Quick Selection
This selection guide has been designed to allow quick and simple selection for a broad range of TROX Grille and Diffuser product. Full product and system details for these and other TROX equipment can be found on our website www.troxuk.co.uk. As part of our commitment to a collaborative design process our local Sales Engineers are available to offer assistance and advice on these and other TROX systems and product. To contact you local engineer call 01842 754545. In addition to the Grille and Diffuser product in this guide, TROX offer a complete range of air distribution products and systems, these include: Active Chilled Beams Passive Chilled Beams Multi Service Chilled Beams (MSCB) Chilled Ceilings Fan Coil Units Acoustics Filtration VAV Terminal Units Labcontrol Dealer Desk Cooling Low to High Density Cooling
TROX UK Ltd Caxton Way Thetford Norfolk IP24 3SQ Tel: +44 (0) 1842 754545 Fax: +44 (0) 1842 763051 E-Mail: sales@troxuk.co.uk www.troxuk.co.uk
Contents
Page
Sizes Available
Minimum size 150 x 100. Maximum Size 1200 x 600. Standard increments 50mm.
For full details see publication 1/1.1/B/...
Order Code
AT - AG
Type AT = Horizontal front blade VAT = Vertical front blade Rear Assemblies A = Grille face only AG = Rear opposed blade damper D = Rear adjustable blades
800 x 200
L x H (mm) 0 = No subframe
B30
S11
P3
RAL 9010
Powder coat finish
20% Gloss
Fixing Variant 0 = Without (screw fix) S11 = With (secret fix) X = Without flange drilling or secret fix
Rear Assembly
75 107
Type AT VAT
...-AG Opposed blade action volume control damper, adjustable from the front face.
...-D A set of individually adjustable vertical air pattern control blades. For type VAT these blades are horizontal.
...-DG Volume control dampers as ...-AG plus a set of individually adjustable vertical air pattern control blades.
Type AT shown
04
75 107
H + 45/L + 45
H + 22/L + 22
32 64
H/L
16,7
Performance Data
Grille with ceiling effect (grille installed within 300mm of ceiling). Throw is the distance from sidewall grille to an average velocity of 0.35 m/s. The minimum distance between multiple units must be 20% of Throw.
SECTION 1
Pivot Line
150
Adjustable Grilles
200
150
Throw (m)
350
Pivot line
500
350
600
1200
Throw assumes direction blades set at 45 blade divergence. For 0 blade divergence multiple throw by 1.4 and divide pressure drop by 1.1.
By limiting effective jet velocity to 7 m/s all grille sizes shown meet NC35 assuming 8dB room attenuation and fully open damper.
Subframe
32
75
15
05
Size Available
Minimum Size 150 x 100. Maximum Size 1200 x 600. Standard increments 50mm.
For full details see publication 1/1.3/B/...
Order Code
AE - AG / 200 x 200 / B30 / S11 / P3 / RAL 9010
Powder coat finish Fixing 0 = S11 = X = Variant Without (screw fix) With (secret fix) Without flange drilling or secret fix
20% Gloss
Type AE Rear Assemblies A = Grille face only AG = Rear opposed blade damper
Screw Fixing
Subframe
32
13 H + 22/L + 22 H + 45/L + 45
15
H/L
75
Rear Assembly
70 104
...-AG
06
Performance Data
SECTION 2
Pivot line
100
Extract Grilles
150 300
200
400 250
600 1
100
0.5
Pivot line
50
800
900
600
By limiting effective jet velocity to 7 m/s all grille sizes shown meet NC35 assuming 8 dB room attenuation (no damper or damper fully open).
07
Order Code
CFG - F1
Type CFG AFG
600 x 600
Size (mm)
125
35
P2
P2 = Polyester powder coat silver grey RAL 9006 25% Gloss (Standard) P4 = Polyester powder coat black RAL 9006 20% Gloss N1 = Polyester powder coat with nylon reinforcing black RAL 9005
Rear Assembles F1 = Fan Pack (230V Standard) CFG only A = Face only, AFG only AG = Rear opposed blade damper, AFG only
Unit Depth (mm) 125 = Standard *75 = Optional 0 = Not used AFG
Frame Depth (mm) between face of grille and face of pedestal 25 standard Optionally 26 - 50 in 1mm steps
Type CFG
90mm Maximum Pedestal
Type AFG
599 +0.5/-1mm 13mm Nominal Pitch 6mm Detail A
125mm1)
Power Inlet Plug (C14) Note: 1) 75mm CFG depth option available
Detail A
X 140mm Approx 68.5 Shims to suit height required (factory fitted) X standard 25mm. Can be 25-50mm in 1mm steps
08
SECTION 3
Selection Guide
The floor grille should be located at the front of the I.T./Comms cabinet experiencing hot spot conditions the cabinet should incorporate a perforated door. The floor void static pressure must be considered in the selection process (see Potential cooling below). Sufficient void air (cooled by others) must be available to be drawn by the grille at the specific point of need.
Floor Grilles
Structural performance
The 125mm deep unit will provide the following strength against the performance specification: PSA MOB PF2 PS/SPU March 1992, with the following results:
Potential cooling
6.00 5.11kW 5.00
Test
Stability of deflection (centre of grille): 4.5 kN static load through 25mm square indentor
Result
kW Cooling Capacity
4.00
3.00
2.00
Deflection 23 hours after load applied - 3mm Deflection 24 hours after load applied - 3mm 0.09mm permanent deformation 0.01mm permanent indentation
1.00
0.81kW
Impact load test: 40 kg Sand Bag from 1m height Dynamic rolling load test: 4.5 kN load 50 passes of wheel 3 kN load 50 passes of wheel 3 kN load 50 passes of wheel Did not collapse 0.40mm Vertical permanent deformation (max) 0.20mm Horizontal permanent deformation (max) Did not collapse
Note: Based on 10k rise across I.T. equipment with 1 Pascal floor void static pressure
600 500
Safety load test (centre of grille): 13.5 kN load through 25mm square indentor Did not collapse
-15
-10
-5
10
15
09
150
1 2 3
SM = Dirt trap including adjustable volume control at rear SV = Dirt trap including adjustable volume control at face K = Trim ring1)
For orders without trim ring a spacing ring is provided for technical performance reasons and to ensure correct height of grille core. For orders without adjustable swirl element the direction of air discharge is vertical. Only available for size 200.
150
V00
1 2
SM = Dirt trap including adjustable volume control at rear SV = Dirt trap including adjustable volume control at face K = Trim ring1)
1) 2) 3)
For orders without trim ring a spacing ring is provided for technical performance reasons and to ensure correct height of grille core. For orders without adjustable swirl element the direction of air discharge is vertical. Only available for size 200.
3 4 1 2 3 4 5 6
5 6
Diffuser Core Swirl element for adjustment of air discharge direction Trim Ring Clamping Ring Dirt Trap Plenum Box
10
SECTION 3
Performance Data
Size 150 200 Air Volume Press Drop Air Volume Press Drop (l/s) min - max (Pa) min - max (l/s) min - max (Pa) min - max Horizontal Discharge Throw (m) 0.9 m 1.2 m 15 - 25 18 - 30 18 - 50 28 - 70 21 - 35 25 - 41 13 - 35 18 - 50 Vertical Discharge 1.5 m 30 - 50 28 - 70 10 - 30 5 - 35 10 - 50 5 - 50
0.3 m 10 - 16 8 - 20 16 - 27 8 - 20
Max noise level NC38 assuming 4dB room attenuation. Data for FBA diffusers and dirt trap, damper fully open no plenum box. Horizontal discharge is Throw distance to terminal velocity of 0.15m/s (min vol) and 0.25m/s (max vol). A 600mm clear zone (from centre of diffuser) is recommmended with vertical discharge.
Floor Grilles
Dimensions
Size 150 200 D 98 123 G 50 48 E 160 200 H1 125 150 H2 71.5 84 K1 200 250 K2 198.5 248.8 R1 149.5 199.5 R2 138 188 R3 137 187 R4 150.1 200.1 R5 150.3 200.3 c1 21 21 c2 22 22
Adjustable swirl element to change direction of discharge Vertical/Horizontal (V,H) Vertical - fixed (VF) Clamping ring For installation in floor panels - max. 55mm thickness
R2
R2 E
47
1,5
Plenum box A
18
Trim ring K
4,5 24 c2 R4
K1/K2
H1
R4-9,5
70
H2
11
Type AF
Supply or return air grilles for lay in floor mounting with fixed horizontal profiled blades, blades with either 0 or 15 deflection. Type AF-0 and AF-15 respectively. The grille core is removable. The grille can be fitted into masonry. Standard finish: Powder coated RAL 9006 25% gloss.
