Exothermic welding. Procedure that
provides long-lasting connections
by welding the conductors
autonomously, using graphite moulds.
This drawing does not pretend to represent real
applications but to show the different products
appearing in the catalogue in order to perform a
lightning protection installation.
LIGHTNING
PROTECTION
SYSTEMS
EXTERNAL PROTECTION 12
GUIDE FOR THE DESIGN:
EARLY STREAMER EMISSION AIR TERMINALS (ESE AIR TERMINALS)
Installation standards
The installation of the LPS using ESE air terminals must follow the relevant
standards (NFC 17102, UNE 21186 or similar):
The radius of protection offered by an ESE lightning conductor is related
to its height (h) relative to the area to be protected, to its triggering
advance and to the protection level. The following table shows the DAT
CONTROLER
PLUS
AT-1515 AT-1530 AT-1545 AT-1560
h DC+15 DC+30 DC+45 DC+60
Level 4 Level IV
2 20 28 36 43
4 41 57 72 85
6 52 72 90 107
8 54 73 91 108
10 56 75 92 109
Level 3 Level III
2 18 25 32 39
4 36 51 64 78
6 46 64 81 97
8 47 65 82 98
10 49 66 83 99
Level 2 Level II
2 15 22 28 35
4 30 44 57 69
6 38 55 71 87
8 39 56 72 87
10 40 57 72 88
Level 1 Level I
2 13 19 25 31
4 25 38 51 63
6 32 48 63 79
8 33 49 64 79
10 34 49 64 79
The air terminal must be installed at least 2 meters higher than any other
element within its protected area.
Each air terminal must be connected to the earthing using two
down-conductors that will preferably be placed on different
external walls of the structure.
The down conductor should be installed such that its routing is as
straight as possible and takes the shortest path to earth without sharp
bends or upward sections. Care should also be taken to avoid crossing
or running conductors in close proximity to electrical cables.
When external routing is impracticable, the down-conductor may be
internally routed inside an insulating non-flammable duct with a minimum
internal cross-sectional area of 2000mm
2
. The project manager must
also be aware of the reduced lightning protection system effectiveness,
maintenance difficulties, and the risks resulting from the entry of voltage
surges into structures.
The number of fixings is determined considering 3 clips per meter.
Down conductors should be protected by installing guard tubes up to a
height of 2m above ground level.
The installation of a Lightning Event Counter over the guard tube is
recommended in order to perform the verification and maintenance
operations which are essential for any lightning protection system.
The down-conductor must always be at least 3 meters from external gas
pipes.
Each down-conductor must have an earth termination system.
Earth terminations should be located externally to the building.
The connection with the earth termination system must be done directly
at the end of each down-conductor, using a device that allows the
disconnection of the earth electrode and should be placed inside an
inspection pit marked with the earth symbol.
The resistance of the earth measured by conventional means
must be lower than 10 when separated from other conductive
elements.
The inductance of the earthing must be as low as possible. The
recommended arrangement is vertical electrodes forming a triangle with
a minimum total length of 6m. The vertical electrodes must be bonded
with a conductor buried 50cm deep and separated at a greater distance
than their length.
The use of a soil conductivity improver is recommended in high resistivity
ground.
All the earth termination systems should be bonded together and to the
general earth system of the building.
It is recommended to use a spark gap to connect the lightning earth
termination system to the general earthing, as well as the lightning air
terminal mast to any aerials.
All elements of the earth termination system must always be at least 5
meters from any buried metallic or electrical service.
h: air terminal height over the surface to be protected.
Down-conductors should have a cross-section of at least
50mm. Since lightning current is impulsional, at conductors
(tape) are preferable to round conductors because they have
a larger surface for the same amount of material. On another
side tin-plated copper is recommended due to its physical,
mechanical and electrical characteristics (conductivity,
malleability, corrosion resistance and so on).
EXTERNAL PROTECTION 13
Working basis and main materials
The functioning of Early Streamer Emission Air Terminals is based on the electric characteristics of lightning formation. Lightning initiates with a down-
conductor, propagating in any direction. Once it approaches a close proximity to objects on the earth surfaces any of them can be struck. The objective of an
external lightning protection system is to control the lightning strike point and provide the lightning current with a path to earth avoiding damage to the structure.
The main feature of Early Streamer Emission (ESE) Air Terminals is the generation of the continuous upward leader before any other object within its protected
area. The standards define this characteristic using a parameter called advance time (t): Average gain in upward leader triggering compared with a reference
point having the same geometry. It is obtained by laboratory tests, and is measured in microseconds.
The advance time determines the protection radius of each air terminal. If the triggering occurs earlier, then the distance at which the downward leader is
intercepted increases, thus avoiding a lightning strike in a wider area. The advance time must be measured in a High Voltage laboratory, following the test
procedure described in the ESE lightning protection standards.
The components for a Lightning Protection System using ESE Air Terminals are as follows:
External Lightning Protection System
One or more air terminals.
Two or more down-conductors.
An Earth Termination System.
Internal Lightning Protection System
A correct surge protection installation (see Overvoltage Protection
catalogue)
Other measures minimizing the destructive effects of lightning
(equipotential bonding, screening, etc.)
Recommended materials for a lightning protection installation using ESE Air Terminals:
Interception systems Reference Page
ESE lightning air terminal AT-1560 19
Adapting piece AT-011A 26
Mast AT-056A 30
Anchorage AT-023B 30
Down-conductors Reference Page
Clip AT-015E 40
Tile support AT-094E 54
Downpipe support AT-073E 56
Clamp AT-020F 60
Spark gap for aerial mast AT-060F 66
Lightning event counter AT-001G 67
Guard tube AT-060G 68
Conductor AT-052D 74
Earthing Reference Page
Earth electrode AT-025H 256
Ground enhancing product AT-010L 263
Earth pit AT-010H 264
Bonding bar AT-020H 266
Spark gap for earthing AT-050K 269
Conductor AT-052D 74
AT-1560
AT-011A
AT-056A
AT-023B
AT-052D
AT-060F
AT-020F
AT-028E
AT-001G
AT-094E
AT-060G
AT-010H
AT-020H
AT-050K
AT-052D
AT-025H
AT-010L
EXTERNAL PROTECTION 14
GUIDE FOR THE DESIGN: RODS AND MESHED CONDUCTORS
Installation standards
The installation of a lightning protection system using rods and meshed
conductors must follow the standards IEC62305 Lightning Protection:
The volume protected by the air terminals can be determined using 3
methods:
Angle method
According to this method the protection volume is given by a line which
origin is at the air terminal, and which angle depends on the height and the
protection level, according to the following chart and graphic:
PROTECTION
LEVEL
h (m) 20 30 45 60
D (m)
I 20 25 * * *
II 30 35 25 * *
III 45 45 35 25 *
IV 60 55 45 35 25
* For structures higher than 60m, this method cannot be applied.
Self-standing rods (table 9) are recommended when the rods have to surpass
8m or higher elements on the roof.
Franklin rods should be placed on
the higher and most vulnerable
places (edges, overhangs, etc.),
as shown in the figure:
Rolling sphere method
The rolling sphere method is based on an electrogeometrical model, where
it is assumed that the downward leader that will strike the structure to be
protected has the shape of a sphere with a radius D (space where the last step
of the downward leader can stay). The points where this sphere can touch the
structure should be provided with air terminals.
According to the Standard IEC 62305-3,
the rolling sphere radius depends on the
protection level:
Protection Level I: D = 20m
Protection Level II: D = 30m
Protection Level III: D = 45m
Protection Level IV: D = 60m
Rp= 2Dh-h
2
Once these air terminals are installed, the protection radius (Rp) on a flat
surface can be defined as shown in the figure and the formula:
Mesh method
According to this method, conductors forming a mesh should be placed on the
structure. The separation depends on the protection level:
Protection Level I: w = 5m
Protection Level II: w = 10m
Protection Level III: w = 15m
Protection Level IV: w = 20m
The mesh should initially be applied to the cover perimeter, especially edges
and overhangs.
For buildings higher than 60m, a mesh with the same size should also cover
the upper 20% of the outer walls.
Down-conductors should follow these requirements:
To provide several parallel paths to share the lightning current.
The length of the current paths to the earthing should be as
short and direct as possible.
They should be connected to the grounded metallic parts of
the structure if the distance between them is shorter than the
separation distance as dened in the standard.
The distance between down-conductors depends also on the protection
level:
Protection Level Distance between down-conductors
I 10m
II 10m
III 15m
IV 20m
The conductors should be fixed to the structure once every meter.
For longer conductors, it is recommended to install expansion joints
every 20 meters.
A guard tube should be installed for each down-conductor, covering at
least 2m over the floor, in order to avoid mechanical damages.
Every down-conductor must be connected to the earthing. It is
recommended to equipotentialize all the down-conductors at ground
level and every 20m.
A disconnecting sleeve should be installed in each down-conductor for
measuring earth resistance separated from other conductive elements.
It is recommended that the earthing resistance is less than 10.
Earth conductors should be buried at a depth of at least 0,5m.
It is not recommended to install aluminium conductors or fittings directly
into earth.
Unions between copper and aluminium conductors or copper and
galvanized steel conductors are not recommended in order to avoid
corrosion. Bimetallic or stainless steel clamps should be used.
Protection
Level
EXTERNAL PROTECTION 15
Main materials
Lightning protection using rods and meshed conductors is intended to share and dissipate the lightning current through a network of down-conductors and
earth terminations.
The elements of a lightning protection system using rods and meshed conductors are as follows:
Internal Lightning Protection System
A correct surge protection installation (see Overvoltage
Protection catalogue)
Other measures minimizing the destructive effects of lightning
(equipotential bonding, screening, etc.)
External Lightning Protection System
Simple rods and/or meshed conductors.
Down-conductors.
Earth Termination System.
Recommended materials for a lightning protection installation using rods and meshed conductors:
This table gives the appropriate material for making a copper, aluminium, galvanized steel or stainless steel mesh.
Denomination
Reference
Cu
Page
Reference
Al
Page
Reference
Galv S
Page Reference SS Page
Air rod AT-005A 23 AT-008A 23 AT-038A 24 AT-032A 24
Self-supporting air rod AT-104A 24 AT-104A 24
Air rod base AT-115B 26 AT-116B 26 AT-030B 29 AT-030B 29
Flat washer AT-095B 29 AT-095B 29
Roof conductor holder AT-207E 43 AT-207E 43 AT-042E 51 AT-042E 51
Clamp AT-033F 59 AT-039F 59 AT-125F 62 AT-122F 62
Conductor AT-011D 74 AT-057D 75 AT-060D 77 AT-128D 77
Clip AT-114E 40 AT-121E 40 AT-128E 45 AT-128E 45
Clip for guard tube AT-132E 45
Tile support AT-094E 54 AT-094E 54 AT-090E 52 AT-090E 52
Gutter clamp AT-040F 54 AT-040F 54
Downpipe support AT-177E 58 AT-025J 58 AT-186E AT-186E
Clamp AT-033F 59 AT-039F 59 AT-125F 62 AT-122F 62
Test clamp AT-081F 64 AT-094F 65
Spark gap for aerial mast AT-060F 66 AT-060F 66 AT-060F 66 AT-060F 66
Guard tube AT-060G 68 AT-060G 68 AT-057G 68 AT-054G 68
Joint protection AT-010J 264
Conductor AT-011D 74 AT-057D 75 AT-060D 77 AT-128D 77
Earth electrode AT-041H 259 AT-041H 259 AT-049H 261 AT-080H 260
Coupling AT-038K 261
Ground enhancing product AT-010L 263 AT-010L 263 AT-010L 263 AT-010L 263
Earth pit AT-010H 264 AT-010H 264 AT-010H 264 AT-010H 264
Bonding bar AT-020H 266 AT-020H 266 AT-020H 266 AT-021J 266
Earth clamp AT-080J 272 AT-080J 272 AT-131J 275 AT-133J 275
Conductor AT-011D 74 AT-011D 74 AT-061D 77 AT-129D 77
I
n
t
e
r
c
e
p
t
i
o
n
s
y
s
t
e
m
s
D
o
w
n
-
c
o
n
d
u
c
t
o
r
s
E
a
r
t
h
i
n
g
INTERCEPTION SYSTEMS
ESE lightning air terminals
Rods and meshed conductors
AND ACCESORIES
Fixings
Masts and anchorages
EXTERNAL PROTECTION 18
An Early Streamer Emission (ESE) Air Terminal is characterized by reacting
when lightning approaches, intercepting it earlier than any other element
within its protection area in order to conduct it safely to the ground.
This time ahead is normatively called Advance time (t) and it determines
the air terminal protective radius.
ESE AIR TERMINAL
DAT CONTROLER
PLUS
1
For an enhanced guarantee,
the DAT CONTROLER
PLUS Air Terminals have
been submitted to several
tests in offcial and
independent laboratories:
It is necessary to verify that the air terminals are not perishable and
they continue working after repetitive lightning strikes, maintaining the
advance time capability.
DAT CONTROLER
PLUS
AT-1515 AT-1530 AT-1545 AT-1560
h DC+15 DC+30 DC+45 DC+60
Level 4 Level IV
2 20 28 36 43
4 41 57 72 85
6 52 72 90 107
8 54 73 91 108
10 56 75 92 109
Level 3 Level III
2 18 25 32 39
4 36 51 64 78
6 46 64 81 97
8 47 65 82 98
10 49 66 83 99
Level 2 Level II
2 15 22 28 35
4 30 44 57 69
6 38 55 71 87
8 39 56 72 87
10 40 57 72 88
Level 1 Level I
2 13 19 25 31
4 25 38 51 63
6 32 48 63 79
8 33 49 64 79
10 34 49 64 79
h: air terminal height over the surface to be protected.
EXTERNAL PROTECTION 19
DAT
CONTROLER
PLUS remains
working properly
after withstanding
repetitive lightning
discharges, with no
disruption to the
advance time (t)
The below described A.1 and A.2 tests have been performed on the same air terminals consecutively with the aim of
assuring its proper working after withstanding repetitive lightning currents. These tests have been carried out by the
LCOE (Central Official Electrotechnics Laboratory, Ministry of Science and Technology).
A.1) CERTIFIED WITHSTAND CURRENT: 100kA. Direct application of 10 lightning current impulses (10/350s)
with a current peak higher than 100kA and specific energy higher than 2,5MJ/, according to IEC60060-1 and
IEC61083-1.
A.2) CERTIFIED ADVANCE TIME, tested according to UNE 21186 and NFC 17102 (Annex C Test for the evaluation
of a ESE air terminal) and fixed after applying a security factor equal to twice the uncertainty registered during the
test:
A) AENOR PRODUCT CERTIFICATION NR. 058/000003
(Lightning current advance time consecutive test)
The DAT CONTROLER
PLUS
Air Terminal is provided with:
B) CERTIFICATE OF EFFECTIVE PERFORMANCE
UNDER RAIN.
Insulation superior to 95%.
These tests have been performed according to the standard UNE
21308 (IEC60060-1) in the LCOE (Central Official Electrotechnics
Laboratory, Ministry of Science and Technology).
B.1) Comparative dry/rain tests with continuous voltage
(simulating the electric field during a storm)
B.2) Comparative dry/rain tests with switching impulses
(simulating the approach of the downward leader)
C) CERTIFICATE OF PROTECTION
RADIUS AND FULFILLMENT OF
THE RELEVANT STANDARDS
Certificate of the protection radius for each model and protection
level calculated according to the relevant standards.
