - 200 6*ln 1 SL 97541 OOOO
250 50 200 - 250 6*ln 1 SL 97542 OOOO
DL 400 400 320 50 250 - 320 6*ln 1 SL 97543 OOOO
400 50 320 - 400 6*ln 1 SL 97544 OOOO
"

ORDERING DATA - DTH RANGE


MCCB Pating Current Breaking Overload Short-Circuit Std. Catalogue No. Ordering
(A) Pating (A) Capacity, lcu(kA) Setting (A) Setting Pack Suffix
DTH 100 100 16 6 12 - 16 700 1 SL 94473 OOOO
20 6 16 - 20 700 1 SL 94474 OOOO
25 6 20 - 25 700 1 SL 94475 OOOO
32 6 25 - 32 700 1 SL 94476 OOOO
40 6 30 - 40 700 1 SL 94477 OOOO
50 6 38 - 50 700 1 SL 94478 OOOO
63 8 48 - 63 700 1 SL 94479 OOOO
80 10 60 - 80 700 1 SL 94480 OOOO
100 10 70 -100 700 1 SL 94481 OOOO
DTH 200 200 100 35 70 -100 8*ln 1 SL 94512 OOOO
125 35 90 -125 8*ln 1 SL 94513 OOOO
160 35 120 -160 8*ln 1 SL 94514 OOOO
200 35 140 -200 8*ln 1 SL 94515 OOOO
DTH 250 250 175 50 125 - 175 3-8*ln 1 SL 94466 OOOO
250 50 175 - 250 3-8*ln 1 SL 94467 OOOO
DTH 400 400 320 50 225 - 320 3-8*ln 1 SL 94468 OOOO
400 50 280 - 400 3-8*ln 1 SL 94469 OOOO
DTH 630 630 500 50 360 - 500 3-8*ln 1 SL 94470 OOOO
630 50 460 - 630 3-8*ln 1 SL 94471 OOOO
DTH 800 800 800 50 600 - 800 3-8*ln 1 SL 94472 OOOO
ORDERING DATA - DTH 100 4-POLE
MCCB Pating Current Breaking Overload Short-Circuit Std. Catalogue No. Ordering
(A) Pating (A) Capacity, lcu(kA) Setting (A) Setting Pack Suffix
DTH 100 100 100 6 12 - 16 700 1 SL 94525 OOBO
100 6 16 - 20 700 1 SL 94525 OOCO
100 6 20 - 25 700 1 SL 94525 OODO
100 6 25 - 32 700 1 SL 94525 OOEO
100 6 30 - 40 700 1 SL 94525 OOFO
100 6 38 - 50 700 1 SL 94525 OOGO
100 8 48 - 63 700 1 SL 94525 OOHO
100 10 60 - 80 700 1 SL 94526 OOOO
100 10 70 -100 700 1 SL 94525 OOOO
"

ORDERING DATA - DX..S (3 POLE)


MCCB Pating Utilisation Current Breaking Overload Short-Circuit Std. Catalogue No. Ordering
(A) Category Pating (A) Capacity, lcu(kA) Setting (A) Setting Pack Suffix
DX 100S 100 A 40 35 25 - 40 9.5*ln 1 ST 31038 OOOO
63 35 40 - 63 6-12*ln 1 ST 31039 OOOO
80 35 63 - 80 6-12*ln 1 ST 31040 OOOO
100 35 80 - 100 6-12*ln 1 ST 31041 OOOO
DX 125S 125 A 125 35 80 - 125 6-12*ln 1 ST 31042 OOOO
DX 160S 160 A 160 35 125 - 160 6-12*ln 1 ST 31043 OOOO
DX 200S 200 A 200 35 160 - 200 6-12*ln 1 ST 31044 OOOO
DX 250S 250 A 250 35 200 - 250 6-10*ln 1 ST 31045 OOOO
DX 400S 400 A / B* 250 65 125 - 250 2-12*ln 1 ST 31058 OOOO
A / B* 400 65 200 - 400 2-12*ln 1 ST 31059 OOOO
DX 630S 630 A / B* 630 65 300 - 630 2-12*ln 1 ST 31060 OOOO
ORDERING DATA - DX..S (4 POLE)
MCCB Pating Utilisation Current Breaking Overload Short-Circuit Std. Catalogue No. Ordering
(A) Category Pating (A) Capacity, lcu(kA) Setting (A) Setting Pack Suffix
DX 100S 100 A 40 35 25 - 40 9.5*ln 1 ST 31001 OOOO
63 35 40 - 63 6-12*ln 1 ST 31002 OOOO
80 35 63 - 80 6-12*ln 1 ST 31003 OOOO
100 35 80 - 100 6-12*ln 1 ST 31004 OOOO
DX 125S 125 A 125 35 80 - 125 6-12*ln 1 ST 31005 OOOO
DX 160S 160 A 160 35 125 - 160 6-12*ln 1 ST 31006 OOOO
DX 200S 200 A 200 35 160 - 200 6-12*ln 1 ST 31007 OOOO
DX 250S 250 A 250 35 200 - 250 6-10*ln 1 ST 31008 OOOO
DX 400S 400 A / B* 250 65 125 - 250 2-12*ln 1 ST 31019 OOOO
A / B* 400 65 200 - 400 2-12*ln 1 ST 31021 OOOO
DX 630S 630 A / B* 630 65 300 - 630 2-12*ln 1 ST 31023 OOOO
* To be specified
"

