Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

C0498a - SYNERGY DISTRIBUTION BOARD DB-R (LEVEL 7 ROOF PLANT ROOM) REVISION B 16 APRIL 2007

C0498a-0049(B).xls

REV
FAULT CURRENT: CHASSIS SIZE: CHASSIS RATING: PHASES: 6kA 24 POLES 250A 3 MAINSWITCH: SUPPLIED FROM: SUPPLY CABLE: 100 A NON AUTO ISOLATOR MSB 4C 35 A A A A

CIRC
P1 P2 P3 P4 P5 P6 P7 P8

PH
3 3 3 1 1 1 1 1

CIRCUIT BREAKER (amps)


20 20 20 20 20 20 20 20

CONTROL EQUIPMENT

CABLE SIZE ( mm2 )


2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

LOCATION
ROOF PLANT ROOM ROOF PLANT ROOM ROOF PLANT ROOM ROOF PLANT ROOM ROOF PLANT ROOM ROOF PLANT ROOM ROOF PLANT ROOM ROOF PLANT ROOM

CIRCUIT USE
PUMP PUMP PUMP MAINT GPOs BATTERY CHARGER HWS COMMS GPOs HYD PUMP A A A A A A A A

RCD RCD RCD RCD

L1

20

THIS CIRCUIT IS TO BE MONITORED AND A SIGNAL SENT TO THE BMS WHEN THE GENERAL LIGHTING IS OPERATING. THIS CIRCUIT IS TO BE MONITORED AND A SIGNAL SENT TO THE BMS WHEN THE GENERAL LIGHTING IS OPERATING. PE ON/ TC OFF

2.5

ROOF PLANT ROOM

LIGHTING

L2

20

2.5

ROOF PLANT ROOM

LIGHTING

L3

20

2.5

EXTERNAL

SIGNAGE

B A A A A

C0498a-0049(B).xls

Pages inc. any attach. 1 of 1 ELECTRICAL DESIGN GROUP BRISBANE PTY LTD ACN 092 710 793 TRADING AS ELECTRICAL DESIGN GROUP ABN 96 092 710 793