Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Technical Data and Standards SF

6
-Gas Insulated Switchgear
GIS

WBSETCL
132 kV GIS
Salt Lake


ABB AG - High Voltage Products ABB


Technical data (Rated Values)

Switchgear
- Busbar system DSS
- Designation of phases L1-L2-L3
- Voltage 145 kV
- Lightning impulse withstand voltage, 1.2/50 s 650 kV
- Power frequency withstand voltage, 1 min 275 kV
- Frequency 50 Hz
- Short time withstand current, 3 s 40 kA
- Peak withstand current 100 kA
- Current, Busbar 2000 A
- Current, Bays 1250 A
Auxiliary voltages
- Control (+10 % -15 %) 220 DC V
- Alarm (+10 % -15 %) 220 DC V
- Motor (+10 % -15 %) 220 DC V
- AC-supply (+10 % -15 %) 240 AC V

Circuit breaker
- Short circuit breaking current 40 kA
- Making current 100 kA
- First pole to clear factor 1.5
- Operation sequence O-0,3s-CO-3min-CO
- Filling gas pressure at 20C 700 kPa
abs

- Gas pressure at 20C 600 kPa
abs




Technical Data and Standards SF
6
-Gas Insulated Switchgear
GIS

WBSETCL
132 kV GIS
Salt Lake


ABB AG - High Voltage Products ABB


Painting
- Indoor, incl. CB-drive mechanism RAL 7038 / agate grey
- Outdoor, incl. CB-drive mechanism
- Barrier insulators RAL 2004 / pure orange
- Drive covers (others) RAL 7038 / agate grey
- Steel Structures hot dip galvanized, unpainted



Technical Data and Standards SF
6
-Gas Insulated Switchgear
GIS

WBSETCL
132 kV GIS
Salt Lake


ABB AG - High Voltage Products ABB


Standards

Our GIS is exclusively designed, manufactured and tested according to the
following standards:
Gas Insulated Switchgear IEC 62271-203
Circuit Breaker IEC 62271-100
Disconnector/Earthing switch IEC 62271-102
Current Transformer IEC 60044-1
Voltage Transformer IEC 60044-2
HV - Cable Connection IEC 62271
Air Bushings IEC 60137
SF6-Gas IEC 60376 / 60480
Tests IEC 60060
Pressure vessel EN 50052 / EN 50064

You might also like