CTY TNHH MTV CN CHUNG TN

Service Department

70,ng ch Khim,P14,Q11,H Ch Minh,Vit Nam


Tel; 0963 132 983
Fax: 38617442

Voltage Transformer Test Report

Customer: INTEL
Address: SHTP ,Dist 9 ,Ho Chi Minh City
Substation: ATM CENTER- (HTB)

Object/panel: BB03

Manufacturer:

SCHNEIDER

Serial:

0840076 - 0840077- 084008

Type:

VRS2Bn/S1

Specification:

22 0.11
/

KV
3
3

INSULATION MEGGER TEST :


Subject

Test voltage (kV)

Phase A

- 100VA

Test set used : KYORITSU3121


Result (M)

2.5

Pri. - Housing
N/A

Sec.1 - Housing
N/A

Sec.2 - Housing
N/A

Phase B

2.5

N/A

N/A

N/A

Phase C

2.5

N/A

N/A

N/A

WINDING RESISTANCE TEST:

Status

Test set used : FLUKE 87V


Status
Secondary winding
02 in Ohm
N/A
OK

Phase of test

Primary winding
in Ohm

Secondary winding
01 in Ohm

L1

N/A

0.5

L2

N/A

0.5

N/A

OK

L3

N/A

0.4

N/A

OK

REMARKS :

Done By:

DUONG VAN DONG

Date:

Witnessed By:

NGUYEN THUAN HOA

Date:

Voltage Transformer Test Report

10 DEC 2011

Page 1 of 1