Visio Loop Diagram Cascade Loop2

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

RD

BK
RD
BK
FT
69
FE
69
FCV
69
AS 20 PSIG
TB
41
RD
BK
TB
80
RD
BK
RD
BK
TB
80
RD
BK
RD
BK
+24.5 VDC
+24.5 VDC
RACK: 01
CARD: 03
SLOT:
CHANNEL: 07
FIELD PROCESS AREA BUILDING XX DCS I/O CABINET DCS-01 DCS
PAGE
1 OF 1
Tag No. Description Manufacturer Model No. Spec. No. Calibration Install Detail Location Dwg. Purch. Order P&ID
FY-69
FE-69
FCV-69
FT-69
I/P Transducer
Integral Orifice Plate
Pneumatic Diaphragm Control Valve
Differential Pressure Transmitter
Fisher
Foxburo
Badger
Rosemount
x
x
x
3051
x
FRESH FEED FLOW CONTROL TO UNIT 3
LOOP DIAGRAM
RACK: 01
CARD: 01
SLOT:
CHANNEL: 08
Analog output
Analoginput
PT-69
PY-69
TB
82
TB
81
1002GBN
TB
41
FY
69
19
20
+
-
89
90
17
18
9
10
27
28
87
88
+
-
HI
LO
+
-
J B
10
RB
BL
BK
BN
J B
10
3
4
1
2
TB
40
OR
GN
YL
WT
TB
40
73
74
71
72
J B-1
TB
91
TB
91
DCS01-J B1 C
DCS01-J B1 C J B1-J B10 A
J B1-J B10 A
+
-
546
4-20 mA, 3-15 PSI
0-3.3 GPM, 4-20 mA
3-15 PSI
ATO
IFO
FIC
69
RD
BK
LT
36
TB
41
RD
BK
TB
80
RD
BK
TB
80
RD
BK
+24.5 VDC
RACK: 01
CARD: 01
SLOT:
CHANNEL: 07
Analog input
LT B-Y 36
57
58
11
12
75
76
+
-
+
-
J B
5
RD
BL
1
2
TB
40
RD
BL
59
60
TB
92
DCS01-J B1 B J B1-J B5
FIC
36
LT-36 Level Transmitter Rosemount 3051
0-10" WC, 4-20 mA

You might also like