ORDERING DATA - DX..H (3 POLE)


MCCB Pating Utilisation Current Breaking Overload Short-Circuit Std. Catalogue No. Ordering
(A) Category Pating (A) Capacity, lcu(kA) Setting (A) Setting Pack Suffix
DX 100H 100 A 40 65 25 - 40 9.5*ln 1
63 65 40 - 63 6-12*ln 1
80 65 63 - 80 6-12*ln 1
100 65 80 - 100 6-12*ln 1
DX 125H 125 A 125 65 80 - 125 6-12*ln 1
DX 160H 160 A 160 65 125 - 160 6-12*ln 1
DX 200H 200 A 200 65 160 - 200 6-12*ln 1
DX 250H 250 A 250 65 200 - 250 6-10*ln 1
DX 400H 400 A 250 100 125 - 250 2-12*ln 1 ST 31046 OOOO
400 100 200 - 400 2-12*ln 1 ST 31047 OOOO
DX 630H 630 A 630 100 300 - 630 2-12*ln 1 ST 31048 OOOO
DX 800H 800 B 800 85 400 - 800 3-12*ln 1 ST 31049 OOOO
DX 1000H 1000 B 1000 85 500 - 1000 3-12*ln 1 ST 31050 OOOO
DX 1250H 1250 B 1250 85 630 - 1250 3-12*ln 1 ST 31051 OOOO
DX 1600H 1600 B 1600 100 800 - 1600 3-12*ln 1 ST 31052 OOOO
ORDERING DATA - DX..H (4 POLE)
MCCB Pating Utilisation Current Breaking Overload Short-Circuit Std. Catalogue No. Ordering
(A) Category Pating (A) Capacity, lcu(kA) Setting (A) Setting Pack Suffix
DX 100H 100 A 40 65 25 - 40 9.5*ln 1 ST 31011 OOOO
63 65 40 - 63 6-12*ln 1 ST 31012 OOOO
80 65 63 - 80 6-12*ln 1 ST 31013 OOOO
100 65 80 - 100 6-12*ln 1 ST 31014 OOOO
DX 125H 125 A 125 65 80 - 125 6-12*ln 1 ST 31015 OOOO
DX 160H 160 A 160 65 125 - 160 6-12*ln 1 ST 31016 OOOO
DX 200H 200 A 200 65 160 - 200 6-12*ln 1 ST 31017 OOOO
DX 250H 250 A 250 65 200 - 250 6-10*ln 1 ST 31018 OOOO
DX 400H 400 A 250 100 125 - 250 2-12*ln 1 ST 31020 OOOO
400 100 200 - 400 2-12*ln 1 ST 31022 OOOO
DX 630H 630 A 630 100 300 - 630 2-12*ln 1 ST 31024 OOOO
DX 800H 800 B 800 85 400 - 800 3-12*ln 1 ST 31025 OOOO
DX 1000H 1000 B 1000 85 500 - 1000 3-12*ln 1 ST 31026 OOOO
DX 1250H 1250 B 1250 85 630 - 1250 3-12*ln 1 ST 31027 OOOO
DX 1600H 1600 B 1600 100 800 - 1600 3-12*ln 1 ST 31028 OOOO
"!

ORDERING DATA - DM RANGE


MCCB Pating Current Breaking Overload Short-Circuit Std. Catalogue No. Ordering
(A) Pating (A) Capacity, lcu(kA) Setting (A) Setting Pack Suffix
DM 16 16 0.63 50 0.63 12*ln 1 SL 97581 OOOO
1.0 50 1.0 12*ln 1 SL 97582 OOOO
1.6 50 1.6 12*ln 1 SL 97583 OOOO
2.5 50 2.5 12*ln 1 SL 97584 OOOO
4.0 50 4.0 12*ln 1 SL 97585 OOOO
5.0 50 5.0 12*ln 1 SL 97586 OOOO
6.3 50 6.3 12*ln 1 SL 97587 OOOO
7.5 50 7.5 12*ln 1 SL 97588 OOOO
10 50 10 12*ln 1 SL 97589 OOOO
12 50 12 12*ln 1 SL 97590 OOOO
16 50 16 12*ln 1 SL 97591 OOOO
DM 100 100 16 50 16 12*ln 1 SL 97811 OOOO
25 50 25 12*ln 1 SL 97812 OOOO
30 50 30 12*ln 1 SL 97816 OOOO
35 50 35 12*ln 1 SL 97813 OOOO
50 50 50 12*ln 1 SL 97814 OOOO
60 50 60 12*ln 1 SL 97817 OOOO
70 50 70 12*ln 1 SL 97815 OOOO
DM 160 160 100 50 100 12*ln 1 SL 97123 OOOO
120 50 120 12*ln 1 SL 97703 OOOO
160 50 160 12*ln 1 SL 97124 OOOO
DM 250 250 200 50 200 12*ln 1 SL 97551 OOOO
230 50 230 12*ln 1 SL 97552 OOOO
250 50 250 12*ln 1 SL 97553 OOOO
DM 400 400 275 50 275 12*ln 1 SL 97554 OOOO
325 50 325 12*ln 1 SL 97555 OOOO
350 50 350 12*ln 1 SL 97556 OOOO
400 50 400 12*ln 1 SL 97557 OOOO
""

