on
Upgraded Thermal Insulation System
for Dairy Industry
by
K.K. Mitra / Ashu Sharma
LLOYD INSULATIONS (INDIA) LIMITED
Thermal Insulation
A provision made to retard heat flow from a hot
surface to a cold environment and from cold surface
to a warm environment.
This simple device in Industry has acquired
enormous importance in recent times for what it can
do for us if we were to give a very little extra
attention
Todays need is for Correctly designed and well installed
insulation system.
Which is Easy on the purse
Speedy to erect
Stays maintenance-free & Efficient in service
An efficient insulation in place serves our best interests
in todays context
Economy: safety :smoother process control at Plant
level
Substantial reduction of fuel costs & enhanced
profitability at the corporate level
Reduction of Greenhouse gas emissions at the larger
Global level
DIFFERENCE IN TEMP. BETWEEN
AMBIENT AND SURFACE
0
C
HEAT LOSS
KCAL/M
2
HR.
25
40
100
150
200
340
600
1910
3225
5330
Insulation can being down heat losses to 90-150
kcals/m2.hr.
DIFFERENCE IN TEMP. BETWEEN
AMBIENT AND SURFACE
0
C
HEAT LOSS
KCAL/M
2
HR.
5
10
15
20
38
76
125
165
Properly designed cold insulation can cut down to
10-15 kcal/m2 hr
SUSTAINABILITY
Thermal transmission, or the transfer of heat
from a warmer body to a colder body may in
principal take place in the following ways:
1) Conduction - Transfer of heat through
solid/liquid material.
2) Convection - The moving of heat through
moving fluid or gas.
3) Radiation - Transfer of heat by means of
electromagnetic waves.
Heat Conduction
Conduction is heat transfer by means of molecular agitation within a material
without any motion of the material as a whole. The higher speed particles will
collide with the slower ones with a net transfer of energy to the slower ones.
For heat transfer between two plane surfaces, the rate of conduction heat
transfer is:
Q= heat transferred in time =
K = thermal conductivity of the barrier
A = area
T = temperature
d= thickness of barrier
SUSTAINABILITY
SUSTAINABILITY
The exact rate of Heat Loss is very complicated to calculate on
theoretical ground alone, since it shall be affected by -
Air movement on casing surface / Ambient wind velocity
Colour / Texture of the casing ( e.g. casing emissivity)
Vertical and horizontal orientation of the casing
Exposure to thermal radiation,(e.g. Sun light)
SUSTAINABILITY
Surface Heat Transfer or film Coefficient ( f )
Time rate of heat flow per unit area by convection and
radiation from unit area of the surface, for unit
temperature difference between the surface and the
surrounding medium.
f = f
Conv.
+ f
Rad
.
SUSTAINABILITY
Insulation
Wind Speed =V
Surface1 Emissivity = e
Conducted heat through insulation
Surface Heat Transfer or film Coefficient
f
Conv.
=1.683 x (T
s
- T
a
)
0.25
x (2.857 x V+ 1)
0.5
Heat
Ambient Temp (T
a
)
Surface Temp. (T
s
)
f
Rad
= 4.876 x 10
-8
x ex ( T
s
4
- T
a
4
)
( T
s
- T
a
)
Components of Heat Transmission
f = 4.876 x 10
-8
x ex + 1.683 x (T
s
- T
a
)
0.25
x (2.857 x V + 1)
0.5
( T
s
- T
a
)
( T
s
4
- T
a
4
)
Surface Heat Transfer or film Coefficient
SUSTAINABILITY
As per IS 14164 values of f under still air condition
Bright Aluminium :
New GI Sheet :
Hard Setting Plaster :
W/m
2
K Kcal/m
2
hr.