For an ESE Air Terminal, the triggering device supply comes from
the high difference of potential, in storm conditions, between its
isolated metallic armatures. It is therefore necessary to guarantee
this potential difference under bad weather conditions.
Ref. Model
Advance time
during the test
Uncertainty
of the test (i)
Security
factor
Certified
Advance
Time
AT-1515 DAT CONTROLER
PLUS 15 39 s 11 s 2 x i 15 s
AT-1530 DAT CONTROLER
PLUS 30 52 s 11 s 2 x i 30 s
AT-1545 DAT CONTROLER
PLUS 45 68 s 12 s 2 x i 45 s
AT-1560 DAT CONTROLER
PLUS 60 86 s 12 s 2 x i 60 s
Lightning current
advance time
consecutive test
The patented design of DAT
CONTROLER
PLUS avoids
the contact between the metallic
framework at atmospheric potential
(in blue) and the metallic axis
connected to earth (in red)
EXTERNAL PROTECTION 20
ESE LIGHTNING AIR TERMINALS EXAMPLES
These are several examples of interception systems with ESE lightning air terminals, showing the most relevant material:
Reference Denomination Table
AT-1560 DAT CONTROLER
PLUS 1
AT-011A Tape adapting piece 14
AT-056A Mast 26
AT-023B U shaped anchorage 27
AT-015E Tape clip 42
AT-094E Tile support 71
AT-020F Square tape clamp 87
AT-060F Spark gap for aerial mast 101
AT-052D Tape conductor 116
Reference Denomination Table
AT-1560 DAT CONTROLER
PLUS 1
AT-011A Tape adapting piece 14
AT-080B Chimney anchorage 36
AT-081B Isolated support for chimneys 36
AT-085B 5m rod for chimneys 36
AT-015E Tape clip 42
AT-052D Tape conductor 116
Reference Denomination Table
AT-1560 DAT CONTROLER
PLUS 1
AT-011A Tape adapting piece 14
AT-012C Free standing mast 38
AT-052D Tape conductor 116
Reference Denomination Table
AT-1560 DAT CONTROLER
PLUS 1
AT-010A Cable adapting piece 14
AT-031C Trestle tower 39
AT-044C Cable trestle tower clip 40
AT-046C Cable to Guy wire clamp 40
AT-050D Cable conductor 124
ESE lightning air terminals
AT-084B
AT-081B
Ver tabla 1
AT-080B
AT-085B
INTERCEPTION SYSTEMS AND ACCESORIES
EXTERNAL PROTECTION 21
These are several examples of interception systems with rods and meshed
conductors, showing the most relevant material:
Reference Denomination Table
AT-002A Multi-point 12
AT-056A Mast 26
AT-023B U shaped anchorage 27
AT-043E Cable clip 56
AT-090E Curve tile support 67
AT-120F T clamp 88
AT-060F Spark gap for aerial mast 101
AT-060D Round conductor 125
Reference Denomination Table
AT-005A Taper pointed air rod 5
AT-115B Air rod base 16
AT-033F Square tape clamp 85
AT-011D Tape conductor 115
Reference Denomination Table
AT-038A Lightning rod for wedge 8
AT-111A Self-supporting air termination rod 9
AT-030B Concrete base 25
AT-095B Flat washer for concrete base 25
AT-042E Roof conductor holder 64
AT-025F Rod universal clamp 91
AT-125F Universal clamp 91
AT-012G Expansion unit 104
AT-060D Round conductor 125
Reference Denomination Table
AT-041E Pyramidal roof conductor holder 63
AT-145E
Pyramidal roof conductor
holder with square clamp
63
AT-052D Tape conductor 116
Rods and meshed conductors
RODS AND MESHED CONDUCTORS EXAMPLES
INTERCEPTION SYSTEMS AND ACCESORIES
EXTERNAL PROTECTION 22
ESE AIR TERMINAL / Rods
Reference Model Dimensions (mm) Material Weight (Kg)
AT-1465 TRAZOR T- PDC / 5 175 x 175 x 750 Stainless steel 6,5
AT-1467 TRAZOR T- PDC / 7 175 x 175 x 750 Stainless steel 6,5
AT-1469 TRAZOR T- PDC / 9 175 x 175 x 750 Stainless steel 6,5
AT-1470 TRAZOR T- PDC / 10 175 x 175 x 750 Stainless steel 6,5
Reference Dimensions (mm) Thread Material Weight (Kg)
AT-053L 20 x 300 female thread M10 Stainless steel 0,65
AT-055L 20 x 500 female thread M10 Stainless steel 1,14
AT-096A 20 x 1000 female thread M10 Stainless steel 2,35
AT-097A 20 x 300 female thread M10 Chrome plated copper 0,7
AT-098A 20 x 500 female thread M10 Chrome plated copper 1,25
AT-099A 20 x 1000 female thread M10 Chrome plated copper 2,6
AT-023A 20 x 400 M20 Stainless steel 0,9
AT-019A 20 x 400 M20 Chrome plated copper 1
AT-121A 16 x 300 M16 Stainless steel 0,5
AT-122A 16 x 300 M16 Stainless steel 1
2 ESE AIR TERMINAL TRAZOR
AT-1465
Meets UNE 21186, NFC 17102
3 AIR TERMINATION ROD
20mm rods assemble for example with AT-022F or AT-003M (Tables 23, 24), except AT-023A and AT-019A that assemble
for example into AT-010A (Table 14). 16mm rods assemble with AT-124B (Table 17).
For using in conjunction with the mast anchorages (Tables 27 to 35). AT-024A and AT-017A include an adapting piece AT-011A (Table 14) for fixing the conductor
(tape, cable or round) inside the mast. The rest of the references need to fix the conductor outside the mast. (For example AT-033A. Table 61).
Meets with IEC 62305, EN 50164
AT-053L (SS)
AT-097A (CC)
AT-023A (SS)
AT-019A (CC)
AT-024A (SS)
AT-017A (CC)
4 AIR TERMINAL WITH MAST
Reference Dimensions (mm) Total height (m) Material Weight (Kg)
AT-013A 20 x 400 mm + Mast 1 x 1000 mm 1,4 Stainless steel / Stainless steel (mast) 2,5
AT-014A 20 x 400 mm + Mast 1 x 2000 mm 2,4 Stainless steel / Stainless steel (mast) 4,5
AT-024A 20 x 400 mm + Mast 1 x 2000 mm 2,4 Stainless steel / Stainless steel (mast) 8,3
AT-015A 20 x 400 mm + Mast 1 x 1000 mm 1,4 Chrome plated copper / Stainless steel (mast) 2,6
AT-016A 20 x 400 mm + Mast 1 x 2000 mm 2,4 Chrome plated copper / Stainless steel (mast) 4,6
AT-017A 20 x 400 mm + Mast 1 x 2000 mm 2,4 Chrome plated copper / Galvanized steel (mast) 8,4
Meets with IEC 62305, EN 50164
T-PDC/5 T-PDC/7 T-PDC/9 T-PDC/10
Level I 37 42 52 77
Level II 44 48 59 85
Level III 52 57 69 95
Level IV 59 64 77 105
Protection radius in meters
Height of air terminal
INTERCEPTION SYSTEMS AND ACCESORIES
EXTERNAL PROTECTION 23
Rods and meshed conductors
Reference Dimensions (mm) Total height (m) Thread Included Material Weight (Kg)
AT-004A 16 x 350 + 15 x 150 0,5 M16 Tightening nut Copper 0,73
AT-005A 16 x 850 + 15 x 150 1 M16 Tightening nut Copper 1,51
AT-006A 16 x 1850 + 15 x 150 2 M16 Tightening nut Copper 3
AT-007A 16 x 350 + 15 x 150 0,5 M16 Tightening nut Aluminium 0,29
AT-008A 16 x 850 + 15 x 150 1 M16 Tightening nut Aluminium 0,53
AT-009A 16 x 1850 + 15 x 150 2 M16 Tightening nut Aluminium 1,06
Reference Dimensions (mm) Thread Included Material Weight (gr)
AT-092A 10 x 500 M10 Tightening nut Copper 330
AT-093A 10 x 1000 M10 Tightening nut Copper 650
AT-094A 10 x 500 M10 Tightening nut Aluminium 110
AT-095A 10 x 1000 M10 Tightening nut Aluminium 220
AT-116A
TAPER POINTED AIR ROD 5
10 TAPER POINTED AIR ROD 6
These air rods are available in copper or aluminium and fit into the rod couplings, the flat and ridge saddles, air rod base, and multi-point.
(For example AT-104B, AT-110B or AT-000A. Tables 15 to 20, 10).
These air rods are available in copper or aluminium and fit into the horizontal and vertical air terminal saddles.
(For example AT-122B. Tables 21 and 22). Only for applications where mechanical stress such as wind loading is not critical.
Suitable for using with threaded concrete bases.
(For example AT-097B. Table 25)
THREADED LIGHTNING ROD 7
AT-004A (Cu)
AT-007A (Al)
Meets with IEC 62305, EN 50164, BS 1432 C101, BS 2897, AS 1567
Meets with IEC 62305, EN 50164, BS 1432 C101, BS 2897, AS 1567
AT-092A (Cu)
AT-094A (Al)
Reference Dimensions (mm) Total height (m) Thread Material Weight (Kg)
AT-114A 16 x 500 + 10 x 1000 1,5 M16 Aluminium 0,48
AT-115A 16 x 1000 + 10 x 1000 2 M16 Aluminium 0,76
AT-116A 16 x 1500 + 10 x 1000 2,5 M16 Aluminium 1,02
AT-117A 16 x 2000 + 10 x 1000 3 M16 Aluminium 1,3
AT-118A 16 x 2500 + 10 x 1000 3,5 M16 Aluminium 1,52
AT-119A 16 x 3000 + 10 x 1000 4 M16 Aluminium 1,73
Meets with IEC 62305, EN 50164
INTERCEPTION SYSTEMS AND ACCESORIES
EXTERNAL PROTECTION 24
Rods and meshed conductors
Tapered air-termination rod with hinged tripod support for protection of larger roof structures such air conditioners. The air termination rods are designed for
wind velocity up to 145 Km/h. The stackable concrete bases (AT-030B. Table 25), the flat washers (AT-095B. Table 25) and the clip for round conductor 6-10
mm (AT-138E. Table 59) are included. The rod is made of aluminium.
9 SELF-SUPPORTING AIR TERMINATION ROD
AT-026A (GS)
AT-032A (SS)
AT-036A (Cu)
AT-038A (Al) AT-045A
AT-111A (Aplicacin)
No threaded lightning rods suitable for using with stackable wedge concrete bases
(For example AT-030B. Table 25)
Reference Base occupation (mm) Mast height (m)
N of
concrete
bases
Material Weight (Kg)
AT-100A 1700 3 3 Galvanized steel / Aluminium 60
AT-101A 1700 3,5 3 Galvanized steel / Aluminium 61
AT-102A 1700 4 3 Galvanized steel / Aluminium 62
AT-103A 1700 4,5 3 Galvanized steel / Aluminium 63
AT-104A 1700 5 3 Galvanized steel / Aluminium 64
AT-105A 1700 5,5 6 Galvanized steel / Aluminium 115
AT-106A 1700 6 6 Galvanized steel / Aluminium 116
AT-107A 2200 6,5 6 Galvanized steel / Aluminium 125
AT-108A 2200 7 6 Galvanized steel / Aluminium 127
AT-109A 2200 7,5 9 Galvanized steel / Aluminium 180
AT-110A 2200 8 12 Galvanized steel / Aluminium 232
AT-111A 2200 8,5 12 Galvanized steel / Aluminium 234
Reference Dimensions (mm) Total height (m) Material Weight (Kg)
AT-025A 16 x 750 0,75 Galvanized steel 1,22
AT-026A 16 x 1000 1 Galvanized steel 1,6
AT-027A 16 x 1250 1,25 Galvanized steel 2
AT-028A 16 x 1500 1,5 Galvanized steel 2,4
AT-029A 16 x 2000 2 Galvanized steel 3,2
AT-030A 16 x 2500 2,5 Galvanized steel 4
AT-031A 16 x 3000 3 Galvanized steel 4,8
AT-032A 16 x 1000 1 Stainless steel 1,6
AT-034A 16 x 1500 1,5 Stainless steel 2,38
AT-035A 16 x 2000 2 Stainless steel 3,2
AT-036A 16 x 1000 1 Copper 1,85
AT-037A 16 x 1500 1,5 Copper 2,77
AT-038A 16 x 1000 1 Aluminium 0,54
AT-039A 16 x 1500 1,5 Aluminium 0,82
AT-040A 16 x 2000 2 Aluminium 1,8
AT-041A 16 x 2500 2,5 Aluminium 1,4
AT-042A 16 x 3000 3 Aluminium 1,68
AT-043A 10 x 1000 1 Aluminium 0,22
AT-044A 16 x 500 + 10 x 1000 1,5 Aluminium 0,48
AT-045A 16 x 1000 + 10 x 1000 2 Aluminium 0,76
AT-046A 16 x 1500 + 10 x 1000 2,5 Aluminium 1,02
AT-047A 16 x 2000 + 10 x 1000 3 Aluminium 1,3
Meets with IEC 62305, EN 50164
8 LIGHTNING ROD FOR WEDGE
Meets with IEC 62305, EN 50164
INTERCEPTION SYSTEMS AND ACCESORIES
EXTERNAL PROTECTION 25
Rods and meshed conductors
Multi-point suitable only for use with copper taper pointed air rod. (For example AT-004A. Table 5)
GUNMETAL MULTI-POINT 10
Reference Points dimensions (mm) Material Weight (gr)
AT-000A 3 x (9 x 90) Gunmetal 325
AT-000A
AT-000A Application
AT-001A Application
COPPER MULTI-POINT WITH MAST 11
Meets with IEC 62305, EN 50164, BS 6651, BS 1432 C101, BS
1400, BS 2897, BS 2874, AS 1567
Copper multi-point to be mounted at the top of metallic structures. Total height: 1,5m (including mast and anchorage). It includes 8
anchorage holes of 18mm, at 80mm from the centre.
Reference Multi-point dimensions (mm) Material Weight (Kg)
AT-001A (16 x 495) + 4 x (16 x 315) Copper (points) / Galvanized steel (mast) 9,5
Reference Multi-point dimensions (mm)
Conductor range
Material Weight (gr)
(mm) mm
2
AT-002A (16 x 185) + 4 x (8 x 72) 8-10 50 - 70 Stainless steel (points) 885
AT-003A (16 x 185) + 4 x (8 x 72) 8-10 50 - 70 Copper (points) 940
Reference Dimensions (mm) Material Weight (gr)
AT-112A 112 x 112 x 25 Copper 410
AT-113A 112 x 112 x 25 Aluminium 130
Meets with IEC 62305, EN 50164
Meets with IEC 62305, EN 50164
MULTI-POINT 12
Multi-point with the adapting piece made of naval brass, suitable for use with galvanized steel mast 1 1/2". (For example AT-066A. Table 26)
AT-003A (Cu)
AT-002A (SS)
STRIKE PAD 13
Provided with a screw to attach it to the lightning conductors.