Sizes Available
Minimum Size 150 x 100. Maximum Size 1800 x 600. Standard increments 50mm.
For full details see publication 1/1.1/B/...
Order Code
AH - 15 - AG
Type AF AH WAP AHR (20mm border) WAPR (20mm border) Blade deflection 15 0
1000 x 150
L x H (mm)
B30
S11
P3
RAL 9010
20% Gloss
Powder coat finish Rear Assemblies A = Grille Face only AG = Rear opposed blade damper D = Rear adjustable blades DG = Rear adjustable blades and damper
Subframe 0 = No subframe B30 = 75mm subframe bracket (30mm borders) for finite grille B20 = as above but for 20mm border grille L30 = 1800mm subframe (30mm borders) for linear grille** L20 = as above but for 20mm border grille
Fixing 0 = Without (screwfix) S11 = With (secret fix) X = Without flange drilling
Note: ** = Also for use when S11 fix plenum box supplied
Rear Assembly
75 107
...-AG Opposed blade action volume control damper, adjustable from the front face. ...-D A set of individually adjustable vertical air pattern control blades.
Type AH - WAP
Type AF
H+30/L+30 12.5
12.5
H + 41(21)/L + 41(21)
H/L
32 64
AF-0
...-DG Volume control dampers as ...-AG plus a set of individually adjustable vertical air pattern control blades.
75 107
H/L
AH-0 WAP-0
AH-15 WAP-15
12
Performance Data
Linear grille (with aspect ratio >12 to 1) with ceiling effect (grille installed within 300mm of ceiling). Throw is the distance from sidewall grille to an average velocity of 0.35 m/s.
SECTION 4
Nominal height (mm) H Effective Jet Velocity (m/s) Pressure drop (total) (Pa)
60 40 30 20 15 10 7 100 2 5 1.5 150 75
Type
AH/AF
Linear Grilles
L Throw (m)
20
7 6 5 4 3
75 100
WAP AH/AF
15 10
WAP
AH/AF
Pivot line
150 200 WAP AH/AF
30 300 WAP
By limiting effective jet velocity to 6 m/s all grille sizes shown up to 3m long meet NC35 assuming 8 dB room attenuation and fully open damper.
Subframe
32
X Type B30 - 30mm border : X = 15 Type B20 - 20mm border : X = 5 Screwdriver operation to locate fastener tongue behind subframe
15
75
13
Size Available
Minimum Size 150 x 100. Maximum Size 1200 x 600. Standard increments 50mm.
For full details see publication 1/1.1/B/...
Order Code
AGS - T / 250 x 250
L x H (mm)
P3
RAL 9010
Powder coat finish
20% Gloss
0 = without subframe
Type LVV 40
L x H (mm)
150 x 150
L x H (mm)
P3
RAL 9010
Powder coat finish
20% Gloss
14
SECTION 5
Transfer Grilles
By limiting effective jet velocity to 3 m/s all grille sizes shown meet NC35 assuming 8 dB room attenuation.
LCG / LVV40
Neck Size 150 200 200 300 300 400 450 450 600 500 600 x x x x x x x x x x x 150 150 200 200 300 300 300 450 400 500 600 NC20 Volume l/s 45 55 74 100 140 175 200 285 310 325 435 TPa 15 15 15 12 11 10 10 9 9 8 8 NC25 Volume (l/s) 55 70 86 120 170 210 235 325 380 390 530 TPa 23 21 19 18 16 15 14 13 12 12 11 NC30 Volume (l/s) 65 80 105 145 200 250 285 380 450 485 640 TPa 30 30 27 24 20 20 20 17 16 16 15 NC35 Volume (l/s) 80 100 120 170 240 300 340 470 550 560 750 TPa 45 40 35 32 29 26 25 24 22 21 20
Data is for composite unit of 2No. grilles and integral fireblock. NC levels based on 8dB room attenuation.
Type AGS
Type AGS-T
Type LCG/LVV40
H/L H1/L1
min25 max44
15
Size Available
1 to 4 slot lengths available in increments of 150mm.
1200
P3
RAL 9010
20%
HH2
No. of Slots 1 to 4
End Cap P02 = Plate A02 = Angle L02 = Offset angle PL02 = Plank
Finish/colour P3 = powder coated to RAL 9010 20%1 P2 = powder coated to RAL 9006 25% P4 = powder coated to RAL 9005 20% P6 = other colours to RAL 1) standard finish Fixings 0 = Without FK = Fixing kit Blade Setting HH1 = All blades in one direction HH2 = Alternating blades every 300mm HA2 = 45o Alternating blades every 150mm HH3 = Alternating blade 33%/66%. 150mm then 300mm
Flange NF = Not flanged FL = Flanged PL = Plank ceiling1 TZ = Techzone2 1) 4 slot only 2) VSD35 only
Length L1 mm length of diffuser or angle* of mitre in degrees *Only in 90o or 135o with 300mm inside leg
1200 x 1 x 198 x 0
Plenum Type 0 = Standard plenum EH - Extended height RA - Light baffle return air No. of Slots 1 to 4 Lining None D12 = 12mm
Spigot Damper 0 = Standard spigot M = Spigot damper MC = Cord operated spigot damper
Extended neck Y = dimension mm 0 = without extended neck Spigot dia No. of Spigots 1 to 4
16
SECTION 6
Performance Data
VSD50 Number of Slots 1 2 3 4 Air Volume (l/s/m) min Press Drop (Pa) max Air Volume (l/s/m) min Press Drop (Pa) max Air Volume (l/s/m) min Press Drop (Pa) max Air Volume (l/s/m) min Press Drop (Pa) max max max max max 3.0 m 20 - 55 22 40 - 80 14 60 - 100 10 80 - 115 8 Throw (m) 4.5 m 20 - 70 36 40 - 100 22 60 - 120 15 80 - 140 13 6.0 m 20 - 80 47 40 - 115 29 60 - 145 20 80 - 165 18
Slot Diffusers
Perimeter throw pattern for VSD diffusers to a maximum terminal velocity of 0.75 m/s with average room velocities of 0.25 m/s. Blade configuration as detailed below to be set up on site, by others. Diffuser recommended active length between 75% and 80% of facade length. Maximum air change rates up to 25 per hour using special perimeter blade configuration as detailed below. Max NC35 assuming 8dB room attenuation, 1200mm long plenum, recommended max spigot velocity 3.5 m/s.
300
Faade
2.7m
Partition Wall
150
Sections
NF
FL
NF
59.5 101.5 143.5 185.5
PL
299 Width P +/- 1
PL
1 2 3 4
Tolerance
Length L1 +/- 1
Type A
Type L
Type PL
17
Size Available
1 to 4 slots lengths available in increments of 150mm.
1200
P3
RAL 9010
20%
HH2
No. of Slots 1 to 4
End Cap P02 = Plate A02 = Angle L02 = Offset angle PL02 = Plank
Finish/colour P3 = powder coated to RAL 9010 20%1 P2 = powder coated to RAL 9006 25% P4 = powder coated to RAL 9005 20% P6 = other colours to RAL 1) standard finish Fixings 0 = Without FK = Fixing kit Blade Setting HH1 = All blades in one direction HH2 = Alternating blades every 300mm HA2 = 45o Alternating blades every 150mm HH3 = Alternating blade 33%/66%. 150mm then 300mm
Flange NF = Not flanged FL = Flanged PL = Plank ceiling1 TZ = Techzone2 1) 4 slot only 2) VSD35 only
Length L1 mm length of diffuser or angle* of mitre in degrees *Only in 90o or 135o with 300mm inside leg
1200 x 1 x 198 x 0
Plenum Type 0 = Standard plenum EH - Extended height RA - Light baffle return air No. of Slots 1 to 4 Lining None D12 = 12mm
Spigot Damper 0 = Standard spigot M = Spigot damper MC = Cord operated spigot damper
Extended neck Y = dimension mm 0 = without extended neck Spigot dia No. of Spigots 1 to 4
18
SECTION 6
Performance Data
VSD35 Number of Slots 1 2 3 4 Air vol. (l/s/m) min - max Press drop (Pa) max Air vol. (l/s/m) min - max Press drop (Pa) max Air vol. (l/s/m) min - max Press drop (Pa) max Air vol. (l/s/m) min - max Press drop (Pa) max 3.0 m 15 - 40 31 30 - 60 15 45 - 70 10 60 - 80 9 Throw (m) 4.5 m 15 - 50 44 30 - 70 23 45 - 85 16 60 - 100 14 6.0 m 15 - 50 44 30 - 75 26 45 - 95 20 60 - 110 17
Slot Diffusers
Perimeter throw pattern for VSD diffusers to a maximum terminal velocity of 0.75 m/s with average room velocities of 0.25 m/s. Blade configuration as detailed to be set up on site, by others. Diffuser recommended active length between 75% and 80% of facade length. Maximum air change rates up to 25 per hour using special perimeter blade configuration as detailed. Max NC35 assuming 8dB room attenuation, 1200mm long plenum, recommended max spigot velocity 3.5 m/s.