0
C
5.7 4.9
7.9 6.8
10.2 8.7
SUSTAINABILITY
Heat Loss (q) from Insulated Surface :
q=
T
o
- T
a
L 1
K f
+
For Flat Surface
T
o
= Operating Temperature
T
a
= Ambient Temperature
K = Thermal Conductivity of Insulation
L= Thickness of Insulation
f = Surface FilmCoefficient
For Cylindrical Surface
q=
T
o
- T
a
d d
1
d
2K d fd
1
+
ln
d = OD of Insulation
d
1
= OD of Cylinder
d
1
d
SUSTAINABILITY
Thickness Calculation based on ASTM C 680
Upgraded & latest method to calculate thickness of
insulation
Calculates effect of windage & emissivity for each
pipeline
Slightly more thickness
Reduced heat loss
SUSTAINABILITY
ILLUSTRATION
OT : 250 deg.C
AT : 40 deg.C
ST : 60 deg.C
Cladding : Aluminium ( 0.2 Emissivity)
Wind Velocity : 0, 0.5, 1
Pipe OD : 8,10, 12
Insulation : ROCKWOOL MATTRESSES
100 KG/M3 DENSITY
Calculation : ASTMC-680 & IS-14164
Procedure
As per IS-14164 As per ASTMC-680
Dia
(mm)
Thickness
(mm)
Heat Loss
(Kcal/m
2
hr.)
Thickness
(mm)
Heat Loss
(Kcal/m
2
hr.)
8 105 98 95 85
10 110 98 100 85
12 115 98 100 85
WINDAGE = 0
SUSTAINABILITY
COMPARATIVE OF THICKNESS
As per IS-14164 As per ASTMC-680
Dia
(mm)
Thickness
(mm)
Heat Loss
(Kcal/m
2
hr.)
Thickness
(mm)
Heat Loss
(Kcal/m
2
hr.)
8 65 145 70 117
10 65 145 75 117
12 65 145 80 117
SUSTAINABILITY
WINDAGE = 0.5
COMPARATIVE OF THICKNESS
As per IS-14164 As per ASTMC-680
Dia
(mm)
Thickness
(mm)
Heat Loss
(Kcal/m
2
hr.)
Thickness
(mm)
Heat Loss
(Kcal/m
2
hr.)
8 55 163 60 141
10 55 163 65 141
12 55 163 65 141
SUSTAINABILITY
WINDAGE = 1
COMPARATIVE OF THICKNESS
SUSTAINABILITY
Windage
Thickness reduces with wind impact.
Emissivity
Thickness reduces with dull surface.
SUSTAINABILITY
SELECTION OF INSULATION MATERIAL:
THE MATERIALS USED FOR INSULATION SHALL CONFORM
TO THE RELEVANT INDIAN STANDARDS WHEREEVER THEY
EXSIST.
INSULATION MATERIAL USED SHOULD BE SUITABLE FOR
USE AT THE OPERATING TEMPERATURE AS STATED BY THE
PURCHASER.
HAND MADE MATERIALS FROM LOOSE WOOL ARE NOT
PERMITTED DUE TO POOR CONSISTENCY.
ALL INSULATION MATERIAL SHALL HAVE A PROVEN
SERVICE RECORD OF SATISFACTORY PERFORMANCE
UNDER INDIAN CONDITIONS IN SIMILAR PROCESS PLANT
SUSTAINABILITY
Corrosion resistant
Water repellents
Fire Proof / non combustible
Durability
Green insulation materials
OTHER IMPORTANT ASPECTS
THERMAL INSULATION
a) Design Data
Design ambient Temp. : 40 deg.C
Max. Cladding Temp. : 60 deg. C
Wind Speed : 0 or 0.25 m/sec. for inside
0.5 m/sec. for outside
0 m/sec. for Energy
Conservation
TYPICALLY FOLLOWED DESIGN PARAMETERS
IN INDIA
THERMAL INSULATION
b) Design Data
Emissivity of cladding
Aluminium : 0.2
GI : 0.3
Colour coated GI : 0.65
Plaster : 0.65
Glass Cloth : 0.85
c) Pipe / Equipment wall temp. : Fluid design temp.
d) Thickness Calculation Method : ASTM C-680
(Determination of Heat
Gain or Loss and the
Surface Temperatures of
insulated pipe and
Equipment system
Financial Implications of Performance
Specs
0
50000
100000
150000
200000
250000
300000
40 50 60 70 80 90
1982
1988
1991
1998
2004
2008
System details:
Pipe Dia-(NB): 100mm
Surface Film Coeff
:12kcalm2hr C
Ambient Temp : 29 C
Hours of Operation : 8000
Hrs.
