Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 1

PERHITUNGAN KEBUTUHAN KAPASITOR

UNTUK PERBAIKAN FAKTOR DAYA

Q = 3410 kVAR

Diketahui :
S = 5500 kVA 3 Fasa
cos = 0.78 (non corrected)
cos = 0.9 (corrected)

cos = 0.78
sin = 0.62
tan = 0.8
38.73

Q = 2050
kVAR

P = 4290 kW

cos = 0.9
sin = 0.43
tan = 0.48

25.84
P = 4290 kW

Qc = Qnc - Qc
Qc = P.tan 1- P tan 2
Qc = P [tan 1 - tan 2]
Qc = 4290 [0.8 - 0.48]
Qc = 4290 [0.32]
Qc = 1372.8 Kvar

You might also like