300
Faade
2.7m
Partition Wall
150
Sections
NF
FL
TZ
PL
Slots 1 2 3 4
P FL
64 91 118 144.5
NF
44 71 98 124.5
PL
299
TZ
133 -
Tolerance
Length L1 +/- 1
Width P +/- 1
Type A
Type L
Type PL
19
1200
SB
P3
RAL 9010
Powder coat finish
20% Gloss
Not Used
Fixings SB = Support Brackets CF = Clip Fixings BF = Bridge Fixings BX = Bridge Fixings for extended height plenum 0 = Without Length of diffuser in mm or Angle of mitre in degrees End Caps / End Plates A1 = One end cap fitted A2 = End cap both ends fitted P1 = One end plate fitted P2 = End plate both ends fitted 0 = None
Number of slots 1 to 4
0
1)
Minimum overall height including diffuser with CF fixing = spigot diameter + 98 mm + Y Minimum overall height including diffuser with BF fixing = spigot diameter + 122 mm + Y
20
Performance Data
ALS25 Number of Slots 1 2 3 4 Air vol. (l/s/m) min - max Press drop (Pa) max Air vol. (l/s/m) min - max Press drop (Pa) max Air vol. (l/s/m) min - max Press drop (Pa) max Air vol. (l/s/m) min - max Press drop (Pa) max 3.0 m 20 - 55 22 40 - 80 14 60 - 100 10 80 - 115 8 Throw (m) 4.5 m 20 - 70 36 40 - 100 22 60 - 120 15 80 - 140 13 6.0 m 20 - 80 47 40 - 115 29 60 - 145 20 80 - 165 18
Air volume shown is based on diffuser used in a 1-way blow configuration to a maximum terminal velocity of 0.75 m/s with average room velocities of 0.25 m/s. Diffuser recommended active length between 75% and 80% of facade length. Maximum air change rates up to 20 per hour for 1-way discharge pattern, 23 per hour for 2-way discharge pattern. Max NC35 assuming 8dB room attenuation, 1200mm long plenum, recommended max spigot velocity 3.5 m/s.
ALS25-T2-1
DIM A mm
ALS25-T2-2
AIR BAFFLE PLATE IN EACH SLOT
28
25 SLOT DIM P mm
28
28
28
End Angle
1.5
End Plate
Dimensions
Number of Slots 1 2 3 4 Neck A 46.0 90.5 135.0 179.5 Face P 81.0 125.5 170.0 214.5
75
28
75
1.5
76
21
Type ALS20
Supply slot diffuser with integral air straightener, hit and miss damper and air deflection blades. In the supply mode the discharge can either be set to horizontal or vertical direction by adjustment of the air deflection blades. Available as extract diffuser and also blanked dummy variant.
1200
SB
P3
RAL 9010
Powder coat finish
20% Gloss
Not Used
Fixings SB = Support Brackets CF = Clip Fixings BF = Bridge Fixings BX = Bridge Fixings for extended height plenum 0 = Without Length of diffuser in mm or Angle of mitre in degrees End Caps / End Plates A1 = One end cap fitted A2 = End cap both ends fitted P1 = One end plate fitted P2 = End plate both ends fitted 0 = None
Number of slots 1 to 6
0
1)
Minimum overall height including diffuser with CF fixing = spigot diameter + 98 mm + Y Minimum overall height including diffuser with BF fixing = spigot diameter + 122 mm + Y
22
Performance Data
ALS20 Number of Slots 1 2 3 4 5 6 Air vol. (l/s/m) min - max Press drop (Pa) max Air vol. (l/s/m) min - max Press drop (Pa) max Air vol. (l/s/m) min - max Press drop (Pa) max Air vol. (l/s/m) min - max Press drop (Pa) max Air vol. (l/s/m) min - max Press drop (Pa) max Air vol. (l/s/m) min - max Press drop (Pa) max 3.0 m 15 - 45 39 30 - 65 19 45 - 80 13 50 - 90 9 70 - 100 7 75 - 110 6 Throw (m) 4.5 m 15 - 55 55 30 - 80 29 45 - 95 18 50 - 110 14 70 - 125 11 75 - 135 9 6.0 m 15 - 55 55 30 - 85 33 45 - 105 22 50 - 120 16 70 - 135 13 75 - 150 11
Air volume shown is based on diffuser used in a 1-way blow configuration to a maximum terminal velocity of 0.75 m/s with average room velocities of 0.25 m/s. Diffuser recommended active length between 75% and 80% of facade length. Maximum air change rates up to 20 per hour for 1-way discharge pattern, 23 per hour for 2-way discharge pattern. Max NC35 assuming 8dB room attenuation, 1200mm long plenum, recommended max spigot velocity 3.5 m/s.
ALS20-DS-1
DIM A mm
ALS20-DS-2
AIR BAFFLE/HIT & MISS SECTION IN EACH SLOT
28
20 SLOT DIM P mm
28
28
28
End Angle
1.5
End Plate
Dimensions
Number of Slots 1 2 3 4 5 6 Neck A 41.0 80.5 120.0 159.5 199.0 238.5 Face P 76.0 115.5 155.0 194.5 234.0 273.5
75
28
75
1.5
76
23
Order Code
AKV - ALS20 - 3 - BF - D - M
Variable Plenum Diffuser Type ALS20 ALS25
Number of spigots
Number of slots Fixing CF = Clip fix BF = Bridge fix BX = Bridge fix for extended height plenum
Spigot Lengths
Spigot Damper Order Suffix Spigot Length Dimension X Up to 178 YES NO -M75mm 40mm 198 to 398 100mm 40mm
L Max L Min
= 2100 = D+100
L Max L Min
= 2100 = 2D+100
24
SECTION 6
Dimensions
Type Number of slots 1 2 3 4 5 6 1 2 3 4 W 138 176 214 254 310 380 138 214 254 310 Bc 43 82.5 122 161.5 201 240.5 48 92.5 137 181.5 Bb 61 100.5 140 179.5 219 258.5 66 110.5 155 199.5 Ec (D+98) (D+98) (D+98) (D+98) (D+98) (D+98) (D+98) (D+98) (D+98) (D+98) Eb (D+122) (D+122) (D+122) (D+122) (D+122) (D+122) (D+122) (D+122) (D+122) (D+122) D Max 198 248 298 353 448 498 198 298 353 448
AKV-ALS20
AKV-ALS25
Slot Diffusers
Type CF
W X
Type BX or CF
W X
Bb
Bb
Bc
EXTENSION (*) Y
Eb O/A HEIGHT
Ec O/A HEIGHT
(D+22)
(D+22)
(D+22)
25
Size Available
Heights 150 to 450 in increments of 50mm. Length 300mm minimum
For full details see publication 2/2.4/B/...
Order Code
ADM1 - A
Type ADM1 ADM2 Style A = Face only AG = Opposed blade damper1) Note
1)
1000 x 200
L x H (mm) Subframe 0 = without A00= subframe
P3
RAL 9010
Powder coat finish
20% Gloss
Fixing Variant 0 = without (screwfix) S11 = with (secret fix) N2 = with crossbar fixing SB = with support bracket (mitred corner only)
Screw Fixing
Type O Standard Supply
Type ADM1-A
M-1A
Opening size H x L Type-0 fix
A section AG section
Type ADM2-A
2A
Opening size H x L Type-0 fix
A section AG section
70
35
50
7
Blade Pitch
7
Blade Pitch
125
125
30
30
30
30
26
50
70
SECTION 7
The above selections meet noise levels up to and including NC35 assuming 8dB room attenuation. ADM linear diffuser with ceiling effect (horizontal throw). Throw is the distance from diffuser to a velocity of 0.5 m/s.
27
Type ADT
Square louvred face, removable core, ceiling diffusers type ADT giving horizontal air discharge, are suitable for use in rooms with ceiling heights between 2.60 and 4.00m. The recommended supply air temperature differential is 10K. The ADT diffuser can be used for supply or extract air applications.
225 x 225
150 x 150 225 x 225 300 x 300 375 x 375 450 x 450 525 x 525 600 x 600* Size
P3
RAL 9010
20%
Gloss level
State colour P3 P4 P6
Powder coated white RAL9010 20% gloss (standard) Powder coated black RAL9005 20% gloss Powder coated colour RAL...