Conversion Eff.: 100%
Surface Temp. over
insulation in C (specified)
C
o
s
t

o
f

l
o
s
t

h
e
a
t

/

1
0
0

m
t
r
s

/

a
n
n
u
m

i
n

R
s
.
Economic reasons for Thermal insulation
in industry
Reduces fuel consumption,
and hence overall cost of
operation
Reduces capacity
requirements for
heating/cooling systems
(e.g., boilers/ refrigeration
units, etc)
Benefits of higher profits to
owner
Savings in Project Capital costs
Thermal Insulation
The function of Thermal Insulation is performed not
just by a single material, but by an assembly of
engineered provisions or components termed as,
Thermal Insulation System. As called for in all
such works, there is need for careful design of all
such elements.
From this, we can see that insulation is a major tool
in improving energy availability.
The task of the insulation designer is to
evolve system which fit the need-like a
glove to a hand that would wear it.
Thermal Insulation Design
Thermal Properties of Insulation Materials
Important thermal parameters of thermal insulation
materials are
Temperature resistance- limiting service temperature
Thermal conductivity
Coefficient of Expansion / Contraction
Thermal diffusivity, and
Thermal shock resistance
Commonly used Hot Insulation Materials
Mineral wool : our Rockloyd range
Rockloyd Mattress
Rockloyd Slab
Rockloyd Pipe sections
- Conform to IS 8183, BS 3958 &ASTM-C-592/ C-612 IS 9842& C-
547.
- Incombustible when tested as per IS 3144
- Concurrently approved as A-15, A-30 & A-60 Class fire barrier
insulation under SOLAS,
30
Rockwool Water Repellant Grade
Rock Fibres treated with SILANE
31
32
33
34
35
APPLICATION SPECIFICATIONS FOR HORIZONTAL / VERTICAL
HOT PIPELINES
A. For single layer insulation up to maximum thickness of
75mm
Cleaning the surface thoroughly to ensure that the surface is free of
all dust, rust and grease.
Providing and fixing MS flat ring of size 25x3mm, over pipe having
diameter more than 100mm, at every 1150 mm distance having
L shaped lugs with a packing of ceramic paper, duly riveted and
tightening it over the surface with nut and bolt.
Providing and fixing the recommended insulation thickness of
Rockloyd Resin Bonded Rockwool mattress of suitable density
stitched with one side GI wire netting of size 20mm X 24G .
Butting the joints and stitching the mattress properly with GI wire of
20G to secure it firmly to the surface .
36
APPLICATION SPECIFICATIONS FOR HORIZONTAL / VERTICAL
HOT PIPELINES
A. For single layer insulation up to maximum thickness of
75mm
Providing and fixing Aluminium / Zincalume steel sheet cladding
screw at 150mm distance at the sheet joints making an overlap
of minimum 30mm. Sealing all the joints with mastic MAS-94.
Please note that for bare zincalume sheet the MS flat ring should
be fixed at 1200mm distance.
Providing and applying 22G Aluminium band at every 450mm c/c
over the cladding to secure it firmly to its place
37
APPLICATION SPECIFICATIONS FOR HORIZONTAL /
VERTICAL HOT PIPELINES
B. For multiple layer insulation above 75mm thickness.
Cleaning the surface thoroughly to ensure that the surface is free of
all dust, rust and grease.
Providing and fixing MS flat ring of size 25x3mm, over pipe having
diameter more than 100mm, at every 1150 mm distance
having L shaped lugs with a packing of ceramic paper, duly
riveted and tightening it over the surface with nut and bolt.
Providing and fixing the first layer of insulation in recommended
thickness of Rockloyd Resin Bonded Rockwool mattress of
suitable density stitched with one side GI wire netting of size
20mm X 24G.