AT-112A(Cu)
AT-113A (Al)
INTERCEPTION SYSTEMS AND ACCESORIES
EXTERNAL PROTECTION 26
Fixings
14 ADAPTING PIECE
Suitable for fixing the lightning rod in the mast (Table 26) with internal conductor (tape, cable or round) connection. The lightning
rod-adapting piece thread is M20.
Used for supporting lightning conductor air terminals onto the roof and connecting to the tape.
Used for supporting lightning conductor air terminals onto the ridge of the roof and connecting to the tape.
Reference Mast
Dimensions
(mm)
Conductor range
Material Weight (gr)
(mm) mm
2
Tape (mm)
AT-010A 1 48 x 70 8-10 50 - 70 - Naval brass 675
AT-011A 1 48 x 70 8-10 50 - 70 30x2 - 30x3.5 Naval brass 655
AT-012A 1 34 x 97 8-10 50 - 70 - Naval brass 420
AT-020A 1 48 x 70 8-10 50 - 70 - Stainless steel 615
AT-021A 1 48 x 70 8-10 50 - 70 30x2 - 30x3.5 Stainless steel 640
AT-022A 1 34 x 97 8-10 50 - 70 - Stainless steel 400
AT-011A (NB)
AT-021A (SS)
AT-110B (Gu)
AT-111B (Al)
15 RIDGE SADDLE
Reference Dimensions (mm) Conductor range (mm) Thread Material Weight (gr)
AT-110B 150 x 150 x 71 25x3 - 30x3 M16 Gunmetal 1070
AT-111B 150 x 150 x 71 25x3 - 30x3 M16 Aluminium 340
Reference Dimensions (mm) Conductor range (mm) Thread Material Weight (gr)
AT-115B 100 x 100 x 33 25x3 M16 Gunmetal 470
AT-116B 100 x 100 x 33 25x3 M16 Aluminium 150
AT-110B Application
16 AIR ROD BASE
AT-115B (Gu)
AT-116B (Al)
AT-011A Application Meets with EN 50164, UNE 21186, NFC 17102
Meets with IEC 62305, EN 50164, BS 6651, BS 1400, BS 1471, AS 1866, AS 1567
Meets with IEC 62305, EN 50164, BS 6651, BS 1400, BS 1471, AS 1866, AS 1567
See table 5
See table
1 and 2
See table 26
INTERCEPTION SYSTEMS AND ACCESORIES
EXTERNAL PROTECTION 27
Fixings
Used for supporting lightning conductor air terminals onto the roof and connecting to the cable or round.
The brackets are mainly used where it is not possible to fit a saddle on the roof. Used in conjunction with
couplings and taper pointed air rods.
This unit screws onto the air rod and connects to the tape with the fixing screw provided. Used in conjunction with rod brackets and
taper pointed air rods.
This unit screws onto the air rod and connects to the cable with the fixing screw provided. Used in conjunction with rod brackets
and taper pointed air rods.
FLAT SADDLE 17
Reference Dimensions (mm)
Conductor range
Thread Material Weight (gr)
(mm) mm
2
AT-112B 85 x 85 x 64 8 50 M16 Gunmetal 1030
AT-113B 85 x 85 x 64 10 70 M16 Gunmetal 950
AT-114B 85 x 85 x 64 13 95 M16 Gunmetal 950
AT-124B 30 x 34 x 57 8-10 50-70 M16 Stainless steel 170
AT-125B 30 x 34 x 57 8-10 50-70 M20 Stainless steel 170
Reference Dimensions (mm) Rod (mm) Material Weight (gr)
AT-104B 120 x 24 x 60 16 Gunmetal 900
AT-105B 120 x 24 x 60 16 Aluminium 280
AT-114B
ROD BRACKETS 18
AT-104B (Gu)
AT-105B (Al)
AT-100B (Gu)
AT-101B (Al)
ROD TO TAPE COUPLING 19
Reference Dimensions (mm) Rod (mm) Material Weight (gr)
AT-100B 39 x 39 x 80 M16 Gunmetal 200
AT-101B 39 x 39 x 80 M16 Aluminium 60
ROD TO CABLE COUPLING 20
Reference Dimensions (mm)
Conductor range
Thread Material Weight (gr)
(mm) mm
2
AT-102B 39 x 39 x 80 8 - 10 50-70 M16 Gunmetal 220
AT-103B 39 x 39 x 80 13 95 M16 Aluminium 70
AT-122B Application
AT-102B (Gu)
AT-103B (Al)
Meets with IEC 62305, EN 50164, BS 6651, BS 1400, BS 1471, AS 1866, AS 1567
Meets with IEC 62305, EN 50164, BS 6651, BS 1400, BS 1494, BS 2897, AS 1567
Meets with IEC 62305, EN 50164, BS 6651, BS 1400, BS 1494, BS 2897, AS 1567
Meets with IEC 62305, EN 50164, BS 6651, BS 1400, BS 1494, BS 2897, AS 1567
See table 5
Aplication AT-104B
INTERCEPTION SYSTEMS AND ACCESORIES
EXTERNAL PROTECTION 28
21 VERTICAL AIR TERMINAL SADDLE
Fixings
Reference Dimensions (mm)
Conductor range
Thread Material Weight (gr)
(mm) mm
2
AT-122B 65 x 65 x 35 8 50 M10 Gunmetal 300
AT-123B 65 x 65 x 35 8 50 M10 Aluminium 110
Reference Dimensions (mm)
Conductor range
Thread Material Weight (gr)
(mm) mm
2
AT-120B 65 x 65 x 35 8 50 M10 Gunmetal 300
AT-121B 65 x 65 x 35 8 50 M10 Aluminium 110
Used for supporting 10 taper pointed air rods on the wall and connecting to the cable or round. An additional fixing AT-192E
or AT-193E (Table 51) may be used for 1 m taper pointed air rods.
AT-122B (Gu)
AT-123B (Al)
AT-120B (Gu)
AT-121B (Al)
22 HORIZONTAL AIR TERMINAL SADDLE
Used for supporting 10 taper pointed air rods on the roof and connecting to the cable or round. Its not
recommended to use it in combination with the 1 m taper pointed air rods.
Used for supporting lightning conductor air terminals onto the roof and connecting to the earth rod.
Reference Model
Dimensions
(mm)
Max. conductor width (mm)
Thread Material Weight (gr)
(mm) mm
2
Tape (mm)
AT-022F For flat roofs 55 x 55 x 40 8 - 10 50 - 70 30x2 30x3.5 M10 Naval brass 360
AT-011M For the ridge of the roof 270 x 160 x 140 8 - 10 50 - 70 30x2 30x3.5 M10 Naval brass 610
23 NAVAL BRASS ROOF CLAMP
Meets with IEC 62305, EN 50164, BS 6651
Meets with EN 50164, UNE 21186, NFC 17102
AT-022F Application
AT-011M Application
AT-022F
AT-011M
Meets with IEC 62305, EN 50164, BS 6651
See table 3
See table 3
See table 63
AT-122B Application
See table 6
See table
51
INTERCEPTION SYSTEMS AND ACCESORIES
EXTERNAL PROTECTION 29
Fixings
SPECIAL ROD SUPPORTS 24
Reference Model Dimensions (mm) Included Material Weight (gr)
AT-003M To vertical surface 40 x 40 x 40 M10 Stainless steel 130
AT-030M To top of the antennas mast 60 x 70 M10 female Stainless steel 600
Reference Model Dimensions (mm) Rod (mm) Included Material Weight (Kg)
AT-030B Stackable wedged concrete base 325 x 90 16 Wedge Concrete 17
AT-029B Stackable wedged concrete base 230 x 90 10 16 Wedge Concrete 8,5
AT-095B Flat washer 360 x 10 - - EVA 0,22
AT-096B Flat washer 270 x 10 - - EVA 0,19
AT-097B Threaded concrete base 350 x 100 16 Female M16 Concrete 12
AT-098B Threaded concrete base 350 x 120 16 Female M16 Concrete 16
AT-099B Threaded concrete base 350 x 140 16 Female M16 Concrete 25
For fixing air rods with male or female M10 (for example AT-053L, AT-092A tables 3, 6) to vertical surface or to the top of
the antennas mast. AT-030M accepts masts from 6 50 mm.
For supporting air termination rods, on flat roofs. For air rods higher than 3 m, these bases are not recommendable due to wind load. AT-029B only allows 10
x 1000 mm and 16 x 1000 mm air termination rods (for example AT-043A or AT-026A. Table 8).
See table 3 See table 3
CONCRETE BASE 25
AT-003M Application AT-030M Application
AT-029B
AT-030B
Meets with UNE 21186, NFC 17102
Meets with UNE 21186, NFC 17102
AT-095B
AT-097B AT-030B Application
See table 8
INTERCEPTION SYSTEMS AND ACCESORIES
EXTERNAL PROTECTION 30
Masts and anchorages
26 MASTS FOR WALL OR STRUCTURAL FIXING
1 elevation fixture up to 8 m. To be fixed with 2 anchorage supports, except the 8 m height with 3 anchorage supports. The
distance between supports must be 60 cm. In atmospheres with a high level of corrosion, the use of stainless steel masts is
recommended.
Reference Model Dimensions Included Material Weight (Kg)
AT-051A 1 m mast 1 x 1 m 1 section x 1 m Galvanized steel 3.3
AT-052A 2 m mast 1 x 2 m 1 section x 2 m Galvanized steel 6.6
AT-053A 3 m mast 1 x 3 m 1 section x 3 m Galvanized steel 10
AT-050A 4 m mast 1 x 4 m 2 sections x 2 m Galvanized steel 13
AT-056A 6 m mast (2 sections) 1 x 6 m 2 sections x 3 m Galvanized steel 20
AT-057A 6 m mast (3 sections) 1 x 6 m 3 sections x 2 m Galvanized steel 20
AT-058A 8 m mast 2" - 1 x 8 m 3 sections x 3 m Galvanized steel 35
AT-060A 1 m mast 1 x 1 m 1 section x 1 m Stainless steel 3
AT-062A 2 m mast 1 x 2 m 1 section x 2 m Stainless steel 6
AT-063A 3 m mast 1 x 3 m 1 section x 3 m Stainless steel 9
AT-085A 4 m mast 1 x 4 m 2 sections x 2 m Stainless steel 12
AT-066A 6 m mast (2 sections) 1 x 6 m 2 sections x 3 m Stainless steel 18
AT-067A 6 m mast (3 sections) 1 x 6 m 3 sections x 2 m Stainless steel 18
AT-068A 8 m mast 2" - 1 x 8 m 3 sections x 3 m Stainless steel 30
Reference Model Dimensions (mm) Included Material Weight (Kg)
AT-013B 30 cm U shaped anchorage to embed into the wall 2 x (50 x 340 x 390) 2 supports Galvanized steel 4,6
AT-014B 30 cm U shaped anchorage to embed into the wall 3 x (50 x 340 x 390) 3 supports Galvanized steel 6,9
AT-016B 60 cm U shaped anchorage to embed into the wall 2 x (50 x 640 x 615) 2 supports Galvanized steel 11
AT-017B 60 cm U shaped anchorage to embed into the wall 3 x (50 x 640 x 615) 3 supports Galvanized steel 16
AT-023B 30 cm U shaped anchorage to screw into the wall 2 x (50 x 400 x 290) 2 supports Galvanized steel 6
AT-024B 30 cm U shaped anchorage to screw into the wall 3 x (50 x 400 x 290) 3 supports Galvanized steel 9
AT-026B 60 cm U shaped anchorage to screw into the wall 2 x (50 x 600 x 670) 2 supports Galvanized steel 10
AT-027B 60 cm U shaped anchorage to screw into the wall 3 x (50 x 600 x 670) 3 supports Galvanized steel 15
Meets with UNE 21186, NFC 17102
Meets with UNE 21186, NFC 17102
AT-066A (SS)
AT-056A (GS)
27 U SHAPED ANCHORAGE
1 - 1 mast anchorage to be embedded or screwed into the wall. The 60 cm U shaped anchorages are designed to avoid
obstacles such as 50 cm cornices. The anchorages need a minimum separation of 60 cm from each other and at least 30 cm
from the top of the wall, in order to assure a correct fixation.
Single extra supports, ref: AT-012B, AT-015B, AT-021B, AT-025B respectively.
AT-013B
AT-023B
AT-013B Application AT-023B Application
See table 26 See table 26
INTERCEPTION SYSTEMS AND ACCESORIES
EXTERNAL PROTECTION 31
Masts and anchorages
AT-019B
AT-019B (application)
See table 26
ANGLE BAR ANCHORAGE 28
Reference Model Dimensions (mm) Included Material Weight (Kg)
AT-035B 30 cm angle bar anchorage 2 x (50 x 120 x 300) 2 supports Galvanized steel 4
AT-036B 30 cm angle bar anchorage 3 x (50 x 120 x 300) 3 supports Galvanized steel 5,5
AT-045B 30 cm angle bar anchorage 2 x (50 x 120 x 300) 2 supports Stainless steel 3
AT-046B 30 cm angle bar anchorage 3 x (50 x 120 x 300) 3 supports Stainless steel 4,5
AT-038B 60 cm angle bar anchorage 2 x (50 x 120 x 600) 2 supports Galvanized steel 6
AT-039B 60 cm angle bar anchorage 3 x (50 x 120 x 600) 3 supports Galvanized steel 9
AT-048B 60 cm angle bar anchorage 2 x (50 x 120 x 600) 2 supports Stainless steel 4,5
AT-049B 60 cm angle bar anchorage 3 x (50 x 120 x 600) 3 supports Stainless steel 7
1 - 1 mast anchorage to be welded to metallic structures. The anchorages need a minimum separation of 60 cm from
each other, in order to assure a correct fixation.
1 - 1 mast anchorage to be fixed in trestle towers. Not recommendable for masts higher than 6 m. The anchorages need
a minimum separation of 60 cm from each other, in order to assure a correct fixation.
Single extra supports, ref: AT-034B, AT-044B, AT-037B, AT-047B respectively.
Single extra support, ref: AT-018B
Meets with UNE 21186, NFC 17102
Meets with UNE 21186, NFC 17102
MAST TO TRESTLE TOWER ANCHORAGE 29
Reference Dimensions (mm) Included Material Weight (Kg)
AT-019B 2 x (50 x 120 x 700) 2 supports Galvanized steel 7,6
AT-020B 3 x (50 x 120 x 700) 3 supports Galvanized steel 11,4
AT-038B (GS)
AT-048B (SS)
INTERCEPTION SYSTEMS AND ACCESORIES
EXTERNAL PROTECTION 32
Masts and anchorages
30 LIGHT ANCHORAGE
Reference Model Dimensions (mm) Included Material Weight (Kg)
AT-032B 30 cm light anchorage to embed into the wall 2 x (50 x 100 x 300) 2 supports Galvanized steel 3,4
AT-033B 30 cm light anchorage to embed into the wall 3 x (50 x 100 x 300) 3 supports Galvanized steel 5,1
AT-042B 30 cm light anchorage to screw into the wall 2 x (50 x 165 x 300) 2 supports Galvanized steel 4,2
AT-043B 30 cm light anchorage to screw into the wall 2 x (50 x 165 x 300) 3 supports Galvanized steel 6,3
1 - 1 mast anchorage to be embedded or screwed into the wall. The anchorages need a minimum separation of 60 cm from each other and at least 30 cm
from the top of the wall, in order to assure a correct fixation.
