Please find the following cable details as required in trailing mail:

i) LT CABLE DETAILS FOR (FOR MOTOR SPACE HEATERS) 107-J & 108-J :

Voltage Grade 1.1 KV
Suitable For Earthed / Unearthed System Earthed System
No. of Cores & Size of Conductor 3 x 4 Sq. mm
No. of Runs per phase For Space heater 1 RUN
CONSTRUCTIONAL DETAILS
CONDUCTOR
Material Plain Annealed Copper
Construction Stranded Circular
INSULATION
Material XLPE as per IS-7098 (Pt-1)
Thickness (mm) 0.7
INNER
SHEATH
Type & Material Extruded PVC Type ST2
Thickness (mm) 0.3
ARMOURING
Type & Material Round wire / Galvanized Steel
Dia. of Wire / Strip Thickness (mm) 1.4
OUTER
SHEATH
Material Extruded PVC Type ST2
Thickness (mm) 1.24 (min.)
ELECTRICAL DATA
CONTINUOUS CURRENT (A) Ground At 30 C 43
RATING WHEN LAID IN (A) Air At 40 C 37
CONDUCTOR TEMP.
Continuous 90 deg. C
Short Time 250 deg. C
MECHANICAL DATA
Overall DIAMETER WITH TOLERANCE (mm) 15.5 2


ii) LT Cable details for 117-JM/JAM shall be provided shortly after receiving the same from the LT cable vendor.
However cable size & number of runs for the motors (117-JM/JAM) are 1R x 3C x 300 Sq. mm (Al), XLPE, FRLS
overall sheathed.