Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

JP TECHNOSOFT

AHMEDABAD Ph: 27603538 Revision No: R0 Date: 10/08/2011 Email:jptechnosoft@rediffmail.com

DOCUMENT : CABLE SIZING CALCULATION RESULT SHEET

Project : BIL
Sheet No.: 1 Designed By:KJ Cable ID:1 From Location: 12.5 MVA TR ELECTRICAL DATA : Voltage Load PF : : 11000 V 0.80 Load Type Running Load : 12500.00 KVA Future Margin : Laying Method: DUCT Earth : E FOR MOTORISED LOAD : Allowed St. Volt Drop : N.A. Starer Starting PF : N.A. : N.A. Phase Distance :Non-Motorised F.L. Amp 0.00 % SWG (Min) : VCB(1250A) Armoured : ARMOURED :656.08 A : : 3 40 Mtr To Location:11 KV PANEL

Motor Efficiency :N.A. Inrush (n) :N.A. Load Factor:N.A.

CABLE SIZING ON CURRENT CAPACITY : [I Actual = F. L. Amp / Overall DF] o Ambient Temp : 45 C DF: 0.95 Depth_Lay : 750 mm DF: 1.00 o Soil Thermal Ground Temp : 30 C DF: 1.00 150 oC-Cm/W DF: 1.00 Resistivity: Group Deration: 0.70 Overall DF : 0.67 Selected DF: 0.67 Derated Current: Cable Size : 3 No. 1C 979.22 A X 630.0 sq mm

CABLE SIZING ON VOLTAGE DROP : 2 x L/1000] /3 x I x\/ [VD = \ (R COS / )2 + (X SIN / ) Allowed Volt Drop : 1.00 % Cable Size : CABLE SIZING ON FAULT CURRENT : [I fl actual = Fault Curent : 10.50 kA 3 No. 1C 3 No. 1C X 630.0 sq mm

/t] I fl x \
Trip Time X : 1.0000 Sec 630.0 sq mm

Cable Size : ACTUAL DATA FOR SELECTED CABLE(S): F.L. Current : Fault Curent : 2 I R Loss : SELECTED CABLE: 1320.00 A 59.20 kA 1.37 kW

Volt Drop St Volt Drop 2 I R Loss :

0.01 %

:N.A. 0.01 %

Size
Remark :

3 No/Ph

1C

630.0 sqmm

AL(HTXLPE)

ARMOURED

Developed By : www.jptechnosoft.com