Single extra supports, ref: AT-031B, AT-041B respectively.
AT-042B Application AT-032B Application
AT-042B
AT-032B
31 PARALLEL ANCHORAGE
Reference Dimensions (mm) Included Material Weight (Kg)
AT-052B 2 x (50 x 90 x 340) 2 supports Galvanized steel 5
AT-053B 3 x (50 x 90 x 340) 3 supports Galvanized steel 7,5
AT-062B 2 x (50 x 90 x 165) 2 supports Galvanized steel 5
AT-063B 3 x (50 x 90 x 165) 3 supports Galvanized steel 7,5
Meets with UNE 21186, NFC 17102
Double bracket anchoring system, for fixing 1 - 1 mast in parallel to a handrail or pipe. The anchorages need a minimum separation of 60 cm from each
other, in order to assure a correct fixation.
Single extra support, ref: AT-051B , AT-061B respectively
See table 26
See table 26
AT-062B Application AT-052B Application
AT-062B
Meets with UNE 21186, NFC 17102
INTERCEPTION SYSTEMS AND ACCESORIES
EXTERNAL PROTECTION 33
Masts and anchorages
LAMPPOST ANCHORAGE 32
1 - 1 mast anchorage fixture adjustable for conic structures such as lampposts. The anchorages need a
minimum separation of 60 cm from each other, in order to assure a correct fixation.
Double bracket anchoring system, for fixing 1 - 1 mast in cross to a handrail or pipe. The anchorages need
a minimum separation of 60 cm from each other, in order to assure a correct fixation.
Due to the covers or cornices of the roofs, a substantial horizontal distance (from 60 to 80 cm) needs to
be avoided. In these cases it is necessary to use the extendable tube. The anchorages need a minimum
separation of 60 cm from each other, in order to assure a correct fixation.
Single extra support, ref: AT-067B
Single extra support, ref: AT-071B
Single extra support, ref: AT-077B
Reference Dimensions (mm) Included Material Weight (Kg)
AT-068B 2 x (50 x 90 x 190) 2 supports Galvanized steel 6
AT-069B 3 x (50 x 90 x 190) 3 supports Galvanized steel 9
Reference Dimensions (mm) Included Material Weight (Kg)
AT-072B 2 x (170 x 170 x 200) 2 supports Galvanized steel 5,8
AT-073B 3 x (170 x 170 x 200) 3 supports Galvanized steel 8,7
Reference Dimensions (mm) Included Material Weight (Kg)
AT-078B 2 x (300 x 450 x 800) 2 supports Galvanized steel 14
AT-079B 3 x (300 x 450 x 800) 3 supports Galvanized steel 21
AT-068B Application
Meets with UNE 21186, NFC 17102
Meets with UNE 21186, NFC 17102
Meets with UNE 21186, NFC 17102
AT-072B Application
AT-078B Application
CROSS SHAPED ANCHORAGE 33
See table 26
See table 26
See table 26
ADJUSTABLE ANCHORAGE 34
INTERCEPTION SYSTEMS AND ACCESORIES
EXTERNAL PROTECTION 34
Masts and anchorages
35 MAST TO POST ANCHORAGE
Suitable to fix a 1 - 1 mast to a 25 cm square or round post. The anchorages need a minimum separation of 60 cm from each other and at least 30 cm
from the top of the wall, in order to assure a correct fixation.
1 - 1 mast anchorage fixture suitable for chimney in operation. The isolation of the anchorage is necessary
in order to maintain the difference of potential between the parts of the Dat Controler
Plus has to be mounted at least 2 m below the hole of the chimney to avoid the heat of the gases
deforming the structure of the mast and quickening its corrosion rate. The anchorages (AT-088B) have to be
mounted right in the threaded union between the Dat Controler
PLUS
50 x 520
x 1000
Galvanized steel 7,5
AT-088B
DAT CONTROLER
DYNAMIC ELECTRODE
Reference External size (mm) Shape Included Material Weight (kg)
AT-024H 2000 x 28 Vertical AT-020F + AT-031L Copper + Salts 4
AT-025H 2500 x 28 Vertical AT-020F + AT-031L Copper + Salts 4,5
AT-012H (1000 + 2000) x 54 L-shaped AT-020F + 2 x AT-032L Copper + Salts 62,5
AT-030H (1000 + 3000) x 54 L-shaped AT-020F + 2 x AT-032L Copper + Salts 67
AT-032H 2000 (roscado) x 54 Vertical AT-020F + 2 x AT-032L Copper + Salts 58,5
AT-033H 3000 (roscado) x 54 Vertical AT-020F + 2 x AT-032L Copper + Salts 62,5
AT-102H 2000 x 28 Vertical AT-031L Copper + Salts 4
AT-103H 2500 x 28 Vertical AT-031L Copper + Salts 4,5
AT-108H (1000 + 2000) x 54 L-shaped 2 x AT-032L Copper + Salts 62,5
AT-104H (1000 + 3000) x 54 L-shaped 2 x AT-032L Copper + Salts 67
AT-105H 2000 x 54 Vertical 2 x AT-032L Copper + Salts 58,5
AT-106H 3000 x 54 Vertical 2 x AT-032L Copper + Salts 62,5
AT-035H 190 x 220 Charge for APLIROD
Salts 5,5
Meets UL 467, IEC 62305, EN 50164, UNE 21186, NFC 17102
The absence of free ions in the surrounding soil damages the proper
performance of the earthing. Dynamic Electrodes are based on the
contribution of ions to the ground.
The system consists mainly of a conductive electrode (APLIROD
) made of
copper and filled with a mixture of ionic compounds. The moisture condenser
absorbs environmental moisture and leaches out at the bottom of the rod,
lowering gradually the resistivity of the surrounding soil:
The efficacy of this earth electrode is improved by placing a ground
conductivity improver such as CONDUCTIVER PLUS
to 8 litres
of water. The mixture fills the perforation up.
4. Place the electrode in the hole so that the upper end is approximately
20cm below the surface. The filling will expand in few minuts.
5. Place the inspection pit so that the cover remains at surface level. The
electrode will stand out approximately 10 cm over the bottom of the
inspection pit, leaving the breathing holes uncovered.
6. WIthdraw the covers of the upper breathing holes.
7. Conect the grounding electrode to the test bonding bar.
8. More electrodes should be places at even intervals, and interconnected
with bare copper, buried at least 0.5m deep. Its is recommended to cover
the conductor with APLIFILL
.
EARTH ELECTRODES, GROUND ENHANCING PRODUCTS AND EARTH PITS
EARTHING 257
AT-025H AT-103H
AT-104H
AT-035H APLIROD
(description)
APLIROD
(description)
AT-030H
Low
resistivity
compound
APLIFILL
Breathing
holes
Ionic
mixture
Leach holes
Moisture
condenser
EARTH ELECTRODES, GROUND ENHANCING PRODUCTS AND EARTH PITS
EARTHING 258
ENHANCED ELECTRODES FOR LOW-CONDUCTIVITY SOILS
GRAPHITE ELECTRODE
Graphite, with its high electrical and thermal conductivity, being unattackable and inert to chemical agents (apart from oxygen at a high temperature), is a very
good element to make an earth electrode. The materials used such as perforation filling (graphite powder and thin clay-like powder) assure the contact between
the electrode and the ground thanks to the capacity to even penetrate into rocky cracks.
INSTALLATION
This electrode is formed of a rigid graphite core surrounded by a layer of
graphite powder and salts, which whilst helping to avoid mechanical damage
during transportation and installation, also improves the conductivity of the
electrode. This ensemble is introduced into the perforation, which connects
to the test bonding bar installed in the earth pit, using cable of 8-10mm or
tape of 302mm.
In order to optimize its duration and effectiveness, the hole should be filled
with thin clay-like powder and special graphite powder for earthing:
Perforation of 200mm
Machinery needed:
Perforator with drill of 200mm and 2 meters length.
Mixer (recommended).
Material:
2kg of graphite powder (AT-020L).
6kg of thin clay-like powder (AT-030L).
PROCEDURE:
1. Make a perforation of 200mm with a depth of at least 2 meters.
2. Connect to the electrode the necessary length of cable of 8-10mm
or tape of 302mm to be able to make the connections in the earth pit
afterwards.
3. In an adequate recipient (preferably a mixer), mix the fine clay-like powder
(AT-030L) and the graphite powder (AT-020L) with 60 litres of water.
Note: If a mixer or adequate tool is not available, the filling of the
perforation will be done in batches. For example, the filling can be done
in four batches, using each time approximately 15 litres of water, 1,5kg of
thin clay-like powder and 0,5kg of graphite powder.
4. Empty the mixture into the perforation, making sure it reaches the bottom
of the hole.
5. Install the electrode with the wrapping in the perforation, being careful of
not making strong impacts.
6. Make the necessary connections to the test bonding bar installed in the
earth pit and close.
Hole of 1,5 1,5 2 meters
Machinery needed:
Retroexcavator.
Material:
2 bags of graphite powder 25kg (AT-020L).
6 bags of thin clay-like powder of 25kg (AT-030L).
Plenty of water.
PROCEDURE:
1. With the retroexcavator make a hole of 1,5 meters of width and 2 meters
of depth.
2. Mix two bags of thin clay-like powder (AT-030L) and enough earth to
sufficiently cover approximately 30cm height of the hole. Fill the bottom
of the excavation.
3. Connect to the electrode, the necessary meters of cable of 8-10mm or
tape of 302mm to be able to make afterwards the connections in the
earth pit.
4. Install the electrode with the wrapping in the perforation, being careful of
not making strong impacts.
5. Cover with water until you reach a level of 10 cm (approximately 225 litres
of water). Wait a few minutes for the filter of the water and the increase in
volume of the thin clay-like powder.
6. Continue filling the hole mixing a bag of thin clay-like powder, half a bag of
graphite powder and enough earth to fill another 30 cm of height. Empty
the mixture into the hole evenly.
7. Repeat steps 5 and 6 until you have used up the thin clay-like powder and
the graphite (3 times).
8. Make the necessary connections in the test bonding bar installed in the
earth pit and close.
Reference External size (mm) Shape Included Weight (kg)
AT-070H 600 x 150 Rigid graphite core + graphite powder with bag AT-020F 10
AT-073H 1500 x 50 Rigid graphite core AT-020F + AT-032L 35
AT-070H
AT-070H Application
1 bag of thin clay-
like powder 25kg
1/2 bag of graphite
powder 25kg
Soil
Water
2 bags of
thinclay-like
powder of 25kg
EARTH ELECTRODES, GROUND ENHANCING PRODUCTS AND EARTH PITS
EARTHING 259
AT-003K
AT-002K
AT-072H
AT-041H
AT-041H Application
AT-041H (aplicacin tierras)
254m COPPERBOND EARTH RODS
Aplicaciones Tecnolgicas, S.A. has available copperbond earth rods of a
high quality which comply to the most demanding regulations, for efficient and
long lasting earthing. All these electrodes have a covering of electrolytic copper
with a width of 254m and purity 99,9% which allows a proven resistance to
corrosion. This type of electrolytic covering does not produce cracks or fissures,
which are produced in the exterior layer of the copperclad rods, worsening its
resistance to corrosion.
Numerous regulations specify that on the copperbond earth electrodes the
covering of copper should be at least 250m. This especially applies to the
regulations on lightning protection systems:
BS 7430: Code of practice of earthing.
UL 467: Grounding and bonding equipment.
Section 250 of National Electrical Code (NEC).
Application technical guide n 18 of Spanish Low Voltage Electrotechnical
Regulation.
IEC 62305-3 (international lightning protection standard).
EN 50164-2 (european lightning protection components standard).
UNE 21186 (spanish lightning protection standard).
Using the adequate accessories, threaded copperbond earth rods allow the
extension of the rod to get better earthing resistances.
INSTALLATION
The electrodes should be installed to a depth of at least 50cm.
It is preferable to use various conductors conveniently spread rather than only
one very long earth conductor.
In the case of an earth formed by various interconnected electrodes, it is
recommended that:
The buried rods are in a triangle or line and spaced out with a distance
apart of at least the same as the depth buried.
The buried rods are connected by an identical or compatible conductor
to the one used for the down-conductor.
The conductor which joins the rods is buried with a depth of at least 50cm.
Apply the ground enhancing product CONDUCTIVER PLUS
(AT-010L)
to the buried electrodes in order to obtain a lower earthing resistance.
Couplings of copperbond earth rods
Reference Denomination Nominal size (mm) Material
Weight (gr)
AT-002K 5/8" Threaded coupling 70 x 19 Aluminium Bronze 80
AT-003K 5/8" Threaded driving stud 54 x 22 Stainless steel 80
AT-004K 3/4" Threaded coupling 70 x 24 Aluminium Bronze 130
AT-005K 3/4" Threaded driving stud 54 x 25 Stainless steel 130
Reference Nominal size (mm) Shank diameter (mm) Shape
Weight (kg)
AT-076H 1200 x 16 14,23 Two threads 5/8" 1,5
AT-077H 1500 x 16 14,23 Two threads 5/8" 1,9
AT-078H 1800 x 16 14,23 Two threads 5/8" 2,28
AT-041H 2000 x 16 14,23 Two threads 5/8" 2,53
AT-016H 2400 x 16 14,23 Two threads 5/8" 3
AT-098H 3000 x 16 14,23 Two threads 5/8" 3,8
AT-069H 1200 x 14,23 14,23 No thread 1,5
AT-071H 1500 x 14,23 14,23 No thread 1,9
AT-053H 1800 x 14,23 14,23 No thread 2,28
AT-072H 2000 x 14,23 14,23 No thread 2,53
AT-026H 2400 x 14,23 14,23 No thread 3
AT-043H 3000 x 14,23 14,23 No thread 3,8
AT-086H 1200 x 19 17,28 Two threads 3/4" 2,15
AT-087H 1500 x 19 17,28 Two threads 3/4" 2,75
AT-017H 1800 x 19 17,28 Two threads 3/4" 3,27
AT-042H 2000 x 19 17,28 Two threads 3/4" 3,62
AT-018H 2400 x 19 17,28 Two threads 3/4" 4,35
AT-019H 3000 x 19 17,28 Two threads 3/4" 5,44
AT-079H 1200 x 17,28 17,28 No thread 2,15
AT-081H 1500 x 17,28 17,28 No thread 2,75
AT-027H 1800 x 17,28 17,28 No thread 3,27
AT-082H 2000 x 17,28 17,28 No thread 3,62
AT-028H 2400 x 17,28 17,28 No thread 4,35
AT-029H 3000 x 17,28 17,28 No thread 5,44
Meets BS 7430, UL 467, IEC 62305, EN 50164, NFPA 780, UNE 21186, NFC 17102
Other copper thickness as 100m and 300m are available on request.
dL
L
L
50 cm
L dL
EARTH ELECTRODES, GROUND ENHANCING PRODUCTS AND EARTH PITS
EARTHING 260
SOLID COPPER EARTH RODS
STAINLESS STEEL EARTH RODS
Solid copper and stainless steel rods allow a long lasting earth in grounds with high corrosion level. Threaded electrodes with the correct accessories allow
the length to be increased, thus achieving a better resistance.
