Power Supply Installation Standard

March, 2014

Power Supply Installation Standard

1. References
2. Equipment in Power cabinets
3. Cable layout
4. Power and Grounding cables
5. Fuses
6. Labeling
2
1. References
1.PowerOne Cabinet - ACU manual
2.TP 48200A ACU manual
3
4
2. Equipment in Power cabinets
- TP 48200A
3. Cable layout and connection
TP 48200 cabinet
DC power cables
AC power cables
5
4. Power and Grounding cables
AC power cables 5x6 mm
Grounding cable 35mm
Grounding cable 16mm
Inside Rack
6
5.Installation of power and grounding cables
Exterior of the clips

(1) Cable hole for feeders
(2) Cable hole for fiber optic cables
(3) Cable hole for power cables
Cables secured on a cable tray
Installation of grounding clip
7
Cables secured on a tower
5.Installation of power and grounding cables
8
Equipment Voltage
Power
Consumption
Fuse Current
BTS3900L -48V DC 2 x 63A
AC BTS3900A
(APM30H+RFC+IBBS)
3 phase, 220V AC 3 x 16A
Single phase, 220V AC 32A
DC BTS3900A -48V DC 2 x 63A
DC RRU -48V DC 320W 20A
AC RRU Single phase, 220V AC 320W 4A
5. Fuses
Use one fuse for each set of Batteries
9
10
6. Labeling
Use plastic tags to mark power cables near fuses.
Tag should be 2-8cm from fuse. Print on tab should
mark UNIT, unit number(#), Main or StdBy power
and pole.
Use paper tags to mark power cables near unit. Tag
should be 2-8cm from unit. Print on tab should mark
UNIT, unit number(#), Main or StdBy power and
pole.