MechaTronics Co.

External static pressure Calculation


AHU-LB_01 HVAC
Project Al-Hazm Mall Project No. Sheet 8/27 of 27
Designed by M.M Date 4 June 2014 Circ: MA/CAL/8 /File
TOTAL AIR FRICTION FRICTION
E B Br R EQUIV. EQUIV. VELOCITY DROP/100 FT DROP
W H DIA. M FT. FT. FT. FT. FT. LGTH. (FT.) LGTH. (FT.) fpm IN W.G. IN W.G.
AC SUPPLY DUCT
1 3,200 450 400 463.6 2.0 6.6 15.0 10.0 25.0 31.6 1706 0.20 0.064
AC SUPPLY DUCTS & FITTINGS 0.064
AC RETURN DUCT
1 3,200 450 400 463.6 2.0 6.6 15.0 15.0 10.0 40.0 46.6 1706 0.20 0.094
AC RETURN DUCTS & FITTINGS 0.094
Abbreviations:
E = Elbow Equivalenght Length 15 Ft. AC SUPPLY DUCTS & FITTINGS 0.064
B = Branch Equivalenght Length 30 Ft. VOLUME DAMPER ( x 3 ) 0.375
Br = Branch Run Equivalenght Length 15 Ft. SUPPLY AIR DIFFUSER 0.150
R = Reducer Equivalenght Length 5 Ft. AC RETURN DUCTS & FITTINGS 0.094
RETURN AIR GRILLE 0.150
SUB-TOTAL 0.833
ADD 10% 0.083
SECTION CFM
DUCT FITTINGS
SIZE (MM) LENGTH
prepared by/ Engr.Mohamed Mosaad
TOTAL FRICTION DROP IN WG 0.917