Norton 88kv three phase fault level calculations

Voltage Level at Norton 88kV Base MVA used in calculation Base impedance(100MVA, 88kV) Fault level at Norton 88kV busbar (KA) Fault MVA at Norton 88kV busbar source fault impedance source fault impedance. Pu Norton Transformers T3 Capacity (MVA) Norton Transformers T3% Impedance (pu) T3 % Impedance to 100MVA base (pu) Norton Transformers T4 Capacity (MVA) Norton Transformers T4% Impedance (pu) T4 % Impedance to 100MVA base (pu) Norton Transformers T5 Capacity (MVA) Norton Transformers T5% Impedance (pu) T5 % Impedance to 100MVA base (pu) Total impedance for Tx (pu) Total impedance upto 33kV busbar Fault MVA at Norton 33kV (pu) Fault MVA at Norton 33kV (MVA) Fault Level at Norton 33kV busbar (kA) 88 100 134.13 12.41 1891.538 7.091056 0.052867 50 0.125 0.25 20 0.125 0.625 20 0.1168 0.584 0.136755 0.189622 5.273639 527.3639 9.226476