Power Requirement for KPS II Well, Booster and Filtration System

Well
1 - 15 HP Submersible Pump Motor
Multi-Media Filtration
1 - 8.4 HP Feed Pump Motor
1 - 10 HP Backflush Motor
1 - 1 HP Air Compressor
Booster for Filtration
2 - 10 HP Booster Pump for product water
Maximum HP Requirement during filtration cycle:
43.4
= 43.4 HP
Maximum HP Requirement during backflush cycle:
11
= 11 HP
Total Effective KVA Required: 52.08
Smallest KVA Rating Each Transformer = 17.36
Existing Transformer KVA Rating: 3-25 KVA
Power Requirement for Melencio Well, Booster and Filtration System
Well
1 - 15 HP Submersible Pump Motor
Multi-Media Filtration
1 - 8.4 HP Feed Pump Motor
1 - 10 HP Backflush Motor
1 - 1 HP Air Compressor
Booster for Filtration
2 - 10 HP Booster Pump for product water
Maximum HP Requirement during filtration cycle:
43.4
= 43.4 HP
Maximum HP Requirement during backflush cycle:
11
= 11 HP
Total Effective KVA Required: 52.08
Smallest KVA Rating Each Transformer = 17.36
Existing Transformer KVA Rating: 3-25 KVA
MEMBRANE FILTRATION - DUAL SYSTEM
NO. WELL
LOCATION Before Filtration After Filtration
1 Aduas with with
2 Bitas none with
3 Del Pilar with with
4 Kapitan Pepe none with
5 Mayapyap 1 with none
Mayapyap 2 with none
6 Melencio none with
7 Sumacab 1 & 2 one meter none
8 Valdefuente with with
Note: Well number 4-8 can be installed with dual 16 LPS Ultra Filtration with the assumption
that the available land area can accommodate the 2nd Filtration system.
PRODUCTION METER
NO. WELL Q PWL DEPTH CASING
LOCATION 1ST 2ND 3RD
1 Aduas 86.40 39.14 42-45 53-56 61-64 71 250
2 Bitas 64.80 40.06 40-43 60-66 - 71 250
3 Del Pilar 69.48 44.81 42-45 52-61 - 71 250
4 Kapitan Pepe 109.00 15.83 40-43 48-54 59-62 71 250
5 Mayapyap 109.00 16.43 48-57 63-66 - 71 250
6 Melencio 107.50 22.50 45-54 61-64 - 71 250
7 Sumacab 133.50 24.10 44-62 - - 71 300
8 Valdefuente 118.80 13.65 42-45 50-56 - 65 250
Note: Well number 4-8 can be installed with dual 16 LPS Ultra Filtration with the assumption
that the available land area can accommodate the 2nd Filtration system.
SCREENS
WELL DATA
MEMBRANE FILTRATION - DUAL SYSTEM
WATER TANK DIMENSION
Feed (Raw Water) Tank = 14,000 liters
Product (Backwash) Tank = 4,500 liters
Supply (Product Water) Tank = 34,000 liters