C0498a - SYNERGY DISTRIBUTION BOARD DB-T2 (TENANCY 2 LOWER GROUND) REVISION A - 23 MARCH 2007

C0498a-0014(A).xls

REV
FAULT CURRENT: CHASSIS SIZE: CHASSIS RATING: PHASES: 6kA 36 POLES 250A 3 MAINSWITCH: SUPPLIED FROM: SUPPLY CABLE: 100 AMP NON-AUTO ISOLATOR MSB 4C 25 A A A A

PROVIDE THE DB WITH A FULL WIDTH EMPTY DIN RAIL TO ACCOMMODATE FUTURE CONTACTORS AND CONTROLS PROVIDED AS PART OF THE TENANCY FITOUT. PROVIDE THE DB WITH AN AS2293 EMERGENCY LIGHTING CONTROL SYSTEM TO CONTROL THE ASSOCIATED TENANCY EMERGENCY LIGHTS. PROVIDE THE DB WITH SURGE PROTECTION.

CIRC
P1 P2 P3 L1

PH
1 3 3 1

CIRCUIT BREAKER (amps)


20 40 20 20

CONTROL EQUIPMENT
RCD

CABLE SIZE ( mm2 )


2.5 6.0 4.0 2.5

LOCATION
TENANCY 2 TENANCY 2 ROOF PLANT ROOM TENANCY 2

CIRCUIT USE
MFG T1 AC KITCHEN EXHAUST EMERG LIGHTING A A A A A A A A A A A A A A A

AS2293 CONTROL

C0498a-0014(A).xls

Pages inc. any attach. 1 of 1 ELECTRICAL DESIGN GROUP BRISBANE PTY LTD ACN 092 710 793 TRADING AS ELECTRICAL DESIGN GROUP ABN 96 092 710 793