The Unique Role Wind Turbine Step Up (WTSU) Transformers
The Unique Role Wind Turbine Step Up (WTSU) Transformers
TRANSFORMERS
Introduction:
Harnessing wind energy to perform work is not a new concept.
Since the earliest of times, wind power has been captured with sails to allow traders,
merchants and explorers to ply their trades and discover the world around them.
On land, windmills have been used for irrigation, grinding grains, and performing crude
manufacturing for centuries. Even the generation of electricity from wind power is not a
new idea. What is new, however, is the scale at which this renewable energy source is
being used today.
Early wind generation served a local need, often supplying power for isolated
equipment. Today, wind energy represents nearly 5% of the US electrical generation
and is targeted to reach 20% in the foreseeable future.
Historically this WTSU transformer function has been handled by conventional, “off the
shelf” distribution transformers, but the relatively large numbers of recent failures
would strongly suggest that WTSU transformer designs need to be made substantially
more robust. WTSU transformers are neither conventional “off the shelf” distribution
transformers nor are they conventional “off the shelf” power generator step-up
transformers. WTSU transformers fall somewhere in between and as such, we believe,
require a unique design standard.
Although off-shore wind farms using dry-type transformers are beginning to grow in
popularity, for this discussion we will look only at liquid-filled transformers that are
normally associated with inland wind farm sites.
Transformer Loading:
Wind turbine output voltages typically range from 480 volts to 690 volts. This turbine
output is then delivered to the WTSU transformers and transformed to a collector
voltage of 13,800 to 46,000 volts. The turbines are highly dependant upon local
climatic conditions; and this dependency can result in yearly average load factor as low
as 35%. Both conventional distribution transformers and power generator step-up
transformers are typically subjected to more constant loading at, or slightly above, their
theoretical maximum rating. This high level of loading stresses insulation thermally and
leads to reduced insulation life. On the other hand, the relatively light loading of WTSU
transformer has a favorable effect on insulation life but introduces two unique and
The first problem is that, when lightly loaded or idle, the core losses become a more
significant economic factor while the coil or winding losses become less significant and
de-emphasized. Typically used price evaluation formulae do not apply to this scenario.
NEMA TP1 and DOE efficiencies are not modeled for the operational scenario where
average loading is near 30-35% and, consequently, should be cautiously applied when
calculating the total cost of ownership for WTSU transformers
The second problem is that the WTSU transformer goes into thermal cycling as a
function of these varying loads. This causes repeated thermal stress on the winding,
clamping structure, seals and gaskets. Repeated thermal cycling causes nitrogen gas to
be absorbed into the hot oil and then released as the oil cools, forming bubbles within
the oil which can migrate into the insulation and windings to create hot spots and
partial discharges which can damage insulation. The thermal cycling can also cause
accelerated aging of internal and external electrical connections.
These cumulative effects put the WTSU transformer at a higher risk of insulation and
dielectric failure than either the typical “off the shelf” distribution transformer or the
power generator step-up transformer experiences.
While potentially aiding in the initial energization, these same electronic controls
contribute damaging harmonic voltage frequencies that, when coupled with the non-
sinusoidal wave forms from the wind turbines, cannot be ignored from a heating point
of view. Conventional distribution transformers do not typically see non-linear loads
that require preventative steps due to harmonic loading. When a rectifier/chopper
system is used, the WTSU transformer must be designed for harmonics similar to
rectifier transformers, taking the additional loading into consideration as well as
providing electrostatic shields to prevent the transfer of harmonic frequencies between
the primary and secondary windings, quite dissimilar to conventional distribution
transformers.
Since wind turbines must stay connected during disturbances in the network, the WTSU
transformers must be designed to withstand the full mechanical effects of short circuits.
Conclusions:
The role of WTSU transformers in today’s wind generation scheme is unique; it’s design
must be equally unique and robust. The combination of wide variations in loading;
harmonic loads from associated control electronics and generators; sizing without
protection for over-voltages, under-voltages or over-loading; and the requirement to
“ride through” transient events and faults sets the WTSU apart from it’s more
conventional, “off the shelf” counterparts. It is neither a conventional distribution
transformer nor is it a conventional generator step-up transformer.