The document is a test report for a current transformer from Voltech Engineers Pvt. Ltd. for their client Rukmani Power and Steel Ltd. It details the inspection and testing of a Schneider Electric current transformer with a 50:1 ratio including insulation resistance measurements, secondary winding resistance measurement, polarity and ratio tests. All tests were witnessed and the current transformer was found to be in working order with correct polarity and ratios within specified limits.
The document is a test report for a current transformer from Voltech Engineers Pvt. Ltd. for their client Rukmani Power and Steel Ltd. It details the inspection and testing of a Schneider Electric current transformer with a 50:1 ratio including insulation resistance measurements, secondary winding resistance measurement, polarity and ratio tests. All tests were witnessed and the current transformer was found to be in working order with correct polarity and ratios within specified limits.
The document is a test report for a current transformer from Voltech Engineers Pvt. Ltd. for their client Rukmani Power and Steel Ltd. It details the inspection and testing of a Schneider Electric current transformer with a 50:1 ratio including insulation resistance measurements, secondary winding resistance measurement, polarity and ratio tests. All tests were witnessed and the current transformer was found to be in working order with correct polarity and ratios within specified limits.
TRANSFORMER CLIENT : M/S .RUKMANI POWER AND STEEL LTD DATE :25.09.2013 PROJECT : 10MW POWER PLANT AT KHARSIA Sheet No.: 1 of 2
Test Performed by: VEPL Witnessed by: RPSL Witnessed by: RPSL Name : Mr. T.Balaji Name :Mr.K.K.Banerjee Name :Mr.O.P.Sahu Designation : Senior commissioning Engineer Designation : Manager Electrical Designation :Manager E&I Signature & Date Signature & Date Signature & Date
1. Equipment Details
Make : Schneider Electric Sl. No. : 12/023936 Ratio : 50/1A VA : 15 Class : 5P10 Terminal : 1S1-1S2 Mfg year : 2012
2. Feeder Name : Generator Neutral Side
3. Location : NGR Panel
4. General Inspection : Ok
5. Insulation Resistance Measurement: ( Using 500V Megger )
TERMINALS Values Neutral CT Primary Earth 601 M Primary Secondary 571 M Secondary Earth 221 M
6. Secondary Winding Resistance: Temperature: 29C
VOLTECH ENGINEERS PVT. LTD. TEST REPORT FOR CURRENT TRANSFORMER CLIENT : M/S .RUKMANI POWER AND STEEL LTD DATE :25.09.2013 PROJECT : 10MW POWER PLANT AT KHARSIA Sheet No.: 2 of 2
Test Performed by: VEPL Witnessed by: RPSL Witnessed by: RPSL Name : Mr. T.Balaji Name :Mr.K.K.Banerjee Name :Mr.O.P.Sahu Designation : Senior commissioning Engineer Designation : Manager Electrical Designation :Manager E&I Signature & Date Signature & Date Signature & Date
Core Between Terminal Values Core 1 1S1-1S2 1.68
7. Polarity Test: (By connecting positive battery terminal P1 side and Negative battery terminal P2 side with 1.5V DC supply) Core Between Terminal Values Core 1 1S1-1S2 OK
8. Ratio Test:
9. Remarks: CT check found OK
Primary Applied Current (A) Measured Secondary Current in (A) 20 0.203 40 0.391 60 0.693 80 0.804