The following diagram is a clarification of the Commander SK Getting Started Guide manual, figure 4-1, Size A power terminal connections diagram. The connection to the Optional Line Reactor is wired between the L1 terminal of the drive (or through the Optional EMC filter) and the Mains supply L1. The other connection to the Mains supply (L2 or Neutral) is wired directly to the drive on terminal L2/N or through the Optional EMC filter. What is shown in the Getting Started Guide manual is a symbolic drawing. A standard single phase line reactor would have only two (2) connections, one in and one out. The modified diagram is shown below.