AT-031H
AT-006K
AT-007K AT-008K
AT-080H
AT-038H
AT-031H application
Reference Nominal size (mm) Shape Weight (kg)
AT-031H 1200 x 15 Internal 5/8" thread 1,63
AT-036H 1200 x 20 Internal 3/4" thread 3,35
Reference Nominal size (mm) Shape Weight (kg)
AT-000H 1500 x 10 No thread 1,5
AT-099H 1000 x 16 No thread 1,6
AT-100H 1500 x 16 No thread 2,2
AT-080H 2000 x 16 No thread 3,33
AT-038H 1500 x 20 Extensible type AZ 3,75
AT-037H 1200 x 16 Internal 5/8" threads 1,65
Couplings of solid copper and stainless steel earth rods
Reference Denomination Nominal size (mm) Material Weight (kg)
AT-006K 15/16mm Driving stud 39 x 14 Stainless steel 40
AT-007K 15/16mm Spike 42 x 14 Stainless steel 40
AT-008K Coupling dowel 40 x 10 Stainless steel 20
AT-009K 20mm Driving stud 42 x 19 Stainless steel 60
AT-042K 20mm Spike 55 x 19 Stainless steel 80
Meets BS 7430, UL 467, IEC 62305, EN 50164, NFPA 780, UNE 21186, NFC 17102
Meets BS 7430, UL 467, IEC 62305, EN 50164, NFPA 780, UNE 21186, NFC 17102
Meets EN 50164
AT-038H application
EARTH ELECTRODES, GROUND ENHANCING PRODUCTS AND EARTH PITS
EARTHING 261
Galvanized steel rods are a good option to obtain low resistances in unaggresive grounds. There are extendable models to reach longer lengths and achieve
better earth resistances.
AT-045H
AT-003H
AT-037K
AT-046H
AT-095H
AT-000K
AT-003H application
GALVANIZED STEEL EARTH RODS
GOOSE FOOT
Reference Nominal size (mm) Shape Weight (kg)
AT-039H 1000 x 16 No thread 1,65
AT-044H 1500 x 16 No thread 2,53
AT-045H 2000 x 16 No thread 3,42
AT-046H 1500 x 20 Extensible type Z 3,71
AT-003H 1500 x 20 Extensible type S 3,71
AT-047H 1500 x 25 Extensible type Z 5,62
AT-049H 1500 x 25 Extensible type S 5,62
AT-093H 1000 x 50 x 50 x 5 X-shaped profile 3,9
AT-094H 1500 x 50 x 50 x 5 X-shaped profile 5,85
AT-095H 2000 x 50 x 50 x 5 X-shaped profile 7,81
AT-096H 2500 x 50 x 50 x 5 X-shaped profile 9,75
AT-097H 3000 x 50 x 50 x 5 X-shaped profile 11,75
Reference Nominal size Material Weight (kg)
AT-000K 30 x 2 mm (4 m + 3 x 7m) Tin-plated Copper Tape 13
AT-001K 30 x 2 mm (1 m + 3 x 3m) Tin-plated Copper Tape 5
Couplings of galvanized steel earth rods
Reference Denomination Nominal size (mm) Material Weight (kg)
AT-037K Impact tip for earth rods 20mm 40 x 20 Galvanized steel 50
AT-038K Impact tip for earth rods 25mm 45 x 25 Galvanized steel 70
Meets DIN 48-452
Meets EN 50164
Meets UNE 21186, NFC 17102
The duck foot is a configuration that the regulation of Lightning Protection UNE 21186 and NFC 17102 recommends in
order to obtain low earth inductances. It is formed with tin-plated copper tape of 30x2mm.
Installation:
Make ditches of at least half a meter depth.
Extend the tape and cut the corresponding lengths.
Unscrew the clamp and introduce the stretches of tape as indicated in the drawing with an angle of 45.
Firmly fix the screws of the clamp.
AT-095H application
EARTH ELECTRODES, GROUND ENHANCING PRODUCTS AND EARTH PITS
EARTHING 262
EARTH PLATES
COPPER LATTICES AND GRIDS
AT-116H (Cu)
AT-122H (GS)
AT-070J AT-126H
The use of earth plates as electrodes reduces the resistance of earthing in stony grounds, as it increases the area of contact between the electrode and the
ground.
The references AT-116H and AT-122H comply with the minimum dimensions recommended in the n18 Technical Application Guide Earthing installations of
the 2002 Low Voltage Spanish Electrotechnical Regulation.
Reference Nominal size (mm) Included Material Weight (kg)
AT-050J 500 x 500 x 2 AT-020F Copper 4
AT-116H 1000 x 500 x 2 AT-020F Copper 8
AT-117H 600 x 600 x 1,5 - Copper 5
AT-118H 600 x 600 x 3 - Copper 10
AT-119H 900 x 900 x 1,5 - Copper 11
AT-120H 900 x 900 x 3 - Copper 22
AT-121H 500 x 500 x 3 - Galvanized steel 4
AT-122H 1000 x 500 x 3 - Galvanized steel 8
Meets IEC 62305, EN 50164, EN 13601, BS 2874, UNE 21186, NFC 17102, NFPA 780
Meets IEC 62305, EN 50164, EN 13601
Reference Nominal size (mm) Grids Weight (kg)
AT-128H 1000 x 1000 x 2 115 x 55 mm 3
AT-123H 2000 x 1000 x 2 115 x 55 mm 4
AT-070J 3000 x 1000 x 2 115 x 55 mm 5
AT-126H 600 x 600 x 3 120 x 120 mm 4
AT-125H 900 x 900 x 3 190 x 190 mm 7,3
Mesh earths are a more economical option than earth plates and still work well in stony ground, reducing the contact voltages that may occur. AT-070J is
recommended to avoid step voltages in public buildings with low resistivity soil.
EARTH ELECTRODES, GROUND ENHANCING PRODUCTS AND EARTH PITS
EARTHING 263
AT-010L
AT-032L
Meets EN 50164, UNE 21186, NFC 17102
CONDUCTIVER PLUS is a non corrosive ground enhancing gel with low solubility but is very hygroscopic. It is made of an electrolyte base, which
contributes to the conductivity of the mixture.
The conductivity of the ground is almost exclusively of an electrolytic nature due to the salts dispersed in the water which impregnate it and which concentrate
on the surface due to an adhesive phenomenon of the sand grains and clay in the ground.
Therefore, it is possible to increase the conductivity of the ground, improving its absorption power, retention of water and increasing its richness in soluble salts.
It would be very easy to achieve this effect using a simple method, impregnating it with any electrolyte, such as common salt (NaCl) or sodium carbonate
(Na
2CO3), but the high solubility of these salts, as well as their low absorption in the ground mean that they are very quickly swept away by the infiltration waters,
making their action very short term. Another inconvenience of common salt is its corrosive effects on the earthing electrodes.
The components of the CONDUCTIVER PLUS
gel have been selected according to their solubility, in order to obtain from the soluble components, a low
soluble product, which will provide us with a long lasting conductor product deposit. The main advantage of this product is that a conductor gel is formed
below the soil near the electrode.
In summary, the CONDUCTIVER PLUS
EXOTHERMIC WELDING
EXOTHERMIC WELDING 278
EXOTHERMIC WELDING: APLIWELD
The Apliweld
Reference Description
68N Basic tool kit
69N 67N Double brush renewals
70N Flint igniter renewals 10u.
71N Sealer compound (2,25 Kg.)
72N Cable adapter sleeve (25 units)
72NC35 Cable adapter sleeve 35 mm
2
(25 units)
72NC50 Cable adapter sleeve 50 mm
2
(25 units)
72NC70 Cable adapter sleeve 70 mm
2
(25 units)
73N Safety gloves
74N Flint ignitor extension
75N Fire torch
76N Butane gas clynder 0,4L
77N Safety googles
79N Earth rod to earth rod clamp
80N Tool box
81N Ceramic tray
82N Vertical stand pliers
83N Ceramic sheet
84N Mini-blowtorch
85N Mini-blowtorch renewals
89N Cavity sealer
6089N 60 cavity sealers bag
TMS Multiple mould crucible
CHMS MMS horizontal lower piece
CVMS T14 MMS vertical lower piece for 14.3mm e.rod
CVMS T16 MMS vertical lower piece for 15.9mm e.rod
CVMS TX
MMS vertical lower piece for Xmm e.rod
X= required diameter.
Reference Description
E0032
10 welding mixtures of 32 grams +
10 starting powder + 10 metallic disks
E0045
10 welding mixtures of 45 grams +
10 starting powder + 10 metallic disks
E0065
10 welding mixtures of 65 grams +
10 starting powder + 10 metallic disks
E0090
10 welding mixtures of 90 grams +
10 starting powder + 10 metallic disks
E0115
10 welding mixtures of 115 grams +
10 starting powder + 10 metallic disks
E0150
10 welding mixtures of 150 grams +
10 starting powder + 10 metallic disks
E0200
10 welding mixtures of 200 grams +
10 starting powder + 10 metallic disks
E0250
10 welding mixtures of 250 grams +
10 starting powder + 10 metallic disks
50N
Universal Handle Clamp
for the 90% of connections
51N Vertical surfaces and pipes handle clamp
52N Rail base Handle Clamp
53SN Multiple mould handle clamp
54N Rail head and web handle clamp
58N Horizontal surface clamp accessory
59N Holding cable clamp
60N Flint Igniters
61N Conductors cleaning brush
62N Vertical moulds cleaning brush
63N Slag Scraper
64N Welding cavity clearing brush
65N Sealer compound (0,45Kg)
66N Sealer compound (0,9Kg)
67N Double brush for conductor cleaning
Codes for multiple mould.
Codes for specifc moulds.
1 2 3
4 5 6
7
1 2 3 4
EXOTHERMIC WELDING 281
INSTRUCTIONS FOR USE
Place the conductors in the mould and close
the handle clamps to avoid material leakages
during the reaction.
Obstruct the tap hole with the metallic disk. Empty the contents of the welding mixture
package.
Ignite the starting powder extended on the
side of the mould using the flint igniters.
Once started, the reaction will take 3-4
seconds during which it is recommended to
stand back the mould.
Empty 50% of the starting powder on the side
of the mould as a fuse, scattering the rest into
the welding mixture. Close the mould lid.
Place the correct inferior piece
and first cavity sealer.
Put t he c or r es pondent
conductors to be joined, and
then another cavity sealer.
Cl ose t he moul d cover.
Fol l owi ng st eps i ncl udi ng
ignition and clean up jobs are
similar to the case of specific
moulds.
Carefully remove the cavity
sealer to check the result. Be
aware: the system is at an
extremely high temperature.
M
U
L
T
I
P
L
E
M
O
U
L
D
S
P
E
C
I
F
I
C
M
O
U
L
D
Once open, clean the slag stick to
the mould with the relevant clearing
brush. Then the mould will be ready
to be used again without having to
reheat it with a gas welding torch, as
explained before.
PROCESS TO OBTAIN AN APLIWELD
WELDING
The material to be welded (cable, rod, tape...) must be clean and dry using the brush included in the set
of accessories. Then the oxide layer and superficial impurity is eliminated.
Given that the graphite mould also absorbs moisture, this should be removed by preheating with a gas
welding torch to avoid a porous welding. After the first welding is done, it is not necessary to re-heat the
mould if the next welding is done within 15 minutes as it conserves the previously generated heat.
EXOTHERMIC WELDING 282
The multiple mould parts should be purchased
separately or in a suitcase. The references and
the components vary only in part for rod, which
diameter has to be specified:
MULTIPLE MOULD
The Apliweld
v2
Local detection of every stage of the storm thus allowing several tens of
minutes time for taking all the pre-established preventive actions.
No mobile parts thus avoiding breakdowns and service interruptions.
No special maintenance required.
Configurable detection thresholds according to the user necessities.
Universal outputs allowing connection to any alarm device, control
devices, etc.
With specific control software.
Internet connectable.
Integration of several detectors through an included licence ATSTORM
v2 WEB.
Possibility of GSM modem allowing SMS messages to be sent to cell
phones with data or alarms.
Possibility to achieve an efficient sound warning when there is a risk of
thunderstorm with amplifiers and repeaters.
v2
PREVENTIVE PROTECTION 291
An important concept
PREVENTIVE PROTECTION against lightning storms
Who is it for?
Preventive protection means having information in advance (from a storm
detector) that allows the user to start temporary preventive measures before
the storm begins. These measures will be deactivated after the storm.
Preventive protection will be complementary to an installed Lightning
Protection System (LPS) in certain situations, while in others it will be
sufficient to act alone.
Having information about lightning storms is especially convenient for taking
decisions in some of the following situations involving people in open areas,
sensitive goods, losses in industrial procedures, guarantee of basic services,
infrastructures, civil defence organization, environmental protection,
accidents in workplaces, open areas structures
The most advanced
technological solution
All storm stages
detection /No mobile
parts
The most efficient method of detecting storms locally is to measure the
evolution of the electric field. Traditionally, the so-called field mills have
been employed. However, these detectors have got several disadvantages,
mainly due to their mobile parts, which cause obstruction and wear and tear
overtime. In order to solve these problems, Aplicaciones Tecnolgicas, S.A.
has developed and world patented the highly innovative purely electronic
detector, called ATSTORM
v2 series values
can be modified to the users needs.
All stages of a storms evolution can be viewed.
The alert type can be customized for each level of alarm.
The sensor with FCES technology is connected to the interface with a
communication cable.
It is designed to ensure the sensor is working correctly even in difficult weather
conditions and must be installed in the open air.
The sensor does not require calibration related to its height prior to installation.
The interface is configured with the following alarm levels (recommended
levels, suitable for every installation) that may be changed according to the
placement or to the users necessities:
* See Annex I: Lightning storms
** See Annex II: Storm detection
tecnhologies
Touchscreen for easy
use.
Interface between the
sensor and the screen.
Alarm
Level
Electric field
value
Description
LEVEL 0 < 3 kV/m No alert
LEVEL 1 3 a 4 kV/m Alert
LEVEL 2 4 a 7 kV/m Emergency
STORM > 7 kV/m Maximum risk
ATSTORM
v2 STORM DETECTOR. Characteristics.
The interface has to be connected to the sensor in order to:
Ensure a continuous power supply to the sensor.
Record the data.
It is equipped with membrane switches
and a display for easy use.
PREVENTIVE PROTECTION 295
ATSTORM
v2
STORM DETECTOR.
MAIN ADVANTAGES
The main advantages of ATSTORM
v2
Technical Specifications
* Variable according to installation.
PREVENTIVE PROTECTION 296
Electronic module with 4 contact-free outputs
An electronic module with 4 contact-free outputs
(2A, 250V) is included. These outputs can be
employed at the users convenience: for connection
to a sonorous alarm or to UPS equipment or
for warning about possible interruptions in the
communication between the interface and the
sensor.
Many other parameters can also be established by the user, such as the alert corresponding to each relay, the reaction delay after the alert or the time that the
alarm remains active, as in the following figure:
Software
ATSTORM
v2 is provided with
its own software that should
be installed in a computer
that will be connected to the
interface through Ethernet,
having the same advantages
as with the touchscreen:
a) Data saving:
Data frequency storage depending on the alarm levels.