Butting the joints and stitching the mattress properly with GI wire of
20G to secure it firmly to the surface
38
APPLICATION SPECIFICATIONS FOR HORIZONTAL /
VERTICAL HOT PIPELINES
B. For multiple layer insulation above 75mm thickness.
Providing and fixing the second / subsequent layer of insulation in
recommended thickness of Rockloyd Resin Bonded Rockwool
mattress of suitable density stitched with one side GI wire
netting of size 20mm X 24G.
Butting the joints and stitching the mattress properly after every
layer with GI wire of 20G to secure it firmly to the surface.
Providing and applying 22G Aluminium band at every 450mm c/c
over the final layer of insulation to secure it firmly to its place.
Providing and fixing Aluminium / Zincalume steel sheet cladding
screw at 150mm distance at the sheet joints making an overlap
of minimum 30mm. Sealing all the joints with mastic MAS-94.
Please note that for bare zincalume sheet the MS flat ring
should be fixed at 1200mm distance.
Providing and applying 22G AL band at every 450mm c/c over the
cladding to secure it firmly to its place
Insulation Materials for High
Temperatures
Ceramic Fibre: Supercera range
(RT grade up to 1260 C
HT Grade up to 1430 C )
Supercera needled Blankets and fabrications such as:
Folded modules
Encased flexible sections
Supercera Bulk Fibre
Supercera rigid Boards / Vacuum formed blocks & Shapes
Moist felt / Paper / Rope
Calcium Silicate.
Insulation Materials for High
Temperatures
Ceramic Fibre: Supercera range
Also used as Fire protection in
Structural Steel applications
Cable Trays
Ship Bulkheads / deckheads
Turbine Insulation
Removable Type Pads
Supercera Ceramic fibre Removable Pads for
Turbine Insulation
42
SUPERCERA PADS
Supercera blankets of density 128 kg/m3 and thickness 50 &
75mm encased in Supercera Cloth and stitched with SS Wire to
form pads. Special hooks are stitched to the surface and
corners for the purpose of positioning & tieing.
USES : Steam Turbine Insulation, Fire Walls for
Isolation, Valves & Flange Insulation
AVAILABILITY : Width : 610mm;
Length Max. : 7 mtr.
43
SUPERCERA PADS FOR VALVES & FLANGES
INSULATION
44
SUPERCERA PADS
VESSEL INSULATION
Commercial Cold Insulation Materials
Polyurethane Foam (PUF)
Polyisocynurate Foam (PIR)
Foamglass
Phenolic Foam
Expanded Polystyrene (EPS)
Low Temperature Insulants
Among the listed materials, Polyurethane and
Polyisocyanurate, representing products of lowest
Thermal conductivity are materials of choice
because of the easy availability in commercial
quantities and the versatility they offer.
As is well known, these materials offer great
flexibility to the specifier and user since they can be
applied as Preformed shapes or installed in-situ- by
Pouring or by spray.
47
NEW GENERATION SHIPLAP PIPE SECTION
WITH ALUMINIUM FOIL LAMINATION
POLYURETHANE / POLYISOCYANURATE FOAM
48
ROCKLOYD PIPE SECTIONS
NON-COMBUSTIBLE, WATER REPELLANT GRADE INSULATION
Aluminium foil lamination
To protect corrosion under Insulation (CUI)
49
PIPELINE IN TRENCHES
30-50mm Polyurethane Foam Cast-in-Situ application
40-45 kg/m3 with 4-5mm HDPE cladding
50
PIPELINE IN TRENCHES
PIPE-IN-PIPE PRE-FAB INSULATION
51
COLD INSULATION THICKNESS VS. HEAT LOSS
DESIGN DATA
AT : 40 deg.C
Operating : 5 deg.C
Windage : 0 m/s
RH : 85%
Materials : PUF, RW, EPS
Method : IS : 14164 & ASTM C-680
52
COLD INSULATION THICKNESS VS. HEAT LOSS
PUF RW EPS
Thick. (mm) /
Heat Loss
(Kcal/m2 hr.)
Thick. (mm) /
Heat Loss
(Kcal/m2 hr.)