Discharge directions
4 3 2 2C 1
Rear Ancillaries A Diffuser face only AG Opposed blade damper fitted to rear of diffuser
Blanking Plate BP-ADT / 450 Diffuser size Note: *ADTF only **only sizes 150 and 450 ***only size 375
/
Diffuser Size (mm)
P4
RAL9005
State colour
/ 20%
Gloss level
Overall Height (mm) (including diffuser)1) P4 Painted black RAL9005 20% gloss P3 Painted white RAL9010 20% gloss P6 Painted colour RAL...
Plenum size (mm) Diffuser Type ADT 0 M MC AGF ZH AH ZV AV Horizontal spigot (supply) Horizontal spigot (extract) Vertical spigot (supply) Vertical spigot (extract) AGP No damper Spigot damper 2) Spigot damper cord operated 2) Opposed blade damper fitted to rear of diffuser Opposed blade damper fitted to body of plenum
0 C E I
0 No lining D Lining
1)
2)
For ZH, AH minimum height spigot diameter + 102 mm Minimum height with AGF/AGP damper, spigot diameter + 154 mm Minimum height with reduced size plenum + 30 mm on either of above For ZV, AV height fixed at 242mm or 272mm for full or reduced plenum respectively Not available for vertical spigots
28
Diffuser Only Type ADTF performance data (without damper, if fitted, 100% open)
4-Way Discharge
Nominal LxH 150x150 225x225 300x300 375x375 450x450 525x525 600x600 vk m/s
pt in Pa
SECTION 8
1.0 6 in l/s V
L in m LpNC
22 19 22 24 25 27 28
27 26 28 30
32 32 34
Nomenclature:
in l/s V L in m Volume flow per diffuser Distance from the outlet where the maximum time average air velocity is 0.5 m/s vk in m/s Diffuser neck velocity pt in Pa Total pressure drop NC rating of room sound pressure level based LpNC on an assumed 8dB room attenuation.
Note:
The throw distance L should be between 75% and 100% of the distance to the nearest wall or 50% of the diffuser spacing dimension, based on a ceiling height of 2.7 2.9m.
225x225 +7 +6
300x300 +9 +5
375x375 +9 +7
450x450 +10 +9
600x6002) +11 +8
29
SECTION 8
Type ADTF
LxH
53
53 15
The type ADTF has a shaped flanged border for directly mounting to a closed flush ceiling (to maintain horizontal discharge) To fit over ceiling opening size (L+100) (H+100)
The type ADTT has a flat flanged border to enable the diffuser face to be mounted on the back of an exposed T bar or directly to a closed flush ceiling Type *ADTH (size 375 only): 495 O/A to lay-on 500 square ceiling T supports
53
15 7
Type ADTA to locate in clip-in ceiling to match bevelled edge tile with PIP height = 27.5mm (ie SAS system 150) or 25mm (ie Burgess type A) Type ADTB to locate in clip-in ceiling to match square edged tile with PIP height = 25mm (ie Burgess type B or D)
The types ADTM and ADTS each have a border designed to lay into an exposed Threadline support bar system Type ADTM to lay-on threadline ceiling T support bar 15mm wide x 16mm deep (dimension Z) Type ADTS to lay-on threadline ceiling T support bar 15mm wide x 8mm deep (dimension Z) Standard nom (L x H) sizes 150/450
Standard PIP heights: 25mm or 27.5mm NB: Non-standard heights available on request
30
SECTION 8
Order Suffix
75mm 40mm
(L-2) (H-2)
X 25
(L1-2) (H1-2)
Effective
X
25
D (Refer table 2)
40
Notes:
1) For full plenum code details refer to page 28 2) All plenums, and if required transformations, are supplied loose for site assembly by others 3) All full size plenums are supplied with clips for diffuser face fixing 4) Holes (4) provided at top edge of plenum for hanging by others 5) AGF and AGP damper adjustment requires core removal 6) Plenum can be internally lined code D (lining material 12mm black faced class O) foam
242
272
D (Refer table 2)
31
250
Size (mm) 250 300 400 500 600 625
P3
RAL 9010
Powder coat finish
20% Gloss
Not Used
400 x 198 x 6
Diffuser Size
Not Used Reduced plenum size or blank if standard diffuser size Spigot size
32
SECTION 8
Extract
Size 250 300 400 500 600 Lwnc Pressure Drop (Pa) Volume (l/s) Volume (l/s) Volume (l/s) Volume (l/s) Volume (l/s) 15 10 30 50 90 180 300 21 15 38 60 110 200 375 25 20 45 70 125 250 450 30 30 54 90 170 300 500 35 45 60 100 200 375 600
ADLQ louvre diffuser with ceiling effect (horizontal throw). Throw is the distance from diffuser to a velocity of 0.5 m/s for a 4-Way discharge. All selections shown meet NC35 assuming 8 dB room attenuation.
Dimensions
Size 250 300 400 500 600 D 158 158 198 248 313 H 262 262 307 357 420 K 204 254 354 454 554 Q1 248 298 398 498 598 Q2 198 248 348 448 548
Type ADLQ-AK
K 50
Type ADLQ-AR
Q2-55 65
ADLQ-AR
Q1
Type ADLQ-AG
Type ADLQ-A
Q2-58 42
108
Q2 Q1
33
Order Code
ADLR - Q - ZH - M - L
Type ADLR (Circular diffuser) Q = Square diffuser (or blank)
598 x 4
S1
RAL 9016
State colour
A = Diffuser face C = With flap damper AR = With connecting ring Top entry plenum ZV = Supply air AV = Extract air Side entry plenum ZH = Supply air AH = Extract air M = Damper in plenum box spigot 4)MN = Volume setting by cord and measurement test point L = Spigot with lip seal
Size of Diffuser 1 2 3 4 5 6 7 8
0 S1
= Standard surface finish stove enamelled to 3)RAL 9010 = Stove enamelled to RAL...
Type ADLR - Q 593 - for installation in visible T-bar 598 - for installation in ceiling grid with rear sub-structure
1) 2)
Required on constructions without plenum box Only on variants with square face section Type ADLR - Q 3) GL = Gloss level 50 - 60% 4) Available side entry plenum only
Type ADLR-Q
Type ADLR-Q
B K D
H2
35
P R1 (ADLR)
R1 (ADLR)
34
H1
SECTION 8
Performance Data
Size Selection Method Linear Pattern Square Pattern Linear Pattern Square Pattern Linear Pattern Square Pattern Linear Pattern Square Pattern Linear Pattern Square Pattern Linear Pattern Square Pattern Linear Pattern Square Pattern Linear Pattern Square Pattern 1.2 (m) Vol Pa 35 22 32 19 50 15 35 7 60 7 50 5 1.8 (m) Vol Pa 55 60 45 35 80 35 55 17 95 17 65 8 110 13 70 5 Diffuser Centres (m) 2.4 (m) 3.0 (m) Vol Pa Vol Pa 80 130 60 68 110 70 80 35 100 58 130 30 175 60 95 17 130 30 150 25 200 35 100 10 140 19 180 23 230 37 130 12 160 19 220 15 260 25 150 9 180 13 240 15 290 20 175 8 210 10 250 13 320 22 180 7 220 10 3.6 (m) Vol Pa 155 50 250 55 180 32 280 65 200 25 330 40 220 15 360 37 270 19 400 30 280 17 4.2 (m) Vol Pa 300 85 220 40 360 90 260 50 400 50 290 30 450 50 330 32 500 50 360 28
1 2 3 4 5 6 7 8
Linear Pattern based on a single row of Diffusers. Square Pattern with Diffusers at equal centres. Ceiling diffuser with ceiling effect (horizontal throw). At diffuser centres shown, maximum terminal velocity is 0.25 m/s at 1.0m below ceiling. All selections shown meet NC38 assuming 5dB room attenuation including side entry plenum box and spigot damper (fully open).
