Nominal Airflow: 2350 l/s

IMD 550
Cooling Capacity (kW)

Total = Total Capacity (kW); Sens. = Sensible Capacity (kW)


Note: Cooling capacities are based on the nominal airflow.

Entering Air Temperature 23C D.B., 17C W.B.


WATER
FLOW
(l/s)

COIL

PRESSURE
DROP
(kPa)

0.40
0.70
1.00
2.00
3.00
4.00

1 ROW

4 ROWS

ENTERING WATER TEMPERATURE C


6
7
8

6.6
17.6
32.8
9.5
20.6
33.4

Total

Sens.

Total

Sens.

Total

Sens.

Total

Sens.

Total

Sens.

12.5
16.3
19.0
43.9
49.9
53.2

10.9
12.3
13.4
31.9
34.5
36.0

11.6
15.1
17.8
40.5
46.1
49.5

10.6
11.9
12.9
30.5
32.9
34.3

10.7
14.0
16.2
37.2
42.3
45.2

10.3
11.5
12.3
29.1
31.2
32.5

9.9
12.8
14.9
33.8
38.5
41.4

9.9
11.0
11.8
27.7
29.6
30.8

9.2
11.6
13.4
30.5
34.6
37.0

9.2
10.6
11.3
26.4
28.0
29.0

Heating Capacity (kW)


Entering Air Temperature 21C

Note: Heating capacities are total - based on the nominal airflow. Electric Heating option: 18 kW

COIL

0.40
0.80
1.20

1 ROW

ENTERING WATER TEMPERATURE C

PRESSURE
DROP
(kPa)

WATER
FLOW
(l/s)

4.5
15.4
31.5

40

45

50

55

60

65

70

75

80

14.7
17.9
19.6

18.6
22.5
24.8

22.5
27.2
30.0

26.3
31.9
35.2

30.1
36.6
40.2

34.0
41.3
45.4

37.9
46.0
50.6

41.7
50.7
55.8

45.6
55.4
60.9

Air Handling

Sound Levels
- - - - l/s - W

l/s - Pa

INPUT (kW)

3.0
2.5
HIGH
2.0

AVAILABLE EXTERNAL PRESSURE (Pa)

MED

Test Conditions: JIS 8616. 1 m ducting with 25 mm insulation.


Sound Pressure Levels are at 1 m from source.
OCTAVE BAND FREQ. Hz
FAN
SPEED

SPL
dB(A)

SWL
dB(A)

125

LOW
MED
HIGH

50
55
59

60
65
69

61
65
69

1.5

LOW

1.0
0.5

250

500

1k

2k

4k

SOUND POWER LEVELS dB


62
66
71

60
64
69

54
58
63

47
52
57

45
50
55

600
7.2A
400

5.6A
HIGH

4.6A
LOW
0
1300

Note:
1. Air flows given are for a unit with no filter installed.
2. In a free blow application, beware of exceeding
indoor fan motor's full load amp limit.

11 A

200

MED
8A

6A
1700
1900
1500
AIR FLOW (l/s)

2300
2100
2.5 m/s Face Velocity

Dimensions (mm)

OPTIONAL
FILTER BOX WITH
FILTER ACCESS
EACH SIDE

1573
MOUNTING CENTRES

Not to Scale

1430
125

Note: Allow 500 mm


minimum clearance
to each access panel

WATER CONNECTIONS:
32 BSP MALE
(HEATING 32 BSP MALE)

600
MOUNTING
STRAP
CENTRES

688
OPTIONAL
SPRING MTG
CENTRES

FAN ACCESS VIA


REMOVEABLE BASE
& DRAIN TRAY,
OR VIA TOP PANEL

325

1030
ELECTRICAL
ACCESS PANEL
ELECTRICAL
CONDUIT HOLES

ACCESS
PANEL

65

150
65

35
65
310

700
OVERALL

555
355
80
DRAIN 28 OD
1680
OVERALL

temperzone limited 2002

735 OA

31