Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

MechaTronics Co.

External static pressure Calculation


AHU-UB_16 MP
Project Al-Hazm Mall Project No. Sheet 23/27 of 27
Designed by M.M Date 4 June 2014 Circ: MA/CAL/23 /File
TOTAL AIR FRICTION FRICTION
E B Br R EQUIV. EQUIV. VELOCITY DROP/100 FT DROP
W H DIA. M FT. FT. FT. FT. FT. LGTH. (FT.) LGTH. (FT.) Fpm IN W.G. IN W.G.
AC SUPPLY DUCT
1 2,400 600 450 566.6 2.8 9.0 30.0 10.0 40.0 49.0 857 0.05 0.022
AC SUPPLY DUCTS & FITTINGS 0.022
AC FRESH AIR DUCT
6 200 350 350 382.6 1.0 3.3 0.0 3.3 157 0.00 0.000
AC FRESH DUCTS & FITTINGS 0.000
Abbreviations:
E = Elbow Equivalenght Length 15 Ft. AC SUPPLY DUCTS & FITTINGS 0.022
B = Branch Equivalenght Length 30 Ft. VOLUME DAMPER ( x 3 ) 0.375
Br = Branch Run Equivalenght Length 15 Ft. SUPPLY AIR DIFFUSER 0.150
R = Reducer Equivalenght Length 5 Ft. AC FRESH DUCTS & FITTINGS 0.000
FRESH AIR GRILLE 0.150
SOUND ATTENUATOR 0.250
SUB-TOTAL 0.947
SECTION CFM
DUCT FITTINGS
SIZE (MM) LENGTH
prepared by/ Engr.Mohamed Mosaad
ADD 10% 0.095
TOTAL FRICTION DROP IN WG 1.042