TECHNICAL SPECIFICATION FOR CURRENT TRANSFORMERS

1.0 GENERAL
1.1 This specification covers manufacture, test, & supply of LT Current transformers
of class 0.5 accuracy.
1.2 The CTs shall be suitable for metering purpose.
2.0 TYPE:
2.1 The CTs shall be of ring type or winow type !bar type or bus"bar type CT#s shall
not be accepte$.
2.2 The seconary leas shall be terminate with Tinne Cooper rose contact
terminals with arrangements for sealing purposes.
2.% &olarity !both for primary an secon leas$ shall be mar'e.
2.( The CTs shall be varnishe, fiberglass tape insulate or cast resin, air"coole type.
)nly super enamele electrolytic grae copper wires shall be use.
2.5 The CTs shall conform to *+ 2,05-&art"* & **.*/C-105 with latest amenments.
3.0 TECHNICAL DETAILS:
%.1 Technical etails shall be as given below-
1. Class of 1ccuracy 0.5
2. 2ate 3uren 5.00 41
%. &ower 5re6uency 7ithstan 4oltage %84
(. 9ighest +ystem 4oltage (%% 4
5. :ominal +ystem 4oltage (00 4
;. 5re6uency 50 9<
,. +upply +ystem % &h. +olily groune :eutral +ystem

%.2 Transformation ratio shall be specifie from the following stanar ratings as per
re6uirement -
2atio 50/5 150/5 300/5 400/5 1000/5
!+econary with 1 1 may be specifie by the utility incase the same is esire.$
%.% 3ore iameter of the CT shall not be less than (0 mm. 2ing type CTs shall have
suitable clamp to fi= the CT to panel 3oar, wherever re6uire.
%.( The limits of current error an phase angle isplacement as per *+-2,05 at several
efine percentage of rate current are-
1ccuracy > 2atio error at > of rate &hase isplacement in minutes at >
Class current of rate current
5 20 100 120 5 20 100 120
0.5 1.5 0.,5 0.5 0.5 ?0 (5 %0 %0
:ote - Current error an phase isplacement at rate fre6uency is re6uire to be as
above when the seconary buren from 25> to 100> of the rate buren i.e. 50 4 1.
%.5 2ate e=tene primary current shall be 120> of rate primary Current in
accorance with *+-2,05 &t"**.
%.; 2ate *+5 !*nstrument +ecurity 5actor$ shall be eclare by the manufacturer &
mar'e on the CT.
%., CT#s shall be mae with goo engineering practices. Core wining shall evenly
sprea stress & avoi stress concentration at any one point. Cast resin CT#s sha@@
be processe by hot curing metho uner controlle vacuum conitions.
%.0 The base shall be of hot ip galvanise steel.

4.0 TESTS:
4.1. TYPE TESTS:
(.1.1 Copies of all type tests as per *+.2,05 &art"* an ** incluing short time current
& temperature rise tests in :13L accreite laboratory shall be submitte an got
approve before commencement of supply.
4.2 ROUTINE TESTS:
(.2.1 The supplier shall conuct all the routine tests such as 2atio test, phase angle
error test for 0.5 accuracy class as per *+ 2,05 &art * & **.
4.3 COMMISSIONING TEST :
(.%.1 *n accorance with *+-2,05, &ower fre6uency test on primary wining shall be
carrie out after erection on site on sample basis.
5.0 MARKING -
5.1 The CTs shall have mar'ing an nameplate as per *+ 2,05 in aition to class of
insulation & *+5. The mar'ings shall be inellible. The nameplate shall be
securely fi=e to the boy of the CT.
6.0 PACKING:
;.1 /ach CT shall be securely pac'e so as to withstan rough hanling uring transit
an storage.
7.0 UALITY ASSURANCE PLAN:
,.1 The re6uirements of clause 2?.0 of +ection A * of main specification for /nergy
Beters shall apply.
GUARANTEED TEHNICAL PARTICULARS FOR
CURRENT TRANSFORMERS
+.:o. C/+C2*&T*): 150.51
1. Ba'er#s :ame & aress
2. Type an capacity
%. 2ate voltage
a$ 9ighest system 4oltage
b$ 2ate &rimary Current
c$ 2ate +econary Current
e$ 2ate )utput
f$ 2ate continuous thermal current Temperature
rise over ambient
&ower 5re6uency 7ithstan4oltage

(. Class of 1ccuracy
5. Baterial
a$ Core
b$ Conuctor
c$ *nsulation
$ 3ase B+ Dinc plate
;. Cimension in mm
a$ *nner Cia. of CT
b$ )uter Cia. of CT
c$ 9eight of center of CT from base
,. +econary termination
0. *+5
?. /=tene primary current