ORDERING DATA - DTH INST. RANGE


MCCB Pating Current Breaking Overload Short-Circuit Std. Catalogue No. Ordering
(A) Pating (A) Capacity, lcu(kA) Setting (A) Setting Pack Suffix
DTH 800 800 800 50 - 360 1 SB 95052 OOOO
800 50 - 550 1 SB 95053 OOOO
800 50 - 850 1 SB 95054 OOOO
800 50 - 1050 1 SB 95055 OOOO
ORDERING DATA - DF
MCCB Thermal Pating Breaking Magnetic Threshold Std. Pack Catalogue No. Ordering
(A) Capacity, lcu(kA) (A) Suffix
DF 1 50 2 1 SL 97020 OOOO
FUSE MONITORING DEVICE
"#

Note : Any two internal accessories can be fitted simultaneously in a breaker


P To be mounted on right side
L To be mounted on left side
L/P Can be mounted on either side
Ext. External
* Along with DS400
1) Dimension on page 2/82
2) Dimension and wiring diagram on pages 2/80 & 2/81
Accessory Coil voltage / Location Std. Pack Catalogue No. Ordering
Type Suffix
DS 100/125/160/200
Shunt Pelease 110/240/415 v AC L 1 SL 97299 OMOO
24 v DC L 1 SL 97299 O4OO
Under voltage Pelease 415 v AC L 1 SL 97610 OOOO
240 v AC L 1 SL 97611 OOOO
Auxiliary contact Block 1 NO + 1 NC P 1 SL 97296 OOOO
L 1 SL 97297 OOOO
Trip Alarm contact - P 1 SL 97298 OOOO
Potary operating handle Ext. 1 SL 97301 OOOO
Earth Fault module
2)
GF1 Ext. 1 ST 27745 OOOO
S S Enclosure
1)
- Ext. 1 ST 29967 OOOO
DS 250/400
Shunt Pelease 415 v AC/220 v DC P / L 1 SL 97575 OOOO
240 v AC/110 v DC P / L 1 SL 97576 OOOO
Under voltage Pelease 415 v AC L 1 SL 97579 OOOO
240 v AC L 1 SL 97580 OOOO
Auxiliary contact Block 2 NO + 2 NC L / P 1 SL 97573 OOOO
Trip Alarm contact - P 1 SL 97574 OOOO
Spreader Links with Barrier * - Ext. 1 Std. Kit
Potary operating handle POM Ext. 1 SL 97562 OOOO
Earth Fault module
2)
GF2 Ext. 1 ST 27746 OOOO
ACCESSORIES - ORDERING DATA
TYPE DS
"$

Note : Any two internal accessories can be fitted simultaneously in a breaker


P To be mounted on right side
L To be mounted on left side
L/P Can be mounted on either side
Ext. External
* 24 v, 48 v, 110 v & 220 v DC are also available on request
1) Dimension and wiring diagram on pages 2/80 & 2/81
Accessory Coil voltage / Location Std. Pack Catalogue No. Ordering
Type Suffix
DTH 200E
Shunt Pelease 415 v AC/220 v DC P 1 SL 94331 ODOO
240 v AC/110 v DC 1 SL 94331 OBOO
110 v AC 1 SL 94331 OAOO
Under voltage Pelease* 415 v AC L 1 SL 94332 DOOO
240 v AC 1 SL 94332 BOOO
110 v AC 1 SL 94332 AOOO
Auxiliary contact Block 1 NO + 1 NC P 1 SL 94330 OOOO
L 1 SL 94329 OOOO
Potary operating mechanism POM Ext. 1 SL 94336 OOOO
Earth Fault module
1)
GF2 Ext. 1 ST 27746 OOOO
DTH 250E / 400E / 630E / 800E
Shunt Pelease 110 v AC P 1 SL 98523 OOOO
415 v AC/220 v DC P 1 SL 98526 OOOO
24 v DC L 1 SL 98531 OOOO
240 v AC/110 v DC P 1 SL 98534 OOOO
Under voltage Pelease 110 v AC L 1 SL 98543 OOOO
240 v AC L 1 SL 98545 OOOO
415 v AC L 1 SL 98548 OOOO
Auxiliary contact Block 1 NO + 1 NC L / P 1 SL 94217 OOOO
Potary operating mechanism POM 1 SL 94337 OOOO
Earth Fault module
1)
GF11 1 ST 28594 OOOO
ACCESSORIES - ORDERING DATA
TYPE DTH..E
"%

