DELTA POWER ENGINEERING AND CONSULTING

34.5kV
P 5 Ip Ip 30MVA Dyn1

Ip
RC

Ioc
OC

87T RC

Is Is S 5 13.8kV

Is

If Ip = Is then Ioc = 0
a.) The current transformers and differential relays should be properly connected. b.) Current transformers should be properly sized.

DELTA POWER ENGINEERING AND CONSULTING

34.5kV
P 5 Ip Ip 30MVA Dyn1

Vector Group Analysis


HV side connection - Delta LV side connection - Wye LV side neutral Vector position 1 oclock

87T

Dyn1
Is Is S 5 13.8kV

DELTA POWER ENGINEERING AND CONSULTING

A 11 oclock a Dyn11 9 oclock a Dyn9 7 oclock a Dyn7 a a 1 oclock Dyn1

Vector Group Analysis


HV side connection - Delta LV side connection - Wye LV side neutral Vector position 1 oclock

a 3 oclock Dyn3 a 5 oclock Dyn5

Dyn1

DELTA POWER ENGINEERING AND CONSULTING

A a

Vector Group Analysis

n
1 1 2

Dyn1 3

n
2

C
3

DELTA POWER ENGINEERING AND CONSULTING

A 1 1 2 c 3 n

2
b

B A
Ia Ib

Ic

1
Ia

2
Ib n

3
Ic

a b c

DELTA POWER ENGINEERING AND CONSULTING

A 1 1 2 c 3 n

2
b

Ia

Ib

Ic

1
Ia

2
Ib n

3
Ic

DELTA POWER ENGINEERING AND CONSULTING

A 1 1 2 c 3 n

2
b

A
Ia-Ib Ip Ib-Ic Ib Ia Ia

B
Ic-Ia

I (in) = I (out) Ip + Ib = Ia Ip = Ia - Ib

Ib

Ic

1
Ia

2
Ib n

3
Ic

DELTA POWER ENGINEERING AND CONSULTING

Ia-Ib

Ib-Ic

Ic-Ia

Ia

Ib

Ic DELTA POWER ENGINEERING AND CONSULTING

Ia-Ib

Ib-Ic

Ic-Ia

Ia

Ib

Ic DELTA POWER ENGINEERING AND CONSULTING

Ia-Ib

Ib-Ic

Ic-Ia

Ia

Ib

Ic DELTA POWER ENGINEERING AND CONSULTING

Ia-Ib

Ib-Ic

Ic-Ia

Ia-Ib

Ib-Ic

Ic-Ia

Ic-Ia

Ib-Ic

Ia-Ib

Ia

Ib

Ic DELTA POWER ENGINEERING AND CONSULTING

Ia-Ib

Ib-Ic

Ic-Ia

Ia-Ib

Ib-Ic

Ic-Ia

Ic-Ia

Ib-Ic

Ia-Ib

Ia

Ib

Ic

Ia

Ib

Ic DELTA POWER ENGINEERING AND CONSULTING

34.5kV
600 P 5 Ip = 502A Ip 30MVA Dyn1 Solve for Ip : Ip =

Sizing of CTs
30MVA 34.5kVe3 Ip = 502A

Solve for Is :
87T

Is Is = 1255A 2500 S 5 13.8kV

30MVA 13.8kVe3 Is = 1255A Is = Specify P and S such that Ip = Is Let P = 600 For S : Since CT is delta-connected, S = Ise3 S = 1255e3 S = 2174 Let S = 2500

DELTA POWER ENGINEERING AND CONSULTING

34.5kV
600 5 Ip = 502A Ip = 4.18A 30MVA Dyn1 Solve for Ip : Ip =

502A x 5 600 Ip = 4.18A

Solve for Is :
87T

Is = Is = 4.35A

1255A x 5 x e3 2500

Is = 4.35A

Is = 1255A 2500 5 13.8kV

DELTA POWER ENGINEERING AND CONSULTING

502A

600 5

4.18A

4.18A

4.35A

2500 5

2.51A

1255A

DELTA POWER ENGINEERING AND CONSULTING

502A

600 5

4.18A 4.18A

1255A

DELTA POWER ENGINEERING AND CONSULTING

502A

600 5

4.18A 4.18A

2.42A

N1 N2

4.18A

1500 5 1255A

4.18A

N1 4.18A = N2 2.42A

DELTA POWER ENGINEERING AND CONSULTING

Output to relay
2.42A

N1

4.18A

N2

Input from line CTs

N1 4.18A = N2 2.42A

N2 = N1

2.42A 4.18A

Use output windings (S1-S2) and (S3-S4). Hence, N1 = 125 + 90 = 215 turns. 2.42A 4.18A N2 = 125 turns N2 = 215 x Use input windings (5 - 6).

DELTA POWER ENGINEERING AND CONSULTING

Thank you !