Thick. (mm) /
Heat Loss
(Kcal/m2 hr.)
LI / IS : 14164 60/8 80/9 90/10
ASTM C-680 70/6 95/7 105/8
53
THICKNESS OF DIFFERENT INSULATION MATERIALS FOR
CHILLED WATER PIPELINES
DESIGN CRITERIA (CHILLED WATER P/L)
1.Ambient Temperature : 45 Deg.C
2.Max. Allowable surface temp. : 42.22 Deg. C.
3.Windage : 0 m/s.
4.Emissivity of cladding : 0.2 (Al.)
5.Relative humidity : 85 %
6.Calculation Procedure : ASTM C-680
54
Insulation
Materials
Pipe
Dia.
(mm)
Operating Temperature (Deg. C)
-5 -10 -15 -20 -25 +5 +10 +15 +20 +25
Rockwool Pipe
Section
(150kg/m3)
25 80 85 90 100 100 65 60 50 45 35
50 90 100 105 115 115 80 75 65 55 45
80 105 110 120 125 135 85 75 75 60 50
100 110 115 125 135 145 90 80 75 65 55
150 125 130 140 150 160 100 90 85 70 60
Polyurethane pipe
section (36+2
kg/m3)
25 65 70 75 80 85 55 50 45 40 35
50 80 85 90 95 100 70 60 55 45 40
80 80 85 90 95 100 70 60 55 50 40
100 95 105 110 115 120 80 70 65 55 45
150 105 115 120 125 135 90 80 70 60 50
55
Insulation
Materials
Pipe
Dia.
(mm)
Operating Temperature (Deg. C)
-5 -10 -15 -20 -25 +5 +10 +15 +20 +25
Expanded
Polystyrene (18
kg/ m3)
25 85 95 100 105 110 75 65 55 45 45
50 105 110 120 130 135 85 75 65 55 55
80 115 125 135 145 150 100 85 75 65 60
100 125 135 145 155 160 110 90 80 65 65
150 135 150 160 165 175 115 100 85 75 70
56
There is a requirement to shift from EPS to PUF for
Cold Insulation and Rockwool for specific areas for
Energy Saving.
Insulation Finishes
The outer cover over insulation..
Weather Barriers/ claddings- These all have one
basic function - to protect insulation from the
known hazards like external media, mechanical
abuse etc.
External coverings are what we get to seeing in a
completed plant or pipeline. Aesthetics becomes a
secondary, but significant role assigned to this
provision.
Insulation Finishes
Outer Cladding Systems for
Insulation
Metallic Cladding Materials
Aluminium or Galvanised Steel Bare or Colour coated.
Zincalume or Aluminised Steels
Stainless Steel
Other cladding systems
Cementaceous plasters
Liquid applied reinforced Coatings
HDPE and PVC sheets / sleeves
Metal Cladding- some important issues..
As can be easily appreciated, all metal cladding materials need
careful selection from external corrosion point of view as a first
consideration.
However, another important aspect concerns corrosion from
within- contributed by condensation of vapours from the
insulation system on the inner surface.
Since most insulants are faintly alkaline, such condensed water
attacks the metal particularly Aluminium and causes it to pit
and fail as a barrier.
All metal cladding, as a rule need protection on the inner
surface- like a factory laminated Poly Surlyn treatment.
Cladding Materials
Metal Claddings with Moisture Barrier
PolySurlyn
Polyethylene
Surlyn
Polyethylene
Metal
Corrosion
Pits
62
COLOUR COATED GI SHEET CLADDING
0.5mm TCT & 240 MPa as per IS : 277 & 513
For Mechanical strength & lower thickness
Vapour Barrier in cold service
Installed on the high vapour pressure side-I.e., the
warmer side of the insulation systemprior to
cladding), Vapour Barrier (or Vapour retarder as it is
referred sometimes) is designed to arrest entry of
moist vapour into the insulation, causing it to soak
and possibly to freezing.
Insulating Material, when wet can be 30 times more
conductive and would no longer be an insulant!