Dimensions
Size 1 2 3 4 5 6 7 8 B 201.5 257.5 313.5 369.5 425.5 481.5 537.5 593.5 D 123 158 198 248 248 313 313 313 H1 233 233 233 267 267 298 298 298 H2 220 250 295 345 345 410 410 410 K 266 290 372 476 476 567 590 615 P 202 258 314 362 426 482 578 590 R1 244 300 356 412 468 542 598 654 R2 192 248 304 360 416 472 528 584
Type ADLR
R2-55 35
Type ADLR-Q
35 R2-55
Type ADLR-AR/ADRL-Q-AR
R2-51 60
R2 R1 R2 593 or 598
35
Order Code
ADLQL - K - ZH - D - M
Type K = 27mm cover border P = 11mm flush border Supply ZH = horizontal spigot ZV = vertical spigot Extract AH = horizontal spigot AV = vertical spigot Note:
1) 2)
300 X 158 X 0
Size (mm) 300 400 500 600 295 2) 595 2)
P3
RAL 9010
20% Gloss
Not used Reduced plenum size or blank if standard diffuser size Spigot size
Only available for horizontal spigot Only available for flush border & layin T bar
Dimensions
Size 300 400 500 600 295 595 D 158 198 248 313 158 313 DA1 290 390 490 590 DA2 300 400 500 600 300 600 H1 300 340 390 455 300 455 H2 75 75 75 75 H3 83 83 83 83 83 83 K1 274 374 474 574 271 571 K2 269 369 469 569 266 566 Q1 336 436 536 636 Q2 298 398 498 598 295 595
Blanking Plates
ates
Blanking plate
36
SECTION 9
Extract
Size 300 400 500 600 Pressure Drop Volume (l/s) Volume (l/s) Volume (l/s) Volume (l/s) 10 80 105 135 210 15 105 130 160 260 20 120 150 185 300 25 135 170 210 330 30 150 180 225 360
Note: Pressure drop and acoustic data shown is for top entry spigot. For side entry supply & extract acoustic and pressure drop data refer to leaflet 2/15.1/B/...
Horizontal throw distance from diffuser to a velocity of 0.5 m/s for a 4-Way discharge. All selections shown meet NC35 assuming 8 dB room attenuation.
Type ADLQL-K-H
K1
Type ADLQL-P-H
K1
H1
8 DA1 Q1 Q2 DA2
Type ADLQL-K-V
K2 D
H1
Type ADLQL-P-V
K2 D
H2
8 DA1 Q1 Q2 DA2
H3
37
Order Code
LVS
160
G1
G1 - Subframe O - No Subframe
8 B B
Dimensions
Size 100 125 160 200 B 40 46 54 61 C 99 124 159 199 D 132 162 205 245 E 104 129 164 204
38
SECTION 10
100
125
Disc Valves
160
200
Note: Maximum Noise Level NC38, assuming 8dB room attenuation. Throw to a terminal velocity of 0.2 m/s. Performance based on air gap dimension S = 9mm.
39
1.0m
2.7m
The layout and centres of the swirl diffusers must be carefully considered to ensure maximum comfort is achieved. We have provided three alternative arrangements for positioning diffusers, selection methods 1, 2 and 3. Each of the selections will ensure that the maximum terminal velocity in the occupied zone (VH1) will not exceed 0.25m/s, 1.0m below ceiling.
40
SECTION 11
Swirl Diffusers
When the diffuser rows are at least 4.0m apart, the minimum diffuser centres should be A.
When the diffuser rows are at least 3.0m apart, the minimum diffuser centres should be B.
When the diffuser centres in each direction are equal, the minimum diffuser centres should be C.
41
Type SDW
Square faced adjustable blade swirl diffuser. Type SDW is available in a range of sizes. The removable face plate is held in the plenum box with a centre screw fixing. The head of the screw is covered with a decorative cap. The plenum box is available with side or top entry spigot and a volume control damper.
500 - 24 - 600
Diffuser active size 1)
Q21
P3
RAL 9010
Powder coat finish
20% Gloss
= = = = = = =
1)
Square flush face Square lay in T bar Square lay in threadline Square lay in threadline Square lay in threadline Square lay in threadline Burgess Ceiling
0 = Supply air: black air control blades Extract air: no air blades Q11 = Extract air: black air control blades Q21 = Supply air: white air control blades Extract air: white air control blades
Standard sizes Q - 300 x 8, 400 x 16, 500 x 24, 600 x 24, 600 x 48, 625 x 24, 625 x 54 QS15 - 300 x 8 x 600, 400 x 16 x 600, 500 x 24 x 600, 600 x 24 x 600 QB/QL/QS26 - 300 x 8 x 600, 400 x 16 x 600, 500 x 24 x 600, 600 x 24 x 600, 600 x 48 x 600 QM15/QM26 - 300 x 8 x 600, 300 x 8 x 750, 400 x 16 x 600, 400 x 16 x 750, 500 x 24 x 600, 500 x 24 x 750, 600 x 24 x 600, 600 x 24 x 750, 600 x 48 x 600, 600 x 48 x 750, 625 x 24 x 750, 625 x 54 x 750 Face section without central fixing hole, for use on lay in ceilings QL, QS15, QS26, QM15 & QM26 without rear plenum
2)
/
Diffuser Active Size
500 x 198 x 24
Number of blades Spigot2) Size (mm)
M = Spigot Damper D = Lining or no entry MN = Spigot damper and test point connection1) or no entry
1) 2)
Only available on ZH type Refer to product data sheet for spigot sizes available with each plenum size
42
SECTION 11
Performance Data
Size Selection Method 1, Centres A 2, Centres B 3, Centres C 1, Centres A 2, Centres B 3, Centres C 1, Centres A 2, Centres B 3, Centres C 1, Centres A 2, Centres B 3, Centres C 1.2 Vol 100 75 25 140 100 35 150 110 40 190 130 50 m Pa 37 20 5 40 20 5 18 10 3 23 11 2 1.8 Vol 95 70 45 120 85 55 145 105 65 170 110 80 m Pa 30 18 7 27 14 9 17 9 4 18 8 4 Diffuser Centres (m) 2.4 m 3.0 m Vol Pa Vol Pa 105 40 120 46 75 20 85 27 65 15 85 27 130 33 140 38 90 18 100 20 75 11 100 20 110 20 180 25 110 10 130 14 85 6 115 11 180 20 195 24 120 9 140 13 90 6 120 9 3.6 Vol 140 100 110 160 120 120 210 152 170 220 180 180 m Pa 65 47 43 50 27 27 35 18 23 30 22 22 4.2 Vol 250 180 220 300 200 230 m Pa 50 25 38 55 29 33
400 x 16
500 x 24
600 x 24
Swirl Diffusers
600 x 48
Swirl diffuser with ceiling effect (horizontal throw). Minimum diffuser centres ensure maximum terminal velocity is 0.25 m/s at 1.0 m below ceiling. All selections shown meet NC38 assuming 5dB room attenuation including side entry plenum box and spigot damper (fully open). For Selection Methodology see page 40.
Dimensions
298 398 498 598 598 Q x 298 x 398 x 498 x 598 x 598 Size 300 x 8 400 x 16 500 x 24 600 x 24 600 x 48 D 158 198 198 248 248 P 250 295 295 345 345 K 288 370 474 565 588
Spigot Lengths
Spigot Damper Order Suffix Spigot Length Dimension X Up to 178 YES NO -MK I/S PLENUM
75mm 40mm
K I/S PLENUM
250
Type Q
Face-mounted
Type QL
To Lay-on FLAT tee-bar
Type QS15
To Lay-on Tegular tee-bar 15mm wide x 8mm deep
Type QM15
To Lay-on Tegular tee-bar 15mm wide x 16mm deep
16
35
26
573
Type QB
To Push-In spring tee-bar Suitable for tee or omega type
Type QS26
To Lay-on Tegular tee-bar 26mm wide x 8mm deep
Type QM26
To Lay-on Tegular tee-bar 26mm wide x 16mm deep
43
Type VDW
Adjustable swirl diffusers type VDW are supplied in a range of sizes. The face plate is circular to suit the architectural requirements The removable face plate is held in the plenum box with a centre screw fixing. The head of the screw is covered with a decorative cap. The plenum box is available with side or top entry spigot, with volume control damper and / or lip seal on request.