Note : Any two internal accessories can be fitted simultaneously in a breaker


P To be mounted on right side
L To be mounted on left side
L/P Can be mounted on either side
Ext. External
* To be used with DS 125 & above
1) Dimension on page 2/82
2) Dimension and wiring diagram on pages 2/80 & 2/81
Accessory Coil voltage / Location Std. Pack Catalogue No. Ordering
Type Suffix
DG 125/200
Shunt Pelease 110/240/415 v AC L 1 SL 97299 OMOO
24 v DC L 1 SL 97299 O4OO
Under voltage Pelease 415 v AC L 1 SL 97610 OOOO
240 v AC L 1 SL 97611 OOOO
Auxiliary contact Block 1 NO + 1 NC P 1 SL 97296 OOOO
L 1 SL 97297 OOOO
Trip Alarm contact - P 1 SL 97298 OOOO
Potary operating handle Ext. 1 SL 97301 OOOO
Spreader Links with Barrier Ext. 1 Std. Kit
Earth Fault module
2)
GF1 Ext. 1 ST 27745 OOOO
S S Enclosure
1)
- Ext. 1 ST 29967 OOOO
DG 250/400
Shunt Pelease 415 v AC/220 v DC P / L 1 SL 97575 OOOO
240 v AC/110 v DC P / L 1 SL 97576 OOOO
Under voltage Pelease 415 v AC L 1 SL 97579 OOOO
240 v AC L 1 SL 97580 OOOO
Auxiliary contact Block 2 NO + 2 NC L / P 1 SL 97573 OOOO
Trip Alarm contact - P 1 SL 97574 OOOO
Spreader Links with Barrier * - Ext. 1 Std. Kit
Potary operating mechanism POM Ext. 1 SL 97562 OOOO
Earth Fault module
2)
GF2 Ext. 1 ST 27746 OOOO
ACCESSORIES - ORDERING DATA
TYPE DG
"&

Note : Any two internal accessories can be fitted simultaneously in a breaker


P To be mounted on right side
L To be mounted on left side
L/P Can be mounted on either side
Ext. External
* To be used with DS 125 & above
# To be used with DH 630
1) Dimension on page 2/82
2) Dimension and wiring diagram on pages 2/80 & 2/81
Accessory Coil voltage / Location Std. Pack Catalogue No. Ordering
Type Suffix
DH 100/125/160/200
Shunt Pelease 110/240/415 v AC L 1 SL 97299 OMOO
24 v DC L 1 SL 97299 O4OO
Under voltage Pelease 415 v AC L 1 SL 97610 OOOO
240 v AC L 1 SL 97611 OOOO
Auxiliary contact Block 1 NO + 1 NC P 1 SL 97296 OOOO
L 1 SL 97297 OOOO
Trip Alarm contact - P 1 SL 97298 OOOO
Potary operating mechanism POM Ext. 1 SL 97301 OOOO
Adaptor terminal with shroud Ext. 1
Terminal shroud Ext. 1
Spreader Links with Barrier Ext. 1
Earth Fault module
2)
GF1 Ext. 1 ST 27745 OOOO
S S Enclosure
1)
- Ext. 1 ST 29967 OOOO
DH 250/400/630
Shunt Pelease 415 v AC/220 v DC P / L 1 SL 97575 OOOO
240 v AC/110 v DC P / L 1 SL 97576 OOOO
Under voltage Pelease 415 v AC L 1 SL 97579 OOOO
240 v AC L 1 SL 97580 OOOO
Auxiliary contact Block 1 NO + 1 NC L / P 1 SL 97573 OOOO
Trip Alarm contact - P 1 SL 97574 OOOO
Adaptor terminal (3) with shroud (1) - 1 Set - Ext. 1 SL 97564 OOOO
Terminal shroud - Ext. 1 SL 97563 OOOO
Spreader Links with Barrier * - Ext. 1 Std. Kit
Potary operating mechanism POM Ext. 1 SL 97562 OOOO
Earth Fault module
2)
GF2 Ext. 1 ST 27746 OOOO
GF11# Ext. 1 ST28594 OOOO
ACCESSORIES - ORDERING DATA
TYPE DH
"'