Freezing of water is always accompanied by
volumetric expansion resulting in rupture.
In cold insulation system, therefore, the
soundness of the VB virtually determines how
good the insulation system is.
Vapour Barrier in cold service
Weather cum Vapour Barrier
There are a set of materials, which serve both as a
weather barrier and vapour retarder at the same
time.
These are mostly in the form of Mastics- trowelled
or brush applied- which set to becoming a tough
outer skin.
Aluminium foil laminated insulation pipesections.
APPLICATION SPECIFICATIONS FOR
COLD PIPELINES
1. Cleaning the surface thoroughly to ensure that the
surface is free of all dust, rust and grease.
2. Providing and applying a coat of bitumen primer
followed with a coat of bitumen (85/25 grade) or
cold adhesive compound like CPRX or MAS-83 used
as adhesive compound.
3. Providing / Fixing the recommended insulation
thickness of Expanded Polystyrene Pipesection of
suitable density and sealing up all the joints with hot
Bitumen (85/25 grade) or cold adhesive.
4. Providing and applying two coats of insulkote @2.5
kg/m2 for each coat sandwiched with glass fibre
cloth between the coats as vapour barrier.
5. Providing and fixing Aluminium sheet cladding screw
at 150mm distance at the sheet joints making an
overlap of minimum 30mm. Sealing all the joints
with mastic MAS-94.
OR
using aluminium foil laminated prefab shiplap joint
Polyurethane pipe sections and sealing the joints
with 75mm wide aluminium tape.
APPLICATION SPECIFICATIONS FOR
COLD PIPELINES
COLD INSULATION SEQUENCE OF APPLICATION
Insulation Pipe supports
Todays plants need a wide expanse of
extremely low temperature piping.
Unless supports are highly insulating, the
exposed surfaces would attract condensation
and very heavy corrosion at these important
bearing points- with corroded load bearing
points and avoidable unsafe slippery floors
underneath.
SUPERTHERM Pipe supports
These are made from Highest efficiency insulants
i.e., Urethanes, made to high density to afford an
Engineered load bearing capacity.
These are made in all the possible shapes and with
specific features- for sliding, guide and anchor
duties.
Support design and selection are very vital design
inputs for the Process Piping Engineeer / designer.
71
Small diameter pipeline or DG exhaust insulation
with Supercera Ceramic Fibre Rope
72
EHT & INSULATION OF PIPELINE
(SINGLE LAYER)
REFERENCE
ITEM
DESCRIPTION
1 PIPE
2 SLSR ELECTRIC HEAT
TRACER
3 AL./GLASS ADHESIVE TAPE
4 ROCKWOOL MATTRESS
5 G.I. WIRE
6 AL. SHEET (22 SWG)
7 S.T. SCREWS
8 AL. BAND
73
SUPERCERA B BLOCKS
Supercera B Blocks are special shaped blocks of
density 110, 220, 250 kg/m3, dimension 450 x 550 mm,
thickness 80/58mm, having one side circular corrugation
shaped, suitable for direct fixing on to the boiler tubes.
74
SUPERCERA B BLOCKS
75
BASIC INSULATION FUNCTION
AND REQUIREMENTS FOR
APPLICATION BETWEEN
-80
0
C TO 750
0
C
AS PER IS : 14164
(Code of Practice for Industrial
application and finishing of
Thermal Insulation Materials)
76
METHODS OF APPLICATION
All insulation materials applied, shall be in close contact
with the surface to which they are applied, with the
ends butted to one another.
b) Proper density and thickness of material to be applied.
77
MULTI LAYER INSULATION
All joints to be staggered and each layer shall be
separately secured.
All fittings shall be insulated separately and should be
taken out easily without disturbing the main
insulation.
78
For pipelines operating above 500
0
C combination of
Ceramic Fibre & Rockwool can be used for reducing
heat loss, taking advantage of lower K-value of Ceramic
Fibre at higher temperature.
79
APPLICATION SYSTEM
All pipes (upto 14) should preferably be insulated with
pipe section. The pipe sections shall be held with pins
or wires at a spacing of not more than 450mm.
