Typical limiting values of Sub-station electrical equipments. 1.

Transformer / Reactor:
SL. NO. EQUIPMENT / TEST DATA PERMISSIBLE LIMITS REFERENCE

Transformer oil a) BDV -At the time of first charging -During O&M b) Moisture content A) -At the time of first charging -During O&M c) Resistivity at 90 degree C d) Acidity e) IFT at 27 degree C f) Tan delta at 90 degree C g) Flash point B) Vibration level for reactors 15 PPM (Max.) 25 PPM (Max.) 0.1-1012 Ohm-CM (Min.) 0.2 mg KOH/gm (Max.) 0.018 N/M (Min.) 0.20 (Max.) 126 Deg. C (Min.) 200 Microns (Peak to Peak) 60 Microns (Average) C) D) E) F) Tan delta for bushing at 20 Deg. C Capacitance for bushing IR value for winding Tan delta for windings at 20 Deg. C Contact resistance of bushing terminal connectors H) Turret Neutral CT ratio errors 39 0.007* + 5% variation 1000 M-Ohm By 5.0/10.0 kV Ins. Tester 0.007* 10 M. Ohm / Connector

60 kV (Gap-2.5 mm)-Minimum
50 kV (Gap 2.5 mm) Minimum

IS 1866 IS 1867 IS 1868 IS 1869 IS 1870 IS 1871 IS 1872 IS 1873 IS 1874 IS 1875 IS 1876 IS 1877 IEC 137 IEC 138 IEC 139 IEEE/C57.12.90.1980 NGC.UK Recommendations IS 2705