Item no:
BO 001
Alarm and Control
Settings for
Composite Marine Boiler
Data Sheet:
A-177200-01
Water level settings
Top end of upper level glass 653 mm 100 %
High water level alarm 477 mm 73 %
Feed water pump stop 377 mm 58 %
Water level controller set point (normal water level) 327 mm 50 %
Feed water pump start 277 mm 42 %
Low water level alarm 227 mm 35 %
Low-low water level alarm and burner cut off 177 mm 27 %
Bottom end of lower level glass 0 mm 0 %
Steam pressure settings
Steam pressure transmitter maximum 16.0 bar
Steam pressure safety valves 8.5 bar
High steam pressure, burner cut-out and alarm 8.0 bar
Steam dump valve set point 7.3 bar
Working steam pressure (transmitter set point) 7.0 bar
Burner automatically stop 7.0 bar
Burner automatically start 6.0 bar
Low steam pressure alarm 4.5 bar
Fuel oil pressure settings for SKVJ burner
Fuel oil safety valve 7.0 bar
Fuel oil pressure control valve set point 5.0 bar
Start of stand-by fuel oil pump 2.0 bar
Fuel oil temperature settings for 380 cSt at 50 C
and SKVJ burner
High fuel oil temperature alarm 90 C
Fuel oil temperature control valve set point 80 C
Low fuel oil temperature alarm 70 C
Above data can be modified by SAACKE service engineer, according to
the actual situation and customer request during commissioning.