DGA Oil Quality Source of Gas Byproducts of Faults Oil Hydrogen Hydrocarbons Cellulose Carbon Oxides Water
Page 4 OMICRON OMICRON Page 5 C C H H H H C H H H H C H H H C H H H C C C C C H H H H H HH H H H C C H H H H Acetylene Ethylene Methane Ethane Hydrogen Heating Heating Arcing Corona Heating Oil - Byproducts OMICRON Page 6 Degradation of cellulose O H O H O H OH OH O H H CH 2 O CH 2 OH H O H H O OH H Heating Heating C O O C O O H H Carbon Monoxide Carbon Dioxide Water Section of Cellulose Molecule DGA Analysis 1. Fault Gas Levels 2. Rate of Gas Generation (Trend) 3. Ratio of Gas Levels
Oil: Acetylene, Hydrogen Sources of Fault Gases in Transformers OMICRON Page 11 Gas Generation (Not to Scale) Approximate Oil Decomposition Temperature above 150 o C
IEEE and IEC Codes to Interpret Incipient Faults in Transformers, Using Gas in Oil Analysis, by R.R. Rogers C.E.G.B, Transmission Division, Guilford, England. Circa 1978. Partial Discharge (Not Temperature Dependent) Range of Normal Operation Hot Spots (Of increasing temperature) Arcing Conditions 6 5 o
1 5 0 o
2 0 0 o
3 0 0 o
8 0 0 o
7 0 0 o
5 0 0 o
3 5 0 o
2 5 0 o
Hydrogen (H 2 ) Methane (CH 4 ) Ethane (C 2 H 6 ) Ethylene (C 2 H 4 ) Acetylene (C 2 H 2 ) CH 4 >H 2
C 2 H 6 >CH 4
C 2 H 4 >C 2 H 6
C 2 H 2 >10% of C 2 H 4
Trace Combustible Gas Generation vs. Approximate Oil Decomposition Temperature DGA Diagnostic Methodology 1. Determine if DGA results are Normal 1. Single sample compare results to C57.104-2008 Table 1 2. If greater than condition 1 then retest sample within two months 1. Verifies results from first test 2. Establishes gas generation rate 3. Greater than one sample 1. Calculate gas generation rate 2. Compare rate to values in C57.104-2008 Table 3 1. Sampling interval 2. Action 2. If DGA results are abnormal then follow various methodologies to determine fault type and possible cause. 1. Key gas 2. Gas ratios
Page 12 OMICRON OMICRON Page 13 Dissolved Key Gas Concentration Limits (L/L (ppm)) Status H 2
-PD: partial discharges of the corona-type. -D1: discharges of low energy. -D2: discharges of high energy. -T1: thermal fault (T < 300C). -T2: thermal fault (300 C < T < 700C). -T3: thermal fault (T > 700C). -DT: mixtures of discharges and thermal faults.
-S: stray gassing of oil (T < 200 C), catalytic reactions (not related to faults). 16
Typical faults in the equipment:
-PD: corona partial discharges in voids or gas bubbles (poor drying, impregnation). -D1: partial discharges of the sparking type, tracking in paper, small arcing, arc breaking in LTC oil. -D2: short circuits with power follow-through, flashovers, tripping, gas alarms; extensive damage, metal fusion.
17
Typical faults in the equipment:
-T3: large circulating currents, shorts in laminations, carbon particles in oil. -T2: circulating currents, defective contacts, carbonization of paper. -T1: overloading, insufficient cooling. -S: stray gassing , catalytic reactions on wet metal surfaces.
18
Mixtures of faults
-mixtures of faults sometimes occur rather than pure faults and may be more difficult to identify with certainty. -for instance, mixtures of faults D1 and T3 may appear as faults D2 in terms of gas formation.
19 Energy/ temperature required to produce gases:
-Low energy/temperature: H 2 , CH 4 , C 2 H 6 , CO, CO 2 . -High temperature: C 2 H 4 . -Very high temperature/energy: C 2 H 2 .
-In practice, always mixtures of gases are formed. 20 Fault identification methods -Key gas -Rogers -Duval Triangle
-CO and CO 2 (paper involvement in faults) -O 2 /N 2 (hot spots, membrane leaks) -C 2 H 2 /H 2 (OLTC leaks)
OMICRON Page 21 Oil Cellulose Hydrogen Carbon Monoxide, Carbon Dioxide Parti al Di scharge Oil Low Temperature Hydrogen, Methane, Ethane High Temperature Hydrogen, Ethylene, Methane, Ethane Cellulose Low Temperature Carbon Dioxide High Temperature Carbon Monoxide, Carbon Dioxide Pyrol ysi s (Acetylene is most significant) Hydrogen, Acetylene, Methane, Ethane, Ethane, Ethylene Arci ng IEEE C57.104-2008 Key Fault Gases Possible Faults Possible Reasons Rogers Ratio DGA Diagnosis (Duval) OMICRON Page 26 Oil Quality Tests Tests the condition of the insulating fluid.
