External Static Pressure Calculation: Hvac 6/27 M.M 4 June 2014 MA/CAL/6

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

MechaTronics Co.

External static pressure Calculation

Qty.(2)

AHU-B6_R03 & AHU-B6_R04


Al-Hazm Mall

HVAC

Project

Designed by

Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

B
FT.

DIA.

FT.

FT.

15.0

6/27

Sheet
Circ:

FITTINGS
Br
R
FT.

of

27

MA/CAL/6

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

fpm

IN W.G.

IN W.G.

5.0

20.0

39.7

1882

0.07

0.027

AC SUPPLY DUCT
1

28,500

1650

900

1317

6.0

19.7

14,250

1300

700

1031

7.0

23.0

14,250

1300

700

1031

3.0

9.8

15.0

14,250

1300

700

1031

7.8

25.6

30.0

7,125

900

500

725.6

5.0

16.4

3,576

500

500

546.6

5.0

16.4

5.0

30.0

15

5.0

50.0

73.0

1537

0.06

0.046

30.0

15

5.0

65.0

74.8

1537

0.06

0.047

5.0

35.0

60.6

1537

0.06

0.038

10.0

10.0

26.4

1551

0.10

0.026

5.0

21.4

1372

0.11

0.024

AC SUPPLY DUCTS & FITTINGS

0.208

AC RETURN DUCT
6

28,500

1650

900

1317

10.2

33.5

15.0

14,250

1300

700

1031

10.0

32.8

30.0

30.0
15.0

5.0

50.0

83.5

1882

0.07

0.057

10.0

55.0

87.8

1537

0.06

0.056

AC RETURN DUCTS & FITTINGS

0.112

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.208

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 5 )

0.625

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.300

R = Reducer Equivalenght Length

5 Ft.

AC RETURN DUCTS & FITTINGS

0.112

RETURN AIR DIFFUSER

0.150

SUB-TOTAL

1.396

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.140
1.535