When multiple layer to be used, the 2nd layer should be
with mattress and tightly held with wires.
For vertical and near vertical piping metal rings to
be used over pipes to stop downward displacement of
insulation.
80
APPLICATION SYSTEM
81
Pins should be inserted with mitred segment of mattress.
All flanges, valves and other fitting on hot and cold piping
shall be insulated separately and preferably should be of
removable type.
82
83
All stainless steel surfaces shall be applied with a layer
of aluminium foil or sodium silicate before
application of insulation to avoid corrosion.
INHIBITED ROCKWOOL & CERAMIC WOOL
All insulation supports shall be properly insulated.
All joints between aluminium sheet & insulation shall be
sealed with a suitable mastic compound.
CERAMIC PAPER TO REPLACE ASBESTOS MILL
BOARDS FOR CONDUCTION INSULATION
84
Insulation Systems for Tanks
. Prefab Panels
PRE-FAB TANK INSULATION SYSTEM
Lloyd Standing Seam 2000 Panels
The panels are fixed by a concealed metal clips fastening
system held between flanges of panels which are mechanically
seamed together to result in a robust and water-tight seam.
A seaming tool forms the adjacent panels into a vertical seam
that includes the clip.
Clips are fastened to Insulation Support Rings with vertical
spacing of 2000 mm and horizontal spacing of 450 mm
Clips have provision to accommodate thermal expansion and
contraction

The clip cross section is chosen as per wind load requirements.


THERMASEAM PRE-INSULATED PANEL
THERMASEAM Pre-insulated Panels are accepted &
established superior product for Thermal Insulation and
condensate prevention on tanks.
On installation, they make
an unique tank insulation
system due to the design,
robustness & ease of
application.
THERMASEAM PRE-INSULATED PANEL
THERMASEAM Pre-insulated has a galvanized, galvalume (colours
optional) or aluminium outer sheet lined with Thermal Insulation
(Rockwool / Polyurethane Foam / Polyisocyanurate Foam) on inner
side.
These panels are
installed vertically to
the full height of
tank side walls and
are also utilized on
the tank roof.
THERMASEAM PRE-INSULATED PANEL
Protusions from the tanks, such as manways, nozzles
& stair brackets can be fitted and sealed tightly with
proper flashing & silicon sealants.
PANEL CONSTRUCTION
Tank Shell
Anchor Cable
Retaining Clips
Rockloyd Insulation of Rockwool
Slab
Metal sheet machine Formed,
Double - Locking Standing
Seam in panel
COMPONENTS
Standing Seam Insulated Panel Retaining Pin
Rockloyd
Mattress
Rockloyd
Slab
Turnbuckles
Lloyd Standing Seam Profile Manufacturing
PANEL CONSTRUCTION
SPRAYING ADHESIVE ON THE PANEL AS WELL AS
INSULATION
PANEL CONSTRUCTION
PRESSING THE
INSULATION FOR
BETTER ADHESION
LAYING OF INSULATION
OVER THE SHEET
PANEL CONSTRUCTION
STACKING OF INSULATED PANELS
ADVANTAGES OF THERMASEAM PRE-
INSULATED PANELS
Extremely durable
Maintenance free
Aesthetically pleasing
Cost effective
Normally no need for Scaffolding
Screw less fixing of panels, no fear of corrosion.
No horizontal bands
ADVANTAGES OF THERMASEAM PRE-
INSULATED PANELS
Assured weatherproof barrier due to machine formed
double locking Standing Seam joint between adjacent
panels
Single panel is replaceable, if damaged
Continuous 360 deg. interlocking seams provide rigidity.
FIXING DETAIL OF INSULATED PANEL ON
TANKS
FIXING DETAIL OF INSULATED PANEL ON
TANKS
PRE-FAB COLD ROOMS
PRE-FAB COLD ROOMS
CONSTRUCTION DETAILS
PRE-FAB COLD ROOMS
LLOYD INSULATIONS IS AN APPROVED
WE TAKE UP PLANT & BUILDING AUDIT
107