Use results for maintenance action No action Recondition Reclaim Replace Use the results to access the condition of the Insulation System Dielectric Strength Power Factor Moisture Acid Furans
OMICRON Page 27 Oil Quality Tests Several standards are referenced for oil quality tests and result interpretation:
IEC 60422 Mineral Insulating Oil in Electrical Equipment Supervision and Maintenance Guide
IEEE Guides C57.106-2006 Guide for Acceptance and Maintenance of Insulating Oil in Equipment C57.152 IEEE Guide for Diagnostic Field Testing of Fluid Filled Power Transformers, Regulators, and Reactors
Dielectric, Physical and Chemical Analysis Dielectric measurements Break down voltage ASTM D 877 Break down voltage ASTM D 1816 IEC 60156 Power factor ASTM D 924 IEC 60247 Physical properties Interfacial tension ASTM D 971 EN 14210 Particle Count ASTM D 6786 IEC 60970 Sludge ASTM D 1698 Water content ASTM D 1533 IEC 60814 Visual ASTM D 1500 ISO 2049 Specic gravity ASTM D 1298 ISO 3675 Color (lab) ASTM D 1500 ISO 2049 Color (eld) ASTM D 1524 Chemical properties Polychlorinated biphenyl ASTM D 4059 IEC 61619 Acidity ASTM D 974 IEC 62021 Dissolved gas ASTM D 3612 IEC 60599 OMICRON Page 29 IEEE Oil Classifications Class I This group contains oils that are in satisfactory condition for continued use.
Class II This group contains oils that do not meet the dielectric strength and/or water content requirement of Table 5 and should be reconditioned by filter pressing or vacuum dehydration.
Class III This group contains oils in poor condition that should be reclaimed using Fullers earth or an equivelent method. Oils that do not meet the interfacial tension (IFT), dissipation factor, and neutralization number limits provided in table 5 should be reclaimed.
OMICRON Page 30 IEEE C57.106-2006 Suggested Limits If limits for: IFT Dissipation Factor Acidity are exceeded the oil should be reclaimed otherwise the oil can be reconditioned if the limits are exceeded.
OMICRON Page 31 Moisture Content Karl Fisher Titration
Requires approximately 10 mL of oil.
Results are in ppm (mg/kg) OMICRON Page 32 Interfacial Tension (IFT) Measures the strength of the interface between the oil under test and water.
Indicator of the presence of polar contaminents. OMICRON Page 33 Dielectric Strength OMICRON Page 34 Aging process : Cellulose depolymerization CH 2 OH O OH OH O CH 2 OH OH OH O O CH 2 OH OH OH O CH 2 OH O OH OH O H CH 2 OH OH OH O O CH 2 OH OH OH O OH OMICRON Page 35 CH 2 OH O H H H OH OH O H H O Glucose Unit Cellulose Degradation OMICRON Page 36 Degree of Polymerization Measurement of intrinsic viscosity after dissolving the cellulose in a specific solvent. Gives an average measurement of the number of glucose units per molecular chain.
DP of Insulation Components prior to processing ~1200 DP of Insulation Components following processing ~1000 DP level considered as over-processed ~800 DP level considered end of life ~200
OMICRON Page 37 Degree of Polymerization Effects of aging: - darkening of color - loss of electrical and mechanical strength; trans. failure - shortening of cellulose chains DP lowered - paper becomes wetter, and acidic - by-products contaminate the oil
Source ABB Power Technologies, Inc.
Progressive aging with time Paper Insulation Aging in Mineral Oil DP DP DP DP DP
1000 733 549 405 309 DP 181 Brittle & dark End of mech str. IEEE Transformer Committee Panel Session October 25, 2005
OMICRON Page 38 HOH CO HOH HOH CH 2 OH OH O O H H H H O C OH H O CHO H H H WATER WATER WATER FURAN CARBON MONOXIDE Degradation of Cellulose OMICRON Page 39
Most labs determine the concentration of five furanic compounds:
Note: 2FAL is stable for years while all other furanic compounds are less stable. They tend to form and then degrade to 2FAL over a time period of months. Furans OMICRON Page 40
2- Furfural vs. DP Correlation Plots Correlation of DP with 2-FAL OMICRON Page 41 Summary & Conclusions DGA is a valuable tool to detect transformer problems Sample can be taken while transformer is in service Can trend fault gases Industry Acceptance
Oil Quality Testing can detect transformer problems as well as indicate maintenance actions Oil can be reconditioned or reclaimed Inceases life of insulation system Remove moisture, acids, particles etc.
The remaining life of the insulation can be estimated with Furan analysis 31 October 2013 Questions