C0498a - SYNERGY DISTRIBUTION BOARD MP-21 (LEVEL 1 RISER 1) REVISION A - 23 MARCH 2007

C0498a-0027(A).xls

REV
FAULT CURRENT: CHASSIS SIZE: CHASSIS RATING: PHASES: 15KA 18 POLES 250AMPS 3 MAINSWITCH: SUPPLIED FROM: SUPPLY CABLE: 200A NON AUTO ISOLATOR MSB 4C 50 A A A A

CIRC

PH

CIRCUIT BREAKER (amps)


100A TMD100 NSC100N

CONTROL EQUIPMENT
PROVIDE A PRIVATE KWH METER (TYPE AS PER THE EQUIPMENT SCHEDULE) PROVIDE A PRIVATE KWH METER (TYPE AS PER THE EQUIPMENT SCHEDULE) PROVIDE A PRIVATE KWH METER (TYPE AS PER THE EQUIPMENT SCHEDULE)

CABLE SIZE ( mm2 )


25.0

LOCATION

CIRCUIT USE
DB-11 A

P1

LEVEL 1 RISER 1

P2

100A TMD100 NSC100N

25.0

LEVEL 2 RISER 1

DB-21

P3

100A TMD100 NSC100N

25.0

LEVEL 3 RISER 1

DB-31

A A A A A A A A A A A A

C0498a-0027(A).xls

Pages inc. any attach. 1 of 1 ELECTRICAL DESIGN GROUP BRISBANE PTY LTD ACN 092 710 793 TRADING AS ELECTRICAL DESIGN GROUP ABN 96 092 710 793