ACCESSORIES - ORDERING DATA


TYPE DL
Note : Any two internal accessories can be fitted simultaneously in a breaker
P To be mounted on right side
L To be mounted on left side
L/P Can be mounted on either side
Ext. External
* 24 v, 48 v, 110 v & 220 v DC are also available on request
# On request
1) Dimension on page 2/82
2) Dimension and wiring diagram on pages 2/80 & 2/81
Accessory Coil voltage / Location Std. Pack Catalogue No. Ordering
Type Suffix
DL 100
Shunt Pelease 110/240/415 v AC L 1 SL 97299 OMOO
24 v DC L 1 SL 97299 O4OO
Under voltage Pelease 415 v AC L 1 SL 97610 OOOO
240 v AC L 1 SL 97611 OOOO
Auxiliary contact Block 1 NO + 1 NC P 1 SL 97296 OOOO
L 1 SL 97297 OOOO
Trip Alarm contact - P 1 SL 97298 OOOO
Potary operating handle Ext. 1 SL 97301 OOOO
Earth Fault module
2)
GF1 Ext. 1 ST 27745 OOOO
S S Enclosure
1)
- Ext. 1 ST 29967 OOOO
DL 160
Shunt Pelease 415 v AC/220 v DC P 1 SL 94331 ODOO
240 v AC/110 v DC 1 SL 94331 OBOO
110 v AC 1 SL 94331 OAOO
Under voltage Pelease* 415 v AC L 1 SL 94332 DOOO
240 v AC 1 SL 94332 BOOO
110 v AC 1 SL 94332 AOOO
Auxiliary contact Block 1 NO + 1 NC P 1 SL 94330 OOOO
L 1 SL 94329 OOOO
Trip Alarm contact # - P 1 Factory assembled
Potary operating mechanism POM Ext. 1 SL 94336 OOOO
Earth Fault module
2)
GF2 Ext. 1 ST 27746 OOOO
DL 250/400
Shunt Pelease 415 v AC/220 v DC P / L 1 SL 97575 OOOO
240 v AC/110 v DC P / L 1 SL 97576 OOOO
Under voltage Pelease 415 v AC L 1 SL 97579 OOOO
240 v AC L 1 SL 97580 OOOO
Auxiliary contact Block 1 NO + 1 NC L / P 1 SL 97573 OOOO
Trip Alarm contact - P 1 SL 97574 OOOO
Spreader Links with Barrier - Ext. 1 Std. Kit
Potary operating mechanism POM Ext. 1 SL 97562 OOOO
Earth Fault module
2)
GF2 Ext. 1 ST 27746 OOOO
#

ACCESSORIES - ORDERING DATA


TYPE DTH
Note : Any two internal accessories can be fitted simultaneously in a breaker
P To be mounted on right side
L To be mounted on left side
L/P Can be mounted on either side
Ext. External
* 24 v, 48 v, 110 v & 220 v DC are also available on request
# On request.
1) Dimension and wiring diagram on pages 2/80 & 2/81
Accessory Coil voltage / Location Std. Pack Catalogue No. Ordering
Type Suffix
DTH 100
Potary operating handle - Ext. 1 SL 94286 OOOO
Earth Fault module
1)
GF1 Ext. 1 ST 27745 OOOO
DTH 200
Shunt Pelease 415 v AC/220 v DC P 1 SL 94331 ODOO
240 v AC/110 v DC 1 SL 94331 OBOO
110 v AC 1 SL 94331 OAOO
Under voltage Pelease* 415 v AC L 1 SL 94332 DOOO
240 v AC 1 SL 94332 BOOO
110 v AC 1 SL 94332 AOOO
Auxiliary contact Block 2 NO + 2 NC P 1 SL 94330 OOOO
L 1 SL 94329 OOOO
Trip Alarm contact # - P 1 Factory assembled
Potary operating mechanism POM Ext. 1 SL 94336 OOOO
Earth Fault module
1)
GF2 Ext. 1 ST 27746 OOOO
DTH 250/400/630/800
Shunt Pelease 110 v AC P 1 SL 98523 OOOO
415 v AC/220 v DC P 1 SL 98526 OOOO
24 v DC L 1 SL 98531 OOOO
240 v AC/110 v DC P 1 SL 98534 OOOO
Under voltage Pelease 110 v AC L 1 SL 98543 OOOO
240 v AC L 1 SL 98545 OOOO
415 v AC L 1 SL 98548 OOOO
Auxiliary contact Block 1 NO + 1 NC L / P 1 SL 94217 OOOO
Trip Alarm contact # - P 1 Factory assembled
Potary operating mechanism POM 1 SL 94337 OOOO
Earth Fault module
1)
GF11 1 ST 28594 OOOO
#

Accessory Type Std. Pack Catalgoue No. Ordering


Suffix
Shunt Pelease 415 v AC/DC 1 ST 33007 OOOO
240 v AC/DC 1 ST 33006 OOOO
110 v AC/DC 1 ST 33005 OOOO
48 v AC/DC 1 ST 33004 OOOO
24 v AC/DC 1 ST 33003 OOOO
With early-make auxiliary contacts 1
Under voltage Pelease 440 v AC 1 ST 33010 OOOO
415 v AC 1 ST 33009 OOOO
240 v AC 1 ST 33008 OOOO
Off-delayed 1
With early-make auxiliary contacts 1
Auxiliary contact Block NO 1 ST 33001 OOOO
NC 1 ST 33002 OOOO
Early make 1
Trip indicating 1 ST 33021 OOOO
Door coupling rotary handle POM 1 ST 33016 OOOO
Toggle to rotary convert 1 ST 33017 OOOO
Extension shaft 1 ST 33018 OOOO
Pemote operator 240 v AC 1 ST 33013 OOOO
Pesidual-current protection module 1
Paralleling mechanism 1
Mechanical interlock 1
Plug-in adaptor 1
Side wall operator 1
ACCESSORIES - ORDERING DATA
TYPE DX (100/125/160/200/250)S / DX(100/125/160/200/250)H ... (3/4 POLE)
Note: POM consists of (Door coupling rotary handle + Toggle to rotary convert + Extension shaft)
#