Order Code
VDW - R - Z - V - M - L
Type R = Circular Z = Supply A = Extract V = Top entry plenum H = Side entry plenum
1)
600 x 24
Size (mm)
P1
RAL 9010
Powder coat finish
20% Gloss
Not Used
L = Spigot with lip seal M = Volume control damper with adjustable lever MN = Volume control damper with cable and test connection
0 = Supply air: black air control blades Extract air: no air blades Q11 = Extract air: black air control blades Q21 = Supply air: white air control blades Extract air: white air control blades
NOTE:
1) Only
Type VDW-...-V
B D 40
Type VDW-R-...-H
K ~32 D P R
H1
R/Q
Type VDW-R-...-
44
35
H2
Performance Data
Size Selection Method 1, 2, 3, 1, 2, 3, 1, 2, 3, 1, 2, 3, Centres Centres Centres Centres Centres Centres Centres Centres Centres Centres Centres Centres A B Cx A B Cx A B Cx A B Cx 1.2 Vol 100 75 25 140 100 35 150 110 40 190 130 50 m Pa 37 20 5 40 20 5 18 10 3 23 11 2 1.8 Vol 95 70 45 120 85 55 145 105 65 170 110 80 m Pa 30 18 7 27 14 9 17 9 4 18 8 4 Diffuser Centres (m) 2.4 m 3.0 m Vol Pa Vol Pa 105 40 120 46 75 20 85 27 65 15 85 27 130 33 140 38 90 18 100 20 75 11 100 20 160 20 180 25 110 10 130 14 85 6 115 11 180 20 195 24 120 9 140 13 90 6 120 9 3.6 Vol 140 100 110 160 120 120 210 152 170 220 180 180 m Pa 65 47 43 50 27 27 35 18 23 30 22 22 4.2 Vol 250 180 220 300 200 230 m Pa 50 25 38 55 29 33
SECTION 11
400 x 16
500 x 24
600 x 24
Swirl Diffusers
600 x 48
Swirl diffuser with ceiling effect (horizontal throw). Minimum diffuser centres ensure maximum terminal velocity is 0.25 m/s at 1.0 m below ceiling. All selections shown meet NC38 assuming 5dB room attenuation including side entry plenum box and spigot damper (fully open). For Selection Methodology see page 40. If the diffuser is installed below a closed ceiling (i.e. freely suspended) a stable discharge can be achieved if a peripheral collar > 50mm is fitted.
Dimensions
R 300 400 500 600 600 Size 300 x 8 400 x 16 500 x 24 600 x 24 600 x 48 B 280 364 462 559 580 D 158 198 198 248 248 H1 200 200 200 200 300 H2 250 295 295 345 345 P 278 362 460 557 578 K 290 372 476 567 590
45
Type FD
Type FD swirl diffusers are available in various sizes. Depending on the architectural requirements, the face plate can be circular or square. The fixed air control blades on the diffuser face are arranged radially. The diffuser face can be attached or removed via a centre fix screw into the plenum box. The screw head is covered with a decorative cap. The plenum box can be supplied with either top or side entry spigots and on request, with spigot lip seals and volume control damper. If a circular diffuser face is ordered, the plenum box with side entry spigot has a 35mm extension piece fitted to the plenum.
Order Code
FD - Q - Z - V - M - L
Type Q = Square R = Circular Z = Supply A = Extract V = Top entry plenum H = Side entry plenum
400
Size
P1
RAL 9010
Powder coat finish
20% Gloss
Not Used
M = Volume control damper with single blade = Volume control damper with cable and test connection
NOTE:
1)
Type FD-Q-...-H
Type FD-R-...-H
K
Type FD-...-V
B D 40
H2
H2
35
P R
200
R/Q
Type FD-R-...-
Type FD-Q-...-
R L
46
Performance Data
Size Selection Method 1, 2, 3, 1, 2, 3, 1, 2, 3, 1, 2, 3, Centres Centres Centres Centres Centres Centres Centres Centres Centres Centres Centres Centres A B Cx A B Cx A B Cx A B Cx 1.2 Vol 85 60 125 85 150 105 160 115 m Pa 65 36 55 25 40 18 26 12 1.8 Vol 75 54 35 110 78 52 130 92 65 145 100 70 m Pa 60 30 13 40 20 9 28 14 7 20 9 5 Diffuser Centres (m) 2.4 m 3.0 m Vol Pa Vol Pa 80 63 58 33 60 36 45 20 58 33 118 48 120 50 82 23 90 27 68 15 80 21 135 30 150 40 97 16 105 18 85 12 100 17 150 21 160 26 110 11 120 13 95 8 115 12 3.6 Vol 70 80 140 100 100 170 120 125 185 135 145 m Pa 50 63 65 35 35 48 23 25 30 15 20 4.2 Vol 80 120 130 140 155 220 160 175 m Pa 63 50 55 30 42 45 25 28
SECTION 11
300
400
500
Swirl Diffusers
600
Swirl diffuser with ceiling effect (horizontal throw). Minimum diffuser centres ensure maximum terminal velocity is 0.25 m/s at 1.0 m below ceiling. All selections shown meet NC38 assuming 5dB room attenuation including side entry plenum box and spigot damper (fully open). For Selection Methodology see page 40. If the diffuser is installed below a closed ceiling (i.e. freely suspended) a stable discharge can be achieved if a peripheral collar > 50mm is fitted.
Selections shown meet NC38 assuming 5dB room attenuation. Note: Vol = Volume l/s Pa = Pressure Drop
Dimensions
Size 300 400 500 600 B 280 364 462 559 D 158 198 198 248 L 254 336 440 530 Q 298 398 498 598 R 300 400 500 600 H2 250 295 295 345 K 290 372 476 567 P 278 362 460 557
47
Type DCS
Type DCS-P air diffusers consist of the perforated face plate with a thin acoustic fleece lining on the rear. In type DCS-N, the face plate is made of plain sheet steel with perimeter returned edge with central perforated plate insert. The rear swirl diffuser includes a discharge nozzle ring and radially arranged fixed air control blades and connection collar. If required, can be supplied with top entry spigot piece or side entry plenum box with circular spigot. Plenum box can have internal acoustic insulation if specified.
Order Code
DCS - P - V - AK
Type Face Plate P = Perforated N = Non-perforated C = With discharge nozzle ring V = Visible1) H = Hidden2) NOTE:
1) For 2)
593 x 315
Size (mm) 5931) 5982)
P1
RAL 9010
Powder coat finish
20% Gloss
Not Used
K US A AK
= = = =
Connecting collar Top entry spigot Plenum box Plenum box with acoustic insulation
exposed Tee bar fitting...-V (overall face 593) For hidden Tee bar fitting...-H (overall face 598)
Type DCS-P-...-K
A
Type DCS-P-...-A/DCS-P-...-AK
K1 K 8 C B R
H2
593 ( 598)
H2
Type DCS-P-...-US
Size...x 125 and ...x 160 without perforated plate
D
C B R 593 ( 598)
Type DCS-...-H-US
40 H3
Hanging Bracket
C B R 593 ( 598)
598 600
48
H1
Performance Data
Size Selection Method 1, Centres A 2, Centres B 3, Centres C 1, Centres A 2, Centres B 3, Centres C 1, Centres A 2, Centres B 3, Centres C 1, Centres A 2, Centres B 3, Centres C 1, Centres A 2, Centres B 3, Centres C 1.2 Vol 35 70 42 95 51 125 70 125 m Pa 31 50 20 40 11 25 7 8 1.8 Vol 50 35 23 62 45 32 78 54 35 105 75 45 115 m Pa 65 31 14 44 24 10 26 13 5 18 9 4 7 Diffuser Centres (m) 2.4 m 3.0 m Vol Pa Vol Pa 50 65 38 41 39 43 30 24 40 45 62 44 68 45 47 25 51 27 40 17 55 28 76 25 90 35 57 18 63 17 47 9 63 17 110 20 120 22 80 11 85 12 65 6 85 12 125 8 140 12 100 6 100 6 3.6 Vol 45 75 56 70 70 75 140 100 110 155 115 130 m Pa 50 55 29 50 20 25 30 17 20 11 7 9 4.2 Vol 50 65 80 100 170 110 140 170 130 150 m Pa 65 45 27 45 45 20 30 16 9 10
SECTION 11
160
200
250
Swirl Diffusers
315
400
Swirl diffuser with ceiling effect (horizontal throw). Minimum diffuser centres ensure maximum terminal velocity is 0.25 m/s at 1.0 m below ceiling. All selections shown meet NC38 assuming 5dB room attenuation including side entry plenum box and spigot damper (fully open). For Selection Methodology see page 40.
Dimensions
Size ...X 160 ...X 200 ...X 250 ...X 315 ...X 400 A 158 198 248 313 398 B 235 275 325 410 495 C 210 250 300 385 470 D 123 158 198 248 313 H1 180 215 255 305 361 H2 79 79 76 89 89 H3 159 162 167 184 194 K 215 255 305 370 454 K1 237 277 327 392 476 R 250 300 350 450 500
Type DCS-...-V-K
Hanging bracket
593 600
49
Type TDF
TDF - SilentAIR swirl diffusers are available in various sizes. In accordance with architectural requirement the face plate can be circular or square. The fixed air guiding elements of diffuser face are radially arranged. The diffuser can be fastened to the plenum box by means of a central screw and cover cap. The plenum box can be supplied with a horizontal or vertical air connection, or upon request with a volume control damper and / or a sealing lip.
