Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

CUSTOMER'S DATA SHEET

PROJECT: DATE: SOURCE: PROCESSED ON: TOTAL PAGES: 26.07.2011 Yanbu Outgoing final.inq 26.07.2011 3

SYSTEM SPECIFICATIONS:
SHORT CIRCUIT CURRENT: FREQUENCY: CT RATED VOLTAGE: 40 kA, 3s 60 Hz 0,72 kV

ITEM: 1 CORE: 1
RATIO: CLASS:

CURRENT TRANSFORMER TYPE: SECTION: S1 S2

VISWI_H300

CALCULATED ACCURACY 1200/5 C400; 100VA Rct75 [Ohm] : 0,807 FS/ALF U knee [V] I knee [mA] U exc [V] I exc [mA] : 21,0 : 216,6 : 45,8 : : In[%] 100

0VA;Cos=1 p[%] -0,023 d[min] 0,9 p[%] d[min]

EXCITATION CURVE
1.000

100

Ue [V] 10 1 1

10

100 Ie [mA]

1.000

10.000

ZELISKO, Z/IN Industrietechnik

26.07.2011