Accessory Type Std. Pack Catalgoue No. Ordering


Suffix
Time selectivity block 125-250A 1 ST 33053 OOOO
200-400A 1 ST 33054 OOOO
300-630A 1 ST 33055 OOOO
125-250A (1000-6000) 1 ST 33056 OOOO
200-400A (1000-9000) 1 ST 33057 OOOO
300-630A (1000-9000) 1 ST 33058 OOOO
Shunt Pelease 110 v AC/DC 1 ST 33034 OOOO
240 v AC / DC 1 ST 33035 OOOO
415 v AC / DC 1 ST 33036 OOOO
Under voltage Pelease 240 v AC 1 ST 33037 OOOO
415 v AC 1 ST 33038 OOOO
440 v AC 1 ST 33039 OOOO
Off-delayed (AC) 1
Auxiliary contact Block 2NO + 2 NC 1 ST 33030 OOOO
Early make 1
General trip indicating 1
Annunciation unit - 1
Door coupling rotary handle POM 1 ST 33045 OOOO
Toggle to rotary convert 1 ST 33046 OOOO
Extension shaft 1 ST 33047 OOOO
Potary handle Used with Potary drive 1 ST 33048 OOOO
Pemote operator 240 v AC 1 ST 33042 OOOO
415 v AC 1 ST 33043 OOOO
Pesidual-current protection module 240 v AC 1
415 v AC 1
Paralleling mechanism 1
Mechanical interlock For 2 MCCBs 1 ST 33049 OOOO
For 2 MCCBs with Pemote operator 1 ST 33050 OOOO
For 3 MCCBs 3 & 4 Pole with Toggle or Potary drive 1 ST 33051 OOOO
Annunciation unit 1
Earth-fault Pelease (Fitted to Breaker) 3 Pole 1 ST 33031 OOOO
4 Pole 1
Pesidual-current operated relays (AC) 3 Pole (230 v) 1 ST 33040 OOOO
3 Pole (415 v) 1
4 Pole (230 v) 1
4 Pole (415 v) 1
Withdrawable unit 3 Pole 1 ST 33064 OOOO
4 Pole 1 ST 33063 OOOO
Withdrawable unit auxiliary contact For connection indication 1 ST 33061 OOOO
To connect Earth-fault release 1 ST 33062 OOOO
Toggle switch interlock For upto 3 Pad locks 1 ST 33044 OOOO
ACCESSORIES - ORDERING DATA
TYPE DX (400/630)S / DX(400/630)H ... (3/4 POLE)
Note: POM consists of (Door coupling rotary handle + Toggle to rotary convert + Extension shaft)
#!

Accessory Type Std. Pack Catalgoue No. Ordering


Suffix
Shunt Pelease 200 - 480 v AC 1
110 v AC 1
Under voltage Pelease 200 - 480 v AC 1
110 v AC 1
Under voltage Pelease Off-delayed (AC) 1
Auxiliary contact Block 2NO + 2 NC 1
Trip type indicator 240 v AC 1
Load monitoring 200 - 240 v AC 1
Door coupling rotary handle POM 1
Toggle to rotary convert 1
Extension shaft 1
Pemote operator 230 v AC 1
Mechanical interlock 1
Earth-fault Pelease (Fitted to Breaker) 1
Withdrawable unit 800 A 1
1250 A 1
1600 A 1
ACCESSORIES - ORDERING DATA
TYPE DX (800/1000/1250/1600)H ... (3/4 POLE)
Note: POM consists of (Door coupling rotary handle + Toggle to rotary convert + Extension shaft)
#"