Order Code
TDF - SA - Q - Z - V - M - L
Type Silent Air Q = Square R = Circular Z = Supply A = Extract V = Top entry H = Side entry
400
Size (mm) 300 400 500 600
P1
RAL 9016
Powder coat finish
20% Gloss
Not Used
= Volume control damper with sheathed cable and measuring nipple M = Volume control with operating rod
NOTE:
1)
Type TDF-SilentAIR-R-...-V
Type TDF-SilentAIR-Q-...-V
Type TDF-SilentAIR-Q-...-H
Type TDF-SilentAIR-R-...-H
50
Performance Data
Size Selection Method 1, Centres A 2, Centres B 3, Centres C 1, Centres A 2, Centres B 3, Centres C 1, Centres A 2, Centres B 3, Centres C 1, Centres A 2, Centres B 3, Centres C 1.2 Vol 80 62 25 92 80 135 100 160 115 m Pa 45 28 5 20 17 30 17 22 10 1.8 Vol 80 62 37 92 80 45 135 100 60 160 115 m Pa 45 28 10 20 17 5 30 17 6 22 10 Diffuser Centres (m) 2.4 m 3.0 m Vol Pa Vol Pa 80 45 80 45 62 28 62 28 48 17 62 28 92 20 92 20 80 17 80 17 65 11 80 17 135 30 135 30 100 17 100 17 80 10 95 14 160 22 160 22 115 10 115 10 90 7 115 10 3.6 Vol 80 70 80 100 100 110 140 120 125 165 135 145 m Pa 45 38 45 28 28 33 33 22 25 24 14 17 4.2 Vol 80 80 80 110 120 135 150 150 165 190 180 190 m Pa 45 45 45 33 37 45 38 38 45 30 27 30
SECTION 11
300
400
500
Swirl Diffusers
600
Swirl diffuser with ceiling effect (horizontal throw). Minimum diffuser centres ensure maximum terminal velocity is 0.25 m/s at 1.0 m below ceiling. All selections shown meet NC38 assuming 5dB room attenuation including side entry plenum box and spigot damper (fully open). For Selection Methodology see page 40. If the diffuser is installed below a closed ceiling (i.e. freely suspended) a stable discharge can be achieved if a peripheral collar > 50mm is fitted.
Dimensions
Size 300 400 500 600 625 B 280 364 462 559 559 D 158 198 198 248 248 L 254 336 440 530 530 Q 298 398 498 598 623 R 300 400 500 600 623 H2 250 295 295 345 345 K 290 372 476 567 567 P 278 362 460 557 557
Type TDF-SilentAIR-...-V
B D
Type TDF-SilentAIR-Q-...-H
Type TDF-SilentAIR-R-...-H
K
K 40 ~32 H2
~32
H2
200
Q/R
35
P R
51
Type TDV
The diffuser face of the type SilentAIR offers a high volume flow rate at low sound power levels. The horizontal swirl-type discharge of the supply air ensures high induction and hence rapid reduction in jet velocity and temperature differential. Suitable for supply air temperature differentials up to 10K. Depending on requirements, the diffuser can be supplied with a circular or square face and with either white or black air control blades. For the air connection a plenum box is used. The connection can be top or side entry. Face fixing with centre screw and cover cap.
Order Code
TDV - SA - Q - Z - V - M - L
Type Silent Air Q = Square R = Circular Z = Supply A = Extract V = Top entry H = Side entry
400
Q21
P1
RAL 9010
Powder coat finish
20% Gloss
L = Spigot with lip seal M = Volume control with operating rod = Volume control damper with sheathed cable and measuring nipple
1)MN
Air control blades 0 = Supply air: black Extract air: no Q11 = Extract air: black Q21 = Supply air: white Extract air: white
NOTE:
1)
Type TDV-SilentAIR-R-...-
Type TDV-SilentAIR-Q-...-
52
Performance Data
Size Selection Method 1, Centres A 2, Centres B 3, Centres C 1, Centres A 2, Centres B 3, Centres C 1, Centres A 2, Centres B 3, Centres C 1, Centres A 2, Centres B 3, Centres C 1.2 Vol 80 65 120 85 150 100 170 120 m Pa 45 30 36 19 38 17 25 12 1.8 Vol 80 65 40 120 85 50 150 100 65 170 120 m Pa 45 30 13 36 19 6 38 17 8 25 12 Diffuser Centres (m) 2.4 m 3.0 m Vol Pa Vol Pa 80 45 80 45 65 30 65 30 50 19 60 25 120 36 120 36 85 19 85 19 65 12 80 16 150 38 150 38 100 17 100 17 80 10 100 17 170 25 170 25 120 12 120 12 100 9 120 12 3.6 Vol 80 70 75 120 100 110 155 125 140 180 140 150 m Pa 45 37 40 36 27 30 39 25 30 28 16 18 4.2 Vol 80 80 80 120 120 120 160 150 160 200 190 180 m Pa 45 45 45 36 36 36 40 38 40 34 30 28
SECTION 11
300
400
500
Swirl Diffusers
600
Swirl diffuser with ceiling effect (horizontal throw). Minimum diffuser centres ensure maximum terminal velocity is 0.25 m/s at 1.0 m below ceiling. All selections shown meet NC38 assuming 5dB room attenuation including side entry plenum box and spigot damper (fully open). For Selection Methodology see page 40.
Dimensions
Size 300 400 500 600 625 B 280 364 462 559 559 D 158 198 198 248 248 L 254 336 440 530 530 Q 298 398 498 598 623 R 300 400 500 600 623 H2 250 295 295 345 345 K 290 372 476 567 567 P 278 362 460 557 557
Type TDV-SilentAIR-...-V
B D
Type TDV-SilentAIR-Q-...-H
Type TDV-SilentAIR-R-...-H
K
K 40 ~32 H2
~32
H2
200
Q/R
35
P R
53
Type RFD
Available in either circular or square face plate, with or without discharge nozzle, to suit architect requirements. Type RFD-...-UO or RFD-...-UD, top entry plenum boxes are inclusive of internal subframe which holds the diffuser in position by central fixing bolt and covering cap.
Order Code
RFD - Q - D - A - M - L
Type Diffuser Face Q = Square R = Circular D = nozzle K = Connecting ring US = Top entry plenum UD1) = Top entry plenum with internal subframe (discharge nozzle construction) UC1) = Top entry plenum with internal subframe (no discharge nozzle) A = plenum box side entry N1) = Low profile plenum box Size (mm) 125 160 200 250 315 400 Not Used Powder coat finish
200
P1
RAL 9010
20% Gloss
M = Volume control damper with operating rod = Volume control damper with sheathed cable and test nipple
1) 2)
NOTE:
Type RFD-R-D-K
A U2
Type RFD-Q-D-US
D 40 Q2 Q2 Q2
R2
Type RFD-R-D-US
K
Type RFD-R-D-UD
48 32 D 40 D
H3
8 U6
H1
H4
R2
C Q 1 R1
54
U4
Performance Data
Size Selection Method 1, Centres A 2, Centres B 3, Centres C 1, Centres A 2, Centres B 3, Centres C 1, Centres A 2, Centres B 3, Centres C 1, Centres A 2, Centres B 3, Centres C 1, Centres A 2, Centres B 3, Centres C 1, Centres A 2, Centres B 3, Centres C 1.2 Vol 40 25 55 32 15 67 43 110 52 115 72 130 m Pa 70 28 55 18 9 37 14 40 10 18 8 14 1.8 Vol 35 24 18 47 33 24 63 45 30 80 53 35 105 75 45 118 m Pa 50 20 15 40 19 12 34 15 8 23 11 4 15 8 2 11 Diffuser Centres (m) 2.4 m 3.0 m Vol Pa Vol Pa 35 50 38 60 27 35 29 38 23 19 29 38 47 40 53 50 35 21 37 27 30 16 40 30 63 34 68 38 48 18 50 20 38 9 50 20 80 23 100 36 54 11 55 12 45 7 55 12 105 15 110 17 78 9 80 9 60 5 80 9 120 12 140 16 90 7 105 9 100 8 3.6 Vol 45 32 40 60 40 55 75 55 68 120 68 60 130 90 105 155 120 125 m Pa 80 45 70 65 30 55 45 24 38 50 15 13 25 11 15 18 12 13 4.2 Vol 50 38 50 70 47 70 85 65 90 140 78 95 140 100 145 175 135 150 m Pa 100 60 100 95 40 95 65 35 70 70 20 32 27 14 29 25 15 17
SECTION 11
125
160
200
Swirl Diffusers
250
315
400
Swirl diffuser with ceiling effect (horizontal throw). Minimum diffuser centres ensure maximum terminal velocity is 0.25 m/s at 1.0 m below ceiling. All selections shown meet NC38 assuming 5dB room attenuation including side entry plenum box and spigot damper (fully open). For Selection Methodology see page 40.
