Date of issue:

8.5.2012

Serial No.:

0910-010592792

Type:
Product Code:
Protection type:
Cert. No.:

M3KP 280SMA 2 B3
3GKP281210-G
Ex de IIB T4
LCIE 01 ATEX 6078/
IECEx LCI 04.0006

Test Report

Rating:
V
690
400
415

3~Motor
Insul.cl.F
IP55

Eff class IE2

Y
D
D

Hz
50
50
50

kW
75
75
75

r/min
2978
2978
2980

cos
0,88
0,88
0,87

A
76
131
127

Duty
S1
S1
S1

400 V 50Hz: IE2 - 94,3(100%) - 94,1(75%) - 92.8(50%)

Resistance
Line

Ambient:
0,03113
0,03113
0,03110

U1 - V1
U1 - W 1
V1 - W 1

22,0 C

Insulation resistance at
12000 M

44,0

Torque
[Nm]

Line
U[V]
400,1
64,1

240,5

180,9
120,3
60,8

No load test
Locked rotor test
Thermal test (100% load)

Overload
Torque

High-voltage test winding

Test

1000 V

2400 V

D
D

f[Hz]
50
50

Input
I[A]
37,9
131,1

P1 [kW]
2,77
4,09

400,1

50

131,8

79,7

75,0

400,1
400,0
400,0

D
D
D

50
50
50

102,1
74,8
51,4

60,1
40,8
21,7

56,3
37,5
18,8

[oC]

[K]
55,7
25,6
37,5

Method
1
2
2

160 %

60 s

Output
P2 [kW] n[r/min]
3000
0

cos
0,11
0,28

[%]

2977

0,87

94,1

2983
2987
2991

0,85
0,79
0,61

93,6
92,0
86,5

Partial load points:


~75% load
~50% load
~25% load
Temperature rise at rated load.
Stator winding :
Frame :
Bearing D-end :
Ambient Temperature :

25,0

Measurement method
1 Resistance
2 Thermometer
3 Thermocouples

Manufactured and tested in accordance with rules of IEC 60034-1 and IEC 60034-2-1.
PLL determined from residual loss.
On behalf of customer
On behalf of manufacturer

Date of test

12.5.2009
Telephone

Tested by ABB Oy, Motors and Generators, Vaasa, Finland


Computer print-out valid without signature.