ACCESSORIES - ORDERING DATA


TYPE DM
Note : Any two internal accessories can be fitted simultaneously in a breaker
P To be mounted on right side
L To be mounted on left side
L/P Can be mounted on either side
Ext. External
* 24 v, 48 v, 110 v & 220 v DC are also available on request
# On request.
Accessory Coil voltage / Location Std. Pack Catalogue No. Ordering
Type Suffix
DM 16
Shunt Pelease 110/240/415 v AC L 1 SL 97042 OOOO
Auxiliary contact Block 1 NO + 1 NC P 1 SL 97023 OOOO
L 1 SL 97025 OOOO
Trip Alarm contact - P 1 SL 97037 OOOO
Potary operating mechanism POM Ext. 1 SL 97044 OOOO
DM 100
Shunt Pelease 110/240/415 v AC L 1 SL 97299 OMOO
24 v DC L 1 SL 97299 O4OO
Under voltage Pelease 415 v AC L 1 SL 97610 OOOO
240 v AC L 1 SL 97611 OOOO
Auxiliary contact Block 1 NO + 1 NC P 1 SL 97296 OOOO
L 1 SL 97297 OOOO
Trip Alarm contact - P 1 SL 97298 OOOO
Potary operating mechanism POM Ext. 1 SL 97301 OOOO
Spreader Links with Barrier Ext. 1
Earth Fault module GF1 Ext. 1 ST 27745 OOOO
DM 160
Shunt Pelease 415 v AC/220 v DC P 1 SL 94331 ODOO
240 v AC/110 v DC 1 SL 94331 OBOO
110 v AC 1 SL 94331 OAOO
Under voltage Pelease* 415 v AC L 1 SL 94332 DOOO
240 v AC 1 SL 94332 BOOO
110 v AC 1 SL 94332 AOOO
Auxiliary contact Block 1 NO + 1 NC P 1 SL 94330 OOOO
L 1 SL 94329 OOOO
Trip Alarm contact # - P 1 Factory assembled
Potary operating handle POH Ext. 1 SL 94336 OOOO
Earth Fault module GF2 Ext. 1 ST 27746 OOOO
DM 250/400
Shunt Pelease 415 v AC/220 v DC P / L 1 SL 97575 OOOO
240 v AC/110 v DC P / L 1 SL 97576 OOOO
Under voltage Pelease 415 v AC L 1 SL 97579 OOOO
240 v AC L 1 SL 97580 OOOO
Auxiliary contact Block 1 NO + 1 NC L / P 1 SL 97573 OOOO
Trip Alarm contact - P 1 SL 97574 OOOO
Adaptor terminal (3) with shroud (1) - 1 Set - Ext. 1 SL 97564 OOOO
Terminal shroud - Ext. 1 SL 97563 OOOO
Spreader Links with Barrier - Ext. 1 Std. Kit
Potary operating handle POH Ext. 1 SL 97562 OOOO
Earth Fault module GF2 Ext. 1 ST 27746 OOOO
##

Accessory Coil voltage / Location Std. Pack Catalogue No. Ordering


Type Suffix
Shunt Pelease 110 v AC P 1 SL 98523 OOOO
415 v AC/220 v DC P 1 SL 98526 OOOO
24 v DC L 1 SL 98531 OOOO
240 v AC/110 v DC P 1 SL 98534 OOOO
Under voltage Pelease * 110 v AC L 1 SL 98543 OOOO
240 v AC L 1 SL 98545 OOOO
415 v AC L 1 SL 98548 OOOO
Auxiliary contact Block 1 NO + 1 NC L / P 1 SL 94217 OOOO
Potary operating mechanism POM Ext. 1 SL 94337 OOOO
ACCESSORIES - ORDERING DATA
TYPE DTH 800 INST.
Note : Any two internal accessories can be fitted simultaneously in a breaker
P To be mounted on right side
L To be mounted on left side
L/P Can be mounted on either side
Ext. External
* 24 v, 48 v, 110 v & 220 v DC are also available on request
Note : Any one can be used.
P To be mounted on right side
Accessory Coil voltage / Location Std. Pack Catalogue No. Ordering
Type Suffix
Shunt Pelease 110/240/415 v AC P 1 SL 97042 OOOO
Trip Alarm contact - P 1 SL 97037 OOOO
Auxiliary contact Block 1 NO + 1 NC P 1 SL 97023 OOOO
ACCESSORIES - ORDERING DATA
TYPE DF
#$

OVERALL DIMENSIONS
MCCB - TYPE DS
Note: All dimensions are in mm.
DS 100 DS 125/160/200
DS 250/400
MOUNTlNG AND
DOOP CUTOUT DETAlLS
MOUNTlNG AND
DOOP CUTOUT DETAlLS
MOUNTlNG AND
DOOP CUTOUT DETAlLS
#%

OVERALL DIMENSIONS
DIMENSIONAL DETAILS OF ROTARY OPERATING MECHANISM - TYPE DS
Note: All dimensions are in mm.
DS 100/125/160/200
DS 250/400
#&

OVERALL DIMENSIONS
MCCB - TYPE DTH..E
Note: All dimensions are in mm.
ROTARY OPERATING MECHANISM FOR TYPE DTH..E
DTH 200E DTH 250/400/630/800 E
DTH 200E DTH 250/400/630/800 E
MOUNTlNG AND
DOOP CUTOUT DETAlLS
#'

OVERALL DIMENSIONS
MCCB - TYPE DG
Note: All dimensions are in mm.
DG 125/200
DG 250/400
MOUNTlNG AND
DOOP CUTOUT DETAlLS
MOUNTlNG AND
DOOP CUTOUT DETAlLS
$

OVERALL DIMENSIONS
DIMENSIONAL DETAILS OF ROTARY OPERATING MECHANISM - TYPE DG
Note: All dimensions are in mm.
DG 125/200
DG 250/400
EXPLODED VIEW OF ROTARY OPERATING MECHANISM
$

OVERALL DIMENSIONS
MCCB - TYPE DH
Note: All dimensions are in mm.
MOUNTlNG AND
DOOP CUTOUT DETAlLS
DH 100 DH 125/160 DH 200
MOUNTlNG AND
DOOP CUTOUT DETAlLS
MOUNTlNG AND
DOOP CUTOUT DETAlLS
MOUNTlNG AND
DOOP CUTOUT DETAlLS
DH 250 DH 400 DH 630
$

OVERALL DIMENSIONS
DIMENSIONAL DETAILS OF ROTARY OPERATING MECHANISM - TYPE DH
Note: All dimensions are in mm.
DH 100/125/160/200
DH 250/400
DH 630
$!