Dimensions
Size 125 160 200 250 315 400 A 123 158 198 248 313 398 C 123.5 158.5 198.5 248.5 313.5 398.5 D 98 123 158 198 248 313 H1 259 284 314 359 409 474 H3 195 220 250 295 345 410 H4 178 190 202 227 252 285 K 216 266 290 476 567 615 Q1 198 198 248 298 398 498 Q2 198 248 248 298 398 498 R1 158 197 241 295 364 450 R2 200 250 300 350 450 580 U2 75 78 78 75 88 88 U4 153 158 161 166 183 193 U6 192 196 197 202 219 229
55
Order Code
DUK - V - K - E1
Type P1) V = Fixed = Adjustable
250
Size (mm)
/
Not Used
P3
RAL 9010
20% Gloss
Powder coat finish Only with construction V P = With pneumatic actuator E1 = external Rotary actuator 220 V, 50 Hz E2 = external Rotary actuator 24 V, 50 Hz E3 = external Rotary actuator 24 V, 50 Hz, 0...VE4 = internal linear actuator 220 V, 50 Hz E5 = internal linear actuator 24 V, 50 Hz E6 = internal linear actuator 24 V, 50 Hz, 0...V+
Only with construction V K = Duct connection element A = As K plus spigot R = Duct connection element for circular ducting
NOTE: 1) Drilled for fixing as standard: extra text required on order if no holes are required. For sizes 100 and 125, construction with actuator not available
Performance Data
Size 100 Volume (l/s) Throw L (m) Rise + Fall (m) Volume (l/s) Throw L (m) Rise + Fall (m) Volume (l/s) Throw L (m) Rise + Fall (m) Volume (l/s) Throw L (m) Rise + Fall (m) Volume (l/s) Throw L (m) Rise + Fall (m) Volume (l/s) Throw L (m) Rise + Fall (m) Volume (l/s) Throw L (m) Rise + Fall (m) 13 3.9 0.6 17 3.9 0.55 23 3.5 0.38 29 3.8 0.6 37 3.8 0.9 50 3.9 1.3 65 3.9 1.7 17 4.5 0.43 25 5 0.5 35 5.1 0.3 55 6.5 1.1 60 5.4 1.5 100 7 1.8 150 9 2.5 22 5.8 0.44 35 7 0.75 50 7.5 1.1 85 10 2 95 8.5 1.6 200 13.8 3 250 13 4 28 6.9 0.5 45 8.5 0.9 70 10.5 1.6 120 13 3.3 140 12.5 2.8 300 21 4.9 350 18.5 4.6 35 9 0.62 55 11 1.3 95 14 1.8 180 21 3.4 190 17.8 3.3 400 28 9 500 25 7
125
160
200
250
315
400
Based on horizontal discharge with air temperature 10k above or below room temperature to a terminal velocity of 0.75 m/s without ceiling effect. Selections meet NC45 assuming 15dB room attenuation.
56
SECTION 12
Heating
rise
Cooling
Jet Nozzles
d i
i di
l
Possible Circular Duct Diameters R 200 250 315 500 630 800
Dimensions
Size 100 125 160 200 250 315 400 D1 136 159 225 265 315 400 485 D2 115 138 201 241 291 376 461 D3 146 169 200 257 302 384 467 D4 98 123 158 198 248 313 398 D5 50 64 82 108 136 174 230 E 10 10 11 16 16 23 24 F -2 4 10 14 23 29 47 K 134 157 188 242 287 358 441 L1 94 112 122 153 187 224 287 L2 78 89 106 127 159 189 223 L3 80 90 110 140 170 220 260 Size 100 125 160 200 250 315 400
R
D3 60 60 K D4 D3 K
Rotary actuator
Rotary actuator DUK-V-A-E1...E3 (shown) DUK-V-A-E1...E3 (shown) DUK-V-K-E1...E3 (shown) DUK-V-A-P DUK-V-K-E1...E3 (shown) DUK-V-K-P DUK-V-A-P DUK-V-K-P
Type DUK-V-R
Examples of circular duct connection
15
D4
D5 D3
15
Type DUK-V
L2 F
Type DUK-V-K
Examples of rectangular duct connection
9
DUK V
L1 Counterpunched hole 4.5mm for raised countersunk self-tapping screws 4.2 x 16, DIN 7973
D1 D2
D5
DUK-F
Type DUK-F
10
57
Order Code
AJA - CF - A
Type CF = Circular Face or blank Rear Assemblies A = Without NOTE:
1)
250 X 2
Size 200 250 300 350
P3
RAL 9010
20% Gloss
Not Used
Order Code
Plenum Nozzle Type
AK - AJA - ZV - AG
250 X 2
Size (mm) 200 250 300 350
GO
NOTE: 1)Plenum for CP (circular face) only available for single element units
Dimensions
Size 200 250 300 350 C 350 400 450 500 L2 650 750 850 950 L3 950 1100 1250 1400 Nominal L4 1250 1450 1650 1850 Size A 200 250 300 350 E 50 65 75 85 F 180 195 205 235 WxZ 310 310 360 360 410 410 460 460 B 200 250 300 300 H 200 250 300 350
rise
fall
30
Heating
58
SECTION 12
Performance Data
AJA Size 200 1 Element 250 300 350 Throw L (m) Rise + Fall (m) Throw L (m) Rise + Fall (m) Throw L (m) Rise + Fall (m) Throw L (m) Rise + Fall (m) AJA Size 200 2 Element 250 300 350 Throw L (m) Rise + Fall (m) Throw L (m) Rise + Fall (m) Throw L (m) Rise + Fall (m) Throw L (m) Rise + Fall (m) AJA Size 200 3 Element 250 300 350 380 420 470 570 Throw L (m) 11 12 14 15 Rise + Fall (m) 6.5 7.0 7.5 8.0 Throw L (m) 12 Rise + Fall (m) 7.5 Throw L (m) 11 Rise + Fall (m) 10.0 Throw L (m) Rise + Fall (m) AJA Size 200 4 Element 250 300 350 Throw L (m) Rise + Fall (m) Throw L (m) Rise + Fall (m) Throw L (m) Rise + Fall (m) Throw L (m) Rise + Fall (m) 420 470 570 660 9 11 12 14 4.5 5.0 5.5 6.5 11 6.5 660 17 8.5 14 9.0 12 10.5 750 20 9.0 25 9.5 14 11.0 95 140 190 230 280 8 9 12 15 18 4.0 5.5 7.0 9.0 10.0 12 15 9.0 10.0 11 14 12.0 12.5 11 8.5 330 21 12.0 17 10.5 15 14.5 12 12.0 Volume (l/s) 380 420 470 570 660 750 850 940 1040
18 21 24 28 30 11.5 13.0 14.0 15.5 17.0 17 18 21 24 28 34 37 43 15.0 16.5 18.0 20.0 22.0 24.0 34.0 43.0 14 15 17 20 24 28 30 34 37 14.0 15.5 17.0 19.0 24.0 29.0 31.0 33.0 35.0
Volume (l/s) 95 140 190 230 280 330 380 420 470 8 9 11 12 14 15 17 5.0 5.5 6.0 6.5 7.5 8.0 9.0 11 12 14 7.5 8.0 9.0 9 11 12 7.0 10.0 11.0
Jet Nozzles
Volume (l/s) 850 940 1040 1130 1230 1320 23 24 28 10.0 13.0 15.0 17 18 21 23 24 25 10.0 11.0 12.0 12.5 13.0 14.0 15 17 18 20 21 23 12.5 13.0 14.0 14.5 15.0 16.0 12 14 15 17 18 20 11.0 13.0 15.0 16.0 17.5 19.0
Volume (l/s) 750 850 940 1040 15 17 18 21 7.0 7.5 9.0 9.5 12 14 15 17 7.0 7.5 8.0 9.0 14 9.5
1130 1230 1320 23 24 26 10.0 11.0 11.5 18 18 20 10.0 10.5 10.0 15 17 18 10.0 12.0 13.0 14 15 15 13.5 14.0 14.5
Based on horizontal discharge with air temperature 10K above or below room temperature to average terminal velocity of 0.25m/s without ceiling effect. Selections meet NC45 assuming 15dB room attenuation.
Type AJA
Standard type with square face section. Border: for plenum or flanged duct fitting.
F Flange duct section E Duct
Installation
Suspension by others 30
Lockable lever
60 Conical Adjustment
W x Z duct size
A nom size
A Nominal size
30
450
BxH