HV 110KV
CT 300/5A 10P10
Int=40MVA(1.732x110KV)=210.1A
Set: 300/210.1A=1.42
LV 20KV
CT 1200/5A 10P10
Int=40MVA(1.732x20KV)=1156A
Set: 1200/1156A=1.03
Starting ratio
Turn ponint 2
I2f/I1f
Basic setting
1.42
10% HV CT +
10% LV CT +
19% (tap changer) +
4% relay +
5% margin +
0,5x48+10=34
1.03
48
1.5
15%