OVERALL DIMENSIONS
MCCB - TYPE DL
Note: All dimensions are in mm.
DL 100 DL 160/200
DL 250/400
$"

OVERALL DIMENSIONS
DIMENSIONAL DETAILS OF ROTARY OPERATING MECHANISM - TYPE DL
Note: All dimensions are in mm.
DL 100 DL 160
DL 250/400
$#

OVERALL DIMENSIONS
MCCB - TYPE DTH
Note: All dimensions are in mm.
DTH 100 3 POLE / 4 POLE DTH 200
DTH 250/400/630.800
MOUNTlNG AND
DOOP CUTOUT DETAlLS
$$

OVERALL DIMENSIONS
ROTARY OPERATING MECHANISM FOR TYPE DTH
Note: All dimensions are in mm.
DTH 200
DTH 250/400/630/800
DTH 100
PANEL CUT OUT
$%

OVERALL DIMENSIONS
DX 100-250 S/H ... 3/4 POLE
Note: All dimensions are in mm.
POTAPY DPlvE / POTAPY HANDLE FOP SUPFACE MOUNTlNG BPEAKEPS
$&

OVERALL DIMENSIONS
DX 100-250 S/H... 3/4 POLE
Note: All dimensions are in mm.
EXTENSlON SHAFT
DOOP COUPLlNG POTAPY HANDLE FOP PEAP MOUNTlNG SWlTCHES
PEMOTE OPEPATOP
$'

OVERALL DIMENSIONS
DX 160 S/H, DX 200-250 S/H
Note: All dimensions are in mm.
PLUG-lN ADAPTEP
%

OVERALL DIMENSIONS
DX 400-630 S/H (3/4 POLE)
Note: All dimensions are in mm.
DIMENSIONAL DETAILS OF ROTARY OPERATING MECHANISM
DOOP COUPLlNG POTAPY HANDLE
POTAPY DPlvE
%

OVERALL DIMENSIONS
DX 400-630 S/H ... 3/4 POLE
Note: All dimensions are in mm.
PEMOTE OPEPATOP
WlTHDPAWABLE UNlT
PUSH-BUTTONS FOP PEMOTE OPEPATlON ENCLOSED BPEAKEPS
%

OVERALL DIMENSIONS
DX 800-1250 H ... 3/4 POLE
Note: All dimensions are in mm.
DX 1600 H ... 3/4 POLE
%!

OVERALL DIMENSIONS
DX...H 800-1600 A (3/4 POLE)
Note: All dimensions are in mm.
MOUNTlNG BPACKETS PEAP CONNECTlON
%"

OVERALL DIMENSIONS
DX 800-1600 H ... 3/4 POLE
Note: All dimensions are in mm.
PEMOTE OPEPATOP
POTAPY DPlvE
DOOP COUPLlNG POTAPY HANDLE
%#

OVERALL DIMENSIONS
DX 800-1600 H ... 3/4 POLE
Note: All dimensions are in mm.
WlTHDPAWABLE UNlT
%$

OVERALL DIMENSIONS
MCCB - TYPE DM
Note: All dimensions are in mm.
DM 16 DM 100
DM 160 DM 250/400
MOUNTlNG AND
DOOP CUTOUT
DETAlLS
MOUNTlNG AND
DOOP CUTOUT DETAlLS
MOUNTlNG AND
DOOP CUTOUT DETAlLS
MOUNTlNG AND
DOOP CUTOUT DETAlLS
%%

OVERALL DIMENSIONS
ROTARY OPERATING MECHANISM FOR MOTOR BACK-UP PROTECTION RANGE FOR TYPE DM
Note: All dimensions are in mm.
DM 16 DM 100
DM 160 DM 250/400
%&

OVERALL DIMENSIONS
MCCB - TYPE DTH 800 INST.
Note: All dimensions are in mm.
ROTARY OPERATING MECHANISM FOR DTH 800 INST.
%'

OVERALL DIMENSIONS & CONNECTION DIAGRAM


FUSE MONITORING DEVICE TYPE DF
Note: All dimensions are in mm.
Caution : Connect terminals of DF in parallel with the fuse links.
&

OVERALL DIMENSIONS
EARTH FAULT MODULES - GF1, GF2, GF11
Note: All dimensions are in mm.
GF1 GF2
GF11
&

WIRING DIAGRAM
EARTH FAULT MODULES - GF1, GF2, GF11
GF1 & GF2
GF11
&

OVERALL DIMENSIONS
SS ENCLOSURE
Note: All dimensions are in mm.

You might also like