Alerts about communication failures between the sensor and the
interface or the interface and the PC.
b) Long term analysis of the electric field evolution and the frequency and
effects of lightning storms within the area.
c) Verication of alarm activation when the electric field is maintained for
a predefined length of time.
ATSTORM
v2 is connectable
to a network, therefore
2 different licences are
available:
ATSTORM
v2 WEB
This option is included with the equipment, allowing a connection between
the ATSTORM
v2 NET
Several ATSTORM
v2 NET
Ref.: AT-521
ATSTORM
v2 SPECIAL ACCESSORIES
INSTALLATION AND MAINTENANCE
The sensor works with FCES (Field-Controlled Electrometric Sensor) technology thus
measuring the electrostatic eld without employing mechanical elements.
The detector has to be installed in places situated far away from any elements that deform the electric
field such as trees, metallic structures or power supplies.
Measurements are independent of the height where it is placed. There is thus no need for calibration
according to height and no problems with the installation.
Mast, anchorages and corrugated tube for protecting the communication cable, are included with the
storm detector.
ATSTORM
V2 is easy to install
and no special maintenance is needed.
Sensor head
Connection
cable
Interface
PREVENTIVE PROTECTION 298
ANNEX I: LIGHTNING STORMS
In normal conditions, there is a balance between positive and negative
charges in the atmosphere, where the earth is more negatively charged
than the atmosphere and the elements situated on the ground.
The stages and phenomena that
characterize a lightning storm
can be summarized as follows:
However,
the formation of storm clouds
creates a charge polarisation:
The lower part of the cloud is charged negatively producing a positive
charge on the ground and any elements on it. This can form an electrical
charge in the atmosphere in excess of tens of kilovolts.
When the electrical field becomes intense enough, the cloud begins
to discharge the energy towards the ground. The path formed by this
discharge is called the downward leader and produces a fast variation
in the electrical field. This is the process of lightning formation.
PHASE 1:
The charge separation can
be detected at ground level
before t he fi rst l i ght ni ng
discharge using electric eld
measuring devices.
PHASE 3:
Intra-cloud discharges are
often followed by the cloud-
to-ground discharges, that
are associated to a more
mature phase of the storm.
PHASE 4:
When the storm is over, then
the electric field decreases.
PHASE 2:
After the first electrification, the
first discharges occur. In most
cases the first discharges are
intra-cloud type.
PREVENTIVE PROTECTION 299
ANNEX II: STORM DETECTION TECNHOLOGIES
Storm detectors can generally be classified into two groups:
lightning strike detectors and electric field measuring detectors.
LIGHTNING STRIKE DETECTORS: these provide information about already-occurred lightning strikes thus warning about distant storms that are
approaching.
ELECTRIC FIELD MEASURING DETECTORS: they give information about the local electric eld, from which the possibility of lightning strikes can
be deduced. Therefore, no rst lightning strike is required for getting an alert.
Detection by radiofrequency or electromagnetic eld record
Characteristics: Detectors by radiofrequency recognize the electromagnetic variations caused by lightning when crossing the atmosphere from the cloud
to the ground. They are efficient for detecting distant storms.
Disadvantages: they are not able to detect storms that are forming just over the detector since they can only detect the storm when electric discharges
already exist, not in the initial phases. Therefore, there is no time for taking early preventive actions if the first lightning strikes are in or close to the area to
be protected.
FIeld mills
Characteristics: They are detectors containing not electronic but mechanical sensors. They measure the electrostatic field continuously thus detecting
small (quitar) field variations coming both from the storm approaching or from its formation over the detector.
Disadvantages: The main inconvenience of this type of detectors is having a mechanical sensor. The measurement employs a rotatory motor that must
work 24 hours a day. If the motor stops due to malfunctioning, damage, obstruction, etc then the sensor becomes out of service, not giving the necessary
information for preventive purposes. They are high electricity consumers due to the continuously operating motor. As well as this, periodical maintenance
and cleaning of certain elements is required, especially in salty environments, in order to minimize measurement errors.
Field-Controlled Electrometric Sensor (technology used by ATSTORM
v2)
Aplicaciones Tecnolgicas, S.A. has developed and patented the Field-Controlled Electrometric Sensor (FCES) in order to overcome the problems of
the traditional field mills. ATSTORM
v2, based on the FCES technology, is a totally electronic eld measuring detector, without mobile parts,
robust and with maximum reliability.
DISADVANTAGES OF OTHER SYSTEMS ADVANTAGES OF ATSTORM
v2
FIELD MILLS
Due mainly to their mobile parts they are exposed to many problems
(obstructions, wear and tear, out of service time due to maintenance,
etc.).
Fully electronic, no mobile parts that could be affected by wear and
tear or external factors. ATSTORMv2 always responds and needs
no special maintenance.
ELECTROMAGNETIC DETECTORS
The main problem is that they need lightning discharges to occur in
order to detect a storm, so their alert may arrive too late in the case
where the storm is forming just over the place to be protected.
No previous discharges are required to have occurred. Even the
earliest stages of the storm are detected thus providing information
in advance and allowing the preventive measures to be adopted.
The best existing tool for preventive
protection against the effects of lightning.
The sensor detects all the stages of the
lightning storm formation.
Offers an essential time period for
adopting specific preventive measures.
Based on the new patented FCES
technology (Field-Controlled Electrometric
Sensor) where all components are
electronic.
No need for special maintenance.
Fully operational in bad weather
conditions.
Programmable alarm levels.
EXTERNAL PROTECTION 300 INDEX PAR LIGNE DE PRODUITS INDEX BY PRODUCT LINE
Aplicaciones Tecnolgicas has a policy of continuing product development.
Therefore, this catalogue is subject to change without notice. Aplicaciones Tecnolgicas, S.A. is not responsible
for any possible printing errors that may appear in the catalogue. Reproduction in any form whatsoever is
forbidden without Aplicaciones Tecnolgicas, S.A. authorisation.
2010 Aplicaciones Tecnolgicas, S.A. Legal deposit. V xxxx 2010
EXTERNAL PROTECTION 301 INDEX PAR LIGNE DE PRODUITS INDEX BY PRODUCT LINE
INDEX BY PRODUCT LINE
EXTERNAL
PROTECTION
INTERNAL
PROTECTION
EARTHING EXOTHERMIC
WELDING
PREVENTIVE
PROTECTION
PAGE 5 PAGE 81 PAGE 251 PAGE 277 PAGE 289
EXTERNAL PROTECTION 302 INDEX PAR LIGNE DE PRODUITS INDEX BY PRODUCT LINE
INTERCEPTION SYSTEMS AND ACCESORIES
ESE AIR TERMINAL
DAT CONTROLER
PLUS 15 - PDC 18
AT-1530 DAT CONTROLER
PLUS 30 - PDC 18
AT-1545 DAT CONTROLER
PLUS 45 - PDC 18
AT-1560 DAT CONTROLER
PLUS 60 - PDC 18
TRAZOR - PDC AIR TERMINAL
AT-1465 TRAZOR T- PDC / 5 22
AT-1467 TRAZOR T- PDC / 7 22
AT-1469 TRAZOR T- PDC / 9 22
AT-1470 TRAZOR T- PDC / 10 22
RODS AND MESHED CONDUCTORS
AIR TERMINATION ROD
AT-019A 20 x 400 mm chromed plated copper air termination rod 22
AT-023A 20 x 400 mm stainless steel air termination rod 22
AT-053L 20 x 300 mm stainless steel air termination rod 22
AT-055L 20 x 500 mm stainless steel air termination rod 22
AT-096A 20 x 1000 mm stainless steel air termination rod 22
AT-097A 20 x 300 mm chromed plated copper air termination rod 22
AT-098A 20 x 500 mm chromed plated copper air termination rod 22
AT-099A 20 x 1000 mm chromed plated copper air termination rod 22
AT-121A 16 x 300 mm stainless steel air termination rod 22
AT-122A 16 x 600 mm stainless steel air termination rod 22
AIR TERMINAL WITH MAST
AT-013A 1,4 m stainless steel air terminal with 1" mast 22
AT-014A 2,4 m stainless steel air terminal with 1" mast 22
AT-015A 1,4 m chromed plated copper air terminal with 1" mast 22
AT-016A 2,4 m chromed plated copper air terminal with 1" mast 22
AT-017A 2,4 m chromed plated copper air terminal with 1" mast 22
AT-024A 2,4 m stainless steel air terminal with 1" mast 22
TAPER POINTED AIR ROD
AT-004A 16 x 500 mm copper taper pointed air rod with M16 23
AT-005A 16 x 1000 mm copper taper pointed air rod with M16 23
AT-006A 16 x 2000 mm copper taper pointed air rod with M16 23
AT-007A 16 x 500 mm aluminium taper pointed air rod with M16 23
AT-008A 16 x 1000 mm aluminium taper pointed air rod with M16 23
AT-009A 16 x 2000 mm aluminium taper pointed air rod with M16 23
10 TAPER POINTED AIR ROD
AT-092A 16 x 500 mm copper taper pointed air rod with M10 23
AT-093A 16 x 1000 mm copper taper pointed air rod with M10 23
AT-094A 10 x 500 mm aluminium taper pointed air rod with M10 23
AT-095A 10 x 1000 mm aluminium taper pointed air rod with M10 23
THREADED LIGHTNING ROD
AT-114A 16 x 1500 mm aluminium threaded lightning rod with M16 23
AT-115A 16 x 2000 mm aluminium threaded lightning rod with M16 23
AT-116A 16 x 2500 mm aluminium threaded lightning rod with M16 23
AT-117A 16 x 3000 mm aluminium threaded lightning rod with M16 23
AT-118A 16 x 3500 mm aluminium threaded lightning rod with M16 23
AT-119A 16 x 4000 mm aluminium threaded lightning rod with M16 23
LIGHTNING ROD FOR WEDGE
AT-025A 16 x 750 mm galvanized steel lightning rod for wedge 24
AT-026A 16 x 1000 mm galvanized steel lightning rod for wedge 24
AT-027A 16 x 1250 mm galvanized steel lightning rod for wedge 24
AT-028A 16 x 1500 mm galvanized steel lightning rod for wedge 24
AT-029A 16 x 2000 mm galvanized steel lightning rod for wedge 24
AT-030A 16 x 2500 mm galvanized steel lightning rod for wedge 24
AT-031A 16 x 3000 mm galvanized steel lightning rod for wedge 24
AT-032A 16 x 1000 mm stainless steel lightning rod for wedge 24
AT-034A 16 x 1500 mm stainless steel lightning rod for wedge 24
AT-035A 16 x 2000 mm stainless steel lightning rod for wedge 24
AT-036A 16 x 1000 mm copper lightning rod for wedge 24
AT-037A 16 x 1500 mm copper lightning rod for wedge 24
AT-038A 16 x 1000 mm aluminium lightning rod for wedge 24
AT-039A 16 x 1500 mm aluminium lightning rod for wedge 24
AT-040A 16 x 2000 mm aluminium lightning rod for wedge 24
AT-041A 16 x 2500 mm aluminium lightning rod for wedge 24
AT-042A 16 x 3000 mm aluminium lightning rod for wedge 24
AT-043A 10 x 1000 mm aluminium lightning rod for wedge 24
AT-044A 16 x 1500 mm alum. lightning rod for wedge with reduct. 24
AT-045A 16 x 2000 mm alum. lightning rod for wedge with reduct. 24
AT-046A 16 x 2500 mm alum. lightning rod for wedge with reduct. 24
AT-047A 16 x 3000 mm alum. lightning rod for wedge with reduct. 24
SELF-SUPPORTING AIR TERMINATION ROD
AT-100A 3 m self supporting air termination rod 24
AT-101A 3,5 m self supporting air termination rod 24
AT-102A 4 m self supporting air termination rod 24
AT-103A 4,5 m self supporting air termination rod 24
AT-104A 5 m self supporting air termination rod 24
AT-105A 5,5 m self supporting air termination rod 24
AT-106A 6 m self supporting air termination rod 24
AT-107A 6,5 m self supporting air termination rod 24
AT-108A 7 m self supporting air termination rod 24
AT-109A 7,5 m self supporting air termination rod 24
AT-110A 8 m self supporting air termination rod 24
AT-111A 8,5 m self supporting air termination rod 24
GUNMETAL MULTI-POINT
AT-000A Gunmetal multi-point 25
COPPER MULTI-POINT WITH MAST
AT-001A Copper multi-point with mast 25
MULTI-POINT
AT-002A Stainless steel multi-point 25
AT-003A Copper multi-point 25
STRIKE PAD
AT-112A Copper strike pad 25
AT-113A Aluminium strike pad 25
FIXINGS
ADAPTING PIECE
AT-010A 1" mast naval brass adapting piece for cable 26
AT-011A 1" mast naval brass adapting piece for cable and tape 26
AT-012A 1" mast naval brass adapting piece for cable 26
AT-020A 1" mast stainless steel adapting piece for cable 26
AT-021A 1" mast stainless steel adapting piece for cable and tape 26
AT-022A 1" mast stainless steel adapting piece for cable 26
RIDGE SADDLE
AT-110B Gunmetal ridge saddle 26
AT-111B Aluminium ridge saddle 26
AIR ROD BASE
AT-115B Gunmetal air rod base 27
AT-116B Aluminium air rod base 27
FLAT SADDLE
AT-112B 50 mm
2
gunmetal flat saddle 27
AT-113B 70 mm
2
gunmetal flat saddle 27
AT-114B 95 mm
2
gunmetal flat saddle 27
AT-124B M16 stainless steel flat saddle 27
AT-125B M20 stainless steel flat saddle 27
ROD BRACKETS
AT-104B Gunmetal rod brackets 27
AT-105B Aluminium rod brackets 27
ROD TO TAPE COUPLING
AT-100B Gunmetal rod to tape coupling 27
AT-101B Aluminium rod to tape coupling 27
REF. PRODUCT PAG. REF. PRODUCT PAG.
EXTERNAL PROTECTION 303 INDEX PAR LIGNE DE PRODUITS INDEX BY PRODUCT LINE
ROD TO CABLE COUPLING
AT-102B 50-70 mm
2
gunmetal rod to cable coupling 27
AT-103B 95 mm
2
gunmetal rod to cable coupling 27
VERTICAL AIR TERMINAL SADDLE
AT-122B Gunmetal vertical air terminal saddle 28
AT-123B Aluminium vertical air terminal saddle 28
HORIZONTAL AIR TERMINAL SADDLE
AT-120B Gunmetal horizontal air terminal saddle 28
AT-121B Aluminium horizontal air terminal saddle 28
NAVAL BRASS ROOF CLAMP
AT-011M Roof's ridge support 28
AT-022F Naval brass flat roof clamp 28
SPECIAL ROD SUPPORTS
AT-003M Vertical surface rod support 29
AT-030M Antenna's mast rod support 29
CONCRETE BASE
AT-029B 230 mm stackable wedged concrete base 29
AT-030B 325 mm stackable wedged concrete base 29
AT-095B 360 mm flat washer 29
AT-096B 270 mm flat washer 29
AT-097B 12 Kg threaded concrete base 29
AT-098B 16 Kg threaded concrete base 29
AT-099B 25 Kg threaded concrete base 29
MASTS AND ANCHORAGES
MASTS FOR WALL OR STRUCTURAL FIXING
AT-050A 1'' x 4 m galvanized steel mast 30
AT-051A 1'' x 1 m galvanized steel mast 30
AT-052A 1'' x 2 m galvanized steel mast 30
AT-053A 1'' x 3 m galvanized steel mast 30
AT-056A 1'' x 6 m galvanized steel mast (2 sections) 30
AT-057A 1'' x 6 m galvanized steel mast (3 sections) 30
AT-058A 1'' x 8 m galvanized steel mast 30
AT-060A 1'' x 1 m stainless steel mast 30
AT-062A 1'' x 2 m stainless steel mast 30
AT-063A 1'' x 3 m stainless steel mast 30
AT-066A 1'' x 6 m stainless steel mast (2 sections) 30
AT-067A 1'' x 6 m stainless steel mast (3 sections) 30
AT-068A 1'' x 8 m stainless steel mast 30
AT-085A 1'' x 4 m stainless steel mast 30
U SHAPED ANCHORAGE
AT-012B 30 cm U-shaped anchorage system to embed (1 support) 30
AT-013B 30 cm U-shaped anchorage system to embed (2 supports) 30
AT-014B 30 cm U-shaped anchorage system to embed (3 supports) 30
AT-015B 60 cm U-shaped anchorage system to embed (1 support) 30
AT-016B 60 cm U-shaped anchorage system to embed (2 supports) 30
AT-017B 60 cm U-shaped anchorage system to embed (3 supports) 30
AT-021B 30 cm U-shaped anchorage system to screw (1 support) 30
AT-023B 30 cm U-shaped anchorage system to screw (2 supports) 30
AT-024B 30 cm U-shaped anchorage system to screw (3 supports) 30
AT-025B 60 cm U-shaped anchorage system to screw (1 support) 30
AT-026B 60 cm U-shaped anchorage system to screw (2 supports) 30
AT-027B 60 cm U-shaped anchorage system to screw (3 supports) 30
ANGLE BAR ANCHORAGE
AT-034B 30 cm galvanized steel angle bar support (1 support) 31
AT-035B 30 cm galvanized steel angle bar support (2 supports) 31
AT-036B 30 cm galvanized steel angle bar support (3 supports) 31
AT-037B 60 cm galvanized steel angle bar support (1 support) 31
AT-038B 60 cm galvanized steel angle bar support (2 supports) 31
AT-039B 60 cm galvanized steel angle bar support (3 supports) 31
AT-044B 30 cm stainless steel angle bar support (1 support) 31
AT-045B 30 cm stainless steel angle bar support (2 supports) 31
AT-046B 30 cm stainless steel angle bar support (3 supports) 31
AT-047B 60 cm stainless steel angle bar support (1 support) 31
AT-048B 60 cm stainless steel angle bar support (2 supporst) 31
AT-049B 60 cm stainless steel angle bar support (3 supports) 31
MAST TO TRESTLE TOWER ANCHORAGE
AT-018B Mast to trestle tower anchorage (1 support) 31
AT-019B Mast to trestle tower anchorage (2 supports) 31
AT-020B Mast to trestle tower anchorage (3 supports) 31
LIGHT ANCHORAGE
AT-031B 30 cm light anchorage system to embed (1 support) 32
AT-032B 30 cm light anchorage system to embed (2 supports) 32
AT-033B 30 cm light anchorage system to embed (3 supports) 32
AT-041B 30 cm light anchorage system to screw (1 support) 32
AT-042B 30 cm light anchorage system to screw (2 supports) 32
AT-043B 30 cm light anchorage system to screw (3 supports) 32
PARALLEL ANCHORAGE
AT-051B Parallel anchorage system (1 support) 32
AT-052B Parallel anchorage system (2 supports) 32
AT-053B Parallel anchorage system (3 supports) 32
AT-061B H-shaped double bracket anchorage (1 support) 32
AT-062B H-shaped double bracket anchorage (2 supports) 32
AT-063B H-shaped double bracket anchorage (3 supports) 32
LAMPPOST ANCHORAGE
AT-067B Lamppost anchorage (1 support) 33
AT-068B Lamppost anchorage (2 supports) 33
AT-069B Lamppost anchorage (3 supports) 33
CROSS SHAPED ANCHORAGE
AT-071B Cross shaped anchorage (1 support) 33
AT-072B Cross shaped anchorage (2 supports) 33
AT-073B Cross shaped anchorage (3 supports) 33
ADJUSTABLE ANCHORAGE
AT-077B Adjustable anchorage (1 support) 33
AT-078B Adjustable anchorage (2 supports) 33
AT-079B Adjustable anchorage (3 supports) 33
MAST TO POST ANCHORAGE
AT-070B Mast to square post anchorage (1 support) 34
AT-074B Mast to square post anchorage (2 supports) 34
AT-075B Mast to square post anchorage (3 supports) 34
AT-076B Mast to round post anchorage (1 support) 34
AT-083B Mast to round post anchorage (2supports) 34
AT-086B Mast to round post anchorage (3supports) 34
ISOLATED CHIMNEY ANCHORAGE
AT-080B Chimney anchorage 4 DAT CONTROLER
PLUS 34
AT-081B DAT CONTROLER
DYNAMIC ELECTRODE
AT-012H APLIROD
256
AT-102H 28 x 2000 mm APLIROD
263
AT-032L 25kg bag APLIFILL
263
JOINT PROTECTION
AT-000J Self-vulcanising strip 264
AT-010J Denso tape (Bituminous strip) 264
EARTH PITS
AT-010H Polypropylene earth pit 264
AT-010K Concrete earth pit 264
AT-012K Iron cast earth pit 264
EQUIPOTENTIAL BONDING
BONDING BARS FOR EARTH PITS
AT-020H 235 x 40 x 25 mm bonding bar for polypropylene earth pit 266
AT-021J Bonding bar 235 x 40 x 25 mm for polypropylene earth pit 266
AT-051F Bonding bar 325 x 70 x 6 mm for concrete earth pit 266
EQUIPOTENTIAL BONDING BAR
AT-050F Nylon equipotential bonding bar 266
EARTH BARS
AT-020J Earth bar 8 way with single disconnecting link 267
AT-053J Insulator 267
AT-054J Earth bar 6 way 267
AT-055J Earth bar 6 way with single disconnecting link 267
AT-056J Earth bar 6 way with twin disconnecting links 267
AT-057J Disconnecting link 267
AT-058J Earth bar 8 way 267
AT-059J Earth bar 16 way 267
AT-062J Earth bar 10 way with single disconnecting link 267
AT-063J Earth bar 10 way with twin disconnecting links 267
AT-064J Earth bar 12 way 267
AT-065J Earth bar 12 way with single disconnecting link 267
AT-066J Earth bar 12 way with twin disconnecting links 267
AT-067J Earth bar 14 way 267
AT-068J Earth bar 14 way with single disconnecting link 267
AT-069J Earth bar 14 way with twin disconnecting links 267
AT-071J Earth bar 16 way with single disconnecting link 267
AT-072J Earth bar 16 way with twin disconnecting links 267
AT-073J Earth bar 18 way 267
AT-074J Earth bar 18 way with single disconnecting link 267
AT-075J Earth bar 18 way with twin disconnecting links 267
AT-076J Earth bar 20 way 267
AT-077J Earth bar 20 way with single disconnecting link 267
AT-078J Earth bar 20 way with twin disconnecting links 267
AT-079J Earth bar 8 way with twin disconnecting links 267
AT-090J Earth bar 10 way 267
AT-116J Stainless steel earth bar 6 way 267
AT-117J Stainless steel earth bar 8 way 267
AT-118J Stainless steel earth bar 10 way 267
AT-119J Stainless steel earth bar 12 way 267
EARTH POINTS
AT-096J Earth point 1 hole (M8 x 15 mm) 268
REF. PRODUCT PAG. REF. PRODUCT PAG.
EXTERNAL PROTECTION 312 INDEX PAR LIGNE DE PRODUITS INDEX BY PRODUCT LINE
AT-097J Earth point 2 holes (M8 x 12 mm) 268
AT-098J Earth point 4 holes (M8 x 14 mm) 268
AT-099J Earth point 1 hole (M8 x 15 mm) with 500mm tail of 70 mm
2
268
AT-100J Earth point 2 holes (M8 x 12 mm) with 500mm tail of 70 mm
2
268
AT-101J Earth point 4 holes (M8 x 14 mm) with 500mm tail of 70 mm
2
268
EARTH BOSS
AT-102J M10 x 50 x 50 mm earth boss 268
FIXED EARTHING TERMINAL
AT-120J Fixed earthing terminal M10 with connecting plate 80 mm 268
DISTANCE HOLDER
AT-036K Distance holder 268
SUPPORT FOR TAPE CONDUCTORS
AT-033K 30 x 2 mm - 50 x 6 mm copper support for tape conductors 269
AT-034K 30 x 2 mm - 50 x 6 mm galvanized steel support for tape conductors 269
AT-035K 30 x 2 mm - 50 x 6 mm stainless steel support for tape conductors 269
AT-039K 30 x 2 mm - 50 x 11 mm copper support for tape conductors 269
AT-040K 30 x 2 mm - 50 x 11 mm galvanized steel support for tape conductors 269
AT-041K 30 x 2 mm - 50 x 11 mm stainless steel support for tape conductors 269
SPARK GAP FOR EARTH BONDING
AT-050K Spark gap for earth joint 269
MULTIPURPOSE CLAMP
AT-090H Multipurpose clamp 272
ROD TO TAPE A CLAMP
AT-080J 25 x 3 mm - 26 x 12 mm rod to tape A clamp 272
AT-081J 30 x 2 mm - 40 x 12 mm rod to tape A clamp 272
AT-082J 50 x 6 mm - 51 x 12 mm rod to tape A clamp 272
ROD TO CABLE G CLAMP
AT-083J Gunmetal rod to cable G clamp 272
AT-086J 20 mm rod to cable G clamp 272
AT-112J Galvanized steel rod to cable G clamp 272
U-BOLT ROD E CLAMP
AT-087J U-bolt rod E clamp 273
AT-088J 20 mm U-bolt rod E clamp 273
EARTH CLAMPING
ROD TO CABLE CGUV CLAMP
AT-089J Naval brass rod to cable CGUV clamp 273
AT-091J 70 - 185 mm
2
rod to cable CGUV clamp 273
AT-092J 150 - 300 mm
2
rod to cable CGUV clamp 273
AT-094J 16 - 70 mm
2
rod to cable CGUV clamp 273
ROD TO CABLE LUG B CLAMP
AT-093J Rod to cable lug B clamp 273
AT-095J 20 mm rod to cable lug B clamp 273
DISCONNECTING SLEEVE
AT-135J Disconnecting sleeve 274
UNI DISCONNECTING CLAMP FOR CABLE
AT-113J Cu / Gal bimetallic UNI disconnecting cable and rod clamp 274
AT-114J Galvanized steel UNI disconnecting cable and rod clamp 274
AT-115J Stainless steel UNI disconnecting cable and rod clamp 274
UNIVERSAL CLAMP
AT-025F Stainless steel cable and rod universal clamp 274
AT-126J 15 - 25 mm universal clamp 274
AT-127J Copper cable and rod universal clamp 274
AT-128J Galvanized steel cable and rod universal clamp 274
T, L CLAMP
AT-136J Galvanized steel square 50 - 70 mm2 cable - 16 mm rod clamp 275
AT-137J Stainless steel square 50 - 70 mm2 cable - 16 mm rod clamp 275
AT-138J Copper square 50 - 70 mm2 cable - 16 mm rod clamp 275
CONNECTING CLAMP
AT-129J 20 mm galvanized steel connecting clamp 275
AT-130J 16 mm galvanized steel connecting clamp 275
AT-131J 25 mm galvanized steel connecting clamp 275
AT-132J 20 mm stainless steel connecting clamp 275
AT-133J 16 mm stainless steel connecting clamp 275
AT-134J 25 mm stainless steel connecting clamp 275
EXOTHERMIC WELDING: APLIWELD
WELDING MIXTURE
E0032 Welding mixture-10 units 32gr 280
E0045 Welding mixture-10 units 45gr 280
E0065 Welding mixture-10 units 65gr 280
E0090 Welding mixture-10 units 90gr 280
E0115 Welding mixture-10 units 115gr 280
E0150 Welding mixture-10 units 150gr 280
E0200 Welding mixture-10 units 200gr 280
E0250 Welding mixture-10 units 250gr 280
ACCESSORIES
50N Universal clamp 280/285
51N Specific vertical clamp 280/285
52N Tube specific handle clamp 280
53SN Clamp for Standard multiple-mould 280/282
54N Cable to rail welding clamp 280/285
58N Accessory for horizontal welding Clamp 280/285
59N Holding cables clamp 280/285
60N Flint igniter 280
61N Conductors brush 280
62N Mould cleaning brush 280
63N Slag removal spade 280
64N Weld cavity cleaning brush 280
65N Sealer compund 0.45Kg 280/285
66N Sealer compound 0,9Kg 280/285
67N Double brush for conductor 280
68N Basic tool set 280/282/285
69N Recharge for brush 67N 280
70N Flint igniter renewal 10 units 280
71N Sealing paste (2,25 Kg) 280
72N Adaptors for cables (25 units) 280
72NC35 Adaptors for cables de 35 mm
2
(25 units) 280
72NC50 Adaptors for cables de 50 mm
2
(25 units) 280
72NC70 Adaptors for cables de 70 mm
2
(25 units) 280
73N Security gloves 280
74N Flint ignitor extension 280
75N Blow torch 280
76N Butane gas cylinder 0.4Kg 280
77N Safety glasses 280/285
78N Ground rod sleeve 280
79N Ground rod clamp for parallel union 280
80N Case 280
81N Ceramic tray 280/282/283
82N MMS vertical stand pliers 280/282
83N Ceramic blanket 280
84N Mini-blowtorch 280
85N Mini-blowtorch recharge 280
89N Cavity sealer (for unit) 280
6089N 60 cavity sealer 280/282
TMS Standard multiple crucible 280/282
CHMS MMS cable/cable lower piece 280/282
CVMS T14 MMS Cab-tae/ground rod lower piece 14.3mmp 280
CVMS T16 MMS cable/ground rod lower piece. 15.9mm 280
CVMS TX MMS cable/ground rod lower piece Xmm 280/282
REF. PRODUCT PAG. REF. PRODUCT PAG.
EXTERNAL PROTECTION 313 INDEX PAR LIGNE DE PRODUITS INDEX BY PRODUCT LINE INDEX BY REFERENCE
MULTIPLE MOULD
MM-C95-P-T14 Multiple mould kit (earth rod 14mm) 283
MM-C95-P-T16 Multiple mould kit (earth rod 16mm) 283
SPECIFIC GRAPHITE MOULDS
C35/C35/12 T shape cable/cable mould 284
C35/C35/16 Cross shape cable over cable mould 284
C35/C35/17 Parallel cable over cable mould 284
C35/M/49 Parallel cable/surface mould 284
C35/T14/64 T cable over ground rod mould 284
C35/T16/64 T cable over ground rod mould 284
C35/V20/57 Parallel cable/rebar vertical mould 284
C50/C50/12 T shape cable/cable mould 284
C50/C50/16 Cross shape cable over cable mould 284
C50/C50/17 Parallel cable over cable mould 284
C50/M/49 Parallel cable/surface mould 284
C50/T14/64 T cable over ground rod mould 284
C50/T16/64 T cable over ground rod mould 284
C50/V20/57 Parallel cable/rebar vertical mould 284
C70/C70/12 T shape cable/cable moul 284
C70/C70/16 Cross shape cable over cable mould 284
C70/C70/17 Parallel cable over cable mould 284
C70/M/49 Parallel cable/surface mould 284
C70/T14/64 T cable over ground rod mould 284
C70/T16/64 T cable over ground rod mould 284
C70/V20/57 Parallel cable/rebar vertical mould 284
C95/C95/12 T shape cable/cable mould 284
C95/C95/16 Cross shape cable over cable mould 284
C95/C95/17 Parallel cable over cable mould 284
C95/M/49 Parallel cable/surface mould 284
C95/T14/64 T cable over ground rod mould 284
C95/T16/64 T cable over ground rod mould 284
C95/V20/57 Parallel cable/rebar vertical mould 284
C120/C120/12 T shape cable/cable mould 284
C120/C120/16 Cross shape cable over cable mould 284
C120/C120/17 Parallel cable over cable mould 284
C120/M/49 Parallel cable/surface mould 284
C120/T14/64 T cable over ground rod mould 284
C120/T16/64 T cable over ground rod mould 284
C120/V20/57 Parallel cable/rebar vertical mould 284
C150/C150/12 T shape cable/cable mould 284
C150/C150/16 Cross shape cable over cable mould 284
C150/C150/17 Parallel cable over cable mould 284
C150/M/49 Parallel cable/surface mould 284
C150/T14/64 T cable over ground rod mould 284
C150/T16/64 T cable over ground rod mould 284
C150/V20/57 Parallel cable/rebar vertical mould 284
P302/C50/31 Lineal tape to tape mould 284
P302/P302/21 Lineal tape to tape mould 284
P302/P302/23 Cross shape tape/tape mould 284
P302/P302/29 Parallel tape/tape-end mould 284
P302/T14/71 T shape tape over e.rod mould 284
P302/T16/71 T shape tape over e.rod mould 284
PREVENTIVE PROTECTION
STORM DETECTOR
AT-520 ATSTORM
v2 storm detector 294
AT-513 ATSTORM
v2 storm detector (DC/DC) 294
ACCESSORIES
AT-511 GSM Modem module ATSTORM
console 297
AT-516 Amplifier 2000 feet with sound alarm 297
AT-517 Amplifier 2000 feet w. voice messages 297
AT-518 Amplifier/RF Transmit. w. sound alarm 297
AT-519 Amplifier/RF Transmi w. voice message 297
AT-521 ATSTORM
v2
NET 297
REF. PRODUCT PAG. REF. PRODUCT PAG.
INDEX BY REFERENCE
EXTERNAL
PROTECTION
PAGE 5
INTERNAL
PROTECTION
PAGE 81
EARTHING
PAGE 251
EXOTHERMIC
WELDING
PAGE 277
PREVENTIVE
PROTECTION
PAGE 289
EXTERNAL PROTECTION 316 INDEX PAR LIGNE DE PRODUITS INDEX BY PRODUCT LINE INDEX BY REFERENCE
AT-036F 59
AT-036H 260
AT-036K 268
AT-037A 24
AT-037B 31
AT-037C 37
AT-037D 75
AT-037E 48
AT-037F 59
AT-037H 260
AT-037K 261
AT-038A 24
AT-038B 31
AT-038C 37
AT-038D 75
AT-038E 48
AT-038F 59
AT-038H 260
AT-038K 261
AT-039A 24
AT-039B 31
AT-039D 75
AT-039E 48
AT-039F 59
AT-039H 261
AT-039K 269
AT-040A 24
AT-040C 37
AT-040D 75
AT-040E 51
AT-040F 54
AT-040G 72
AT-040K 269
AT-041A 24
AT-041B 32
AT-041C 37
AT-041D 75
AT-041E 51
AT-041G 72
AT-041H 259
AT-041K 269
AT-042A 24
AT-042B 32
AT-042C 37
AT-042D 75
AT-042E 51
AT-042H 259
AT-042K 260
AT-043A 24
AT-043B 32
AT-043C 37
AT-043D 76
AT-043E 47
AT-043H 259
AT-043K 63
AT-044A 24
AT-044B 31
AT-044C 37
AT-044D 76
AT-044E 47
AT-044H 261
AT-011F 61
AT-011M 28
AT-012A 26
AT-012B 30
AT-012C 35
AT-012D 74
AT-012F 60
AT-012G 69
AT-012K 264
AT-013A 22
AT-013B 30
AT-013D 74
AT-013E 44
AT-013F 61
AT-014A 22
AT-014B 30
AT-014D 74
AT-014E 44
AT-014G 70
AT-015A 22
AT-015B 30
AT-015C 35
AT-015D 74
AT-015E 40
AT-015F 61
AT-015G 71
AT-015K 78
AT-016A 22
AT-016B 30
AT-016D 74
AT-016E 54
AT-016F 61
AT-016G 71
AT-016H 259
AT-016K 78
AT-017A 22
AT-017B 30
AT-017D 74
AT-017E 54
AT-017H 259
AT-017K 78
AT-018B 31
AT-018D 74
AT-018E 55
AT-018H 259
AT-018K 78
AT-019A 22
AT-019B 31
AT-019D 74
AT-019H 259
AT-019K 78
AT-020A 26
AT-020B 31
AT-020C 35
AT-020D 74
AT-020E 48
AT-020F 60
AT-020H 266
AT-020J 267
AT-020K 78
AT-020L 263
AT-000A 25
AT-000D 74
AT-000E 46
AT-000G 67
AT-000H 260
AT-000J 264
AT-000K 261
AT-001A 25
AT-001F 69
AT-001G 67
AT-001K 261
AT-002A 25
AT-002D 74
AT-002E 46
AT-002K 259
AT-003A 25
AT-003B 35
AT-003D 74
AT-003E 46
AT-003H 261
AT-003K 259
AT-003M 29
AT-004A 23
AT-004D 74
AT-004E 46
AT-004K 259
AT-005A 23
AT-005D 74
AT-005E 46
AT-005K 259
AT-005M 51
AT-006A 23
AT-006B 35
AT-006C 35
AT-006D 74
AT-006E 40
AT-006K 260
AT-007A 23
AT-007D 74
AT-007K 260
AT-008A 23
AT-008C 35
AT-008D 74
AT-008K 260
AT-009A 23
AT-009D 74
AT-009E 44
AT-009F 61
AT-009K 260
AT-010A 26
AT-010C 35
AT-010D 74
AT-010E 44
AT-010F 65
AT-010H 264
AT-010J 264
AT-010K 264
AT-010L 263
AT-011A 26
AT-011D 74
AT-011E 44
AT-021A 26
AT-021B 30
AT-021D 74
AT-021E 48
AT-021J 266
AT-021K 78
AT-022A 26
AT-022D 74
AT-022E 48
AT-022F 28
AT-022J 41
AT-022K 78
AT-023A 22
AT-023B 30
AT-023D 74
AT-023F 59
AT-023G 72
AT-023J 41
AT-023K 78
AT-024A 22
AT-024B 30
AT-024D 74
AT-024H 256
AT-024J 58
AT-024K 78
AT-025A 24
AT-025B 30
AT-025C 35
AT-025D 74
AT-025E 44
AT-025F 62
AT-025F 274
AT-025H 256
AT-025J 58
AT-025K 78
AT-026A 24
AT-026B 30
AT-026D 74
AT-026F 59
AT-026H 259
AT-026J 45
AT-026K 78
AT-027A 24
AT-027B 30
AT-027D 74
AT-027E 41
AT-027H 259
AT-027J 45
AT-027K 78
AT-028A 24
AT-028D 74
AT-028E 41
AT-028F 59
AT-028H 259
AT-028J 45
AT-028K 78
AT-029A 24
AT-029B 29
AT-029D 75
AT-029E 57
AT-029F 59
AT-029H 259
AT-029J 45
AT-029K 78
AT-030A 24
AT-030B 29
AT-030D 75
AT-030E 50
AT-030G 72
AT-030H 256
AT-030J 45
AT-030K 78
AT-030L 263
AT-030M 29
AT-031A 24
AT-031B 32
AT-031C 36
AT-031D 75
AT-031E 50
AT-031F 60
AT-031G 72
AT-031H 260
AT-031K 78
AT-031L 263
AT-032A 24
AT-032B 32
AT-032C 36
AT-032D 75
AT-032F 59
AT-032G 69
AT-032H 256
AT-032J 69
AT-032K 78
AT-032L 263
AT-033A 50
AT-033B 32
AT-033C 36
AT-033D 75
AT-033F 59
AT-033G 69
AT-033H 256
AT-033J 69
AT-033K 269
AT-034A 24
AT-034B 31
AT-034C 36
AT-034D 75
AT-034E 48
AT-034F 59
AT-034K 269
AT-035A 24
AT-035B 31
AT-035C 36
AT-035D 77
AT-035E 48
AT-035F 59
AT-035H 256
AT-035K 269
AT-036A 24
AT-036B 31
AT-036C 37
AT-036E 48
REF. PAG. REF. PAG. REF. PAG. REF. PAG. REF. PAG.
EXTERNAL PROTECTION 317 INDEX PAR LIGNE DE PRODUITS INDEX BY PRODUCT LINE INDEX BY REFERENCE
AT-053J 267
AT-053K 63
AT-053L 22
AT-054C 38
AT-054E 50
AT-054G 68
AT-054J 267
AT-054K 63
AT-054N 285
AT-055C 38
AT-055D 74
AT-055G 68
AT-055J 267
AT-055K 63
AT-055L 22
AT-056A 30
AT-056C 38
AT-056D 75
AT-056E 49
AT-056G 68
AT-056J 267
AT-056K 63
AT-057A 30
AT-057D 75
AT-057E 49
AT-057G 68
AT-057J 267
AT-057K 63
AT-058A 30
AT-058D 77
AT-058E 49
AT-058J 267
AT-059E 42
AT-059J 267
AT-059N 285
AT-060A 30
AT-060D 77
AT-060E 42
AT-060F 66
AT-060G 68
AT-060N 285
AT-061B 32
AT-061D 77
AT-061N 285
AT-062A 30
AT-062B 32
AT-062J 267
AT-062N 285
AT-063A 30
AT-063B 32
AT-063J 267
AT-063N 285
AT-064J 267
AT-064N 285
AT-065E 57
AT-065J 267
AT-065N 285
AT-066A 30
AT-066E 57
AT-066J 267
AT-066N 285
AT-044K 63
AT-045A 24
AT-045B 31
AT-045C 37
AT-045D 76
AT-045E 47
AT-045H 261
AT-045K 63
AT-046A 24
AT-046B 31
AT-046C 37
AT-046D 76
AT-046E 47
AT-046H 261
AT-046K 63
AT-047A 24
AT-047B 31
AT-047D 76
AT-047E 47
AT-047H 261
AT-047K 63
AT-048A 50
AT-048B 31
AT-048D 76
AT-048E 47
AT-048K 63
AT-049B 31
AT-049D 76
AT-049E 47
AT-049H 261
AT-049K 63
AT-050A 30
AT-050C 38
AT-050D 77
AT-050E 42
AT-050F 266
AT-050G 68
AT-050J 262
AT-050K 269
AT-050N 285
AT-051A 30
AT-051B 32
AT-051C 38
AT-051D 76
AT-051E 42
AT-051F 266
AT-051G 68
AT-051N 285
AT-052A 30
AT-052B 32
AT-052C 38
AT-052D 74
AT-052K 63
AT-052N 285
AT-053A 30
AT-053B 32
AT-053C 38
AT-053D 76
AT-053E 50
AT-053G 68
AT-053H 259
AT-093F 65
AT-093H 261
AT-093J 273
AT-094A 23
AT-094E 54
AT-094F 65
AT-094H 261
AT-094J 273
AT-095A 23
AT-095B 29
AT-095D 77
AT-095E 53
AT-095F 65
AT-095H 261
AT-095J 273
AT-096A 22
AT-096B 29
AT-096E 57
AT-096F 62
AT-096H 261
AT-096J 268
AT-097A 22
AT-097B 29
AT-097E 56
AT-097F 62
AT-097H 261
AT-097J 268
AT-098A 22
AT-098B 29
AT-098E 56
AT-098F 62
AT-098H 259
AT-098J 268
AT-099A 22
AT-099B 29
AT-099E 56
AT-099F 62
AT-099H 260
AT-099J 268
AT-100A 24
AT-100B 27
AT-100E 40
AT-100F 62
AT-100H 260
AT-100J 268
AT-101A 24
AT-101B 27
AT-101E 40
AT-101F 62
AT-101J 268
AT-102A 24
AT-102B 27
AT-102E 40
AT-102F 62
AT-102H 256
AT-102J 268
AT-103A 24
AT-103B 27
AT-103E 40
AT-103F 62
AT-103H 256
AT-067A 30
AT-067B 33
AT-067E 57
AT-067J 267
AT-068A 30
AT-068B 33
AT-068E 42
AT-068J 267
AT-068N 285
AT-069B 33
AT-069E 57
AT-069H 259
AT-069J 267
AT-070B 34
AT-070D 77
AT-070E 56
AT-070F 72
AT-070H 258
AT-070J 262
AT-070N 285
AT-071B 33
AT-071E 56
AT-071F 70
AT-071H 259
AT-071J 267
AT-072B 33
AT-072E 56
AT-072F 41
AT-072H 259
AT-072J 267
AT-073B 33
AT-073E 56
AT-073H 258
AT-073J 267
AT-073N 285
AT-074B 34
AT-074J 267
AT-074N 285
AT-075B 34
AT-075J 267
AT-075N 285
AT-076B 34
AT-076E 56
AT-076H 259
AT-076J 267
AT-076N 285
AT-077B 33
AT-077E 56
AT-077H 259
AT-077J 267
AT-077N 285
AT-078B 33
AT-078H 259
AT-078J 267
AT-078N 285
AT-079B 33
AT-079H 259
AT-079J 267
AT-079N 285
AT-080B 34
AT-080D 76
AT-080G 71
AT-080H 260
AT-080J 272
AT-081B 34
AT-081D 76
AT-081F 64
AT-081H 259
AT-081J 272
AT-082D 76
AT-082E 57
AT-082H 259
AT-082J 272
AT-082N 285
AT-083B 34
AT-083D 76
AT-083E 57
AT-083F 64
AT-083J 272
AT-084B 34
AT-084D 76
AT-084E 57
AT-084F 64
AT-085A 30
AT-085B 34
AT-085D 76
AT-085E 57
AT-085F 64
AT-086B 34
AT-086D 76
AT-086E 57
AT-086F 65
AT-086H 259
AT-086J 272
AT-087D 76
AT-087E 57
AT-087F 65
AT-087H 259
AT-087J 273
AT-088B 34
AT-088E 57
AT-088F 65
AT-088J 273
AT-089E 57
AT-089F 65
AT-089J 273
AT-089J-1 59
AT-090B 70
AT-090E 52
AT-090F 65
AT-090H 61
AT-090H 272
AT-090J 267
AT-091E 52
AT-091F 65
AT-091J 273
AT-092A 23
AT-092E 53
AT-092F 65
AT-092J 273
AT-093A 23
AT-093E 53
REF. PAG. REF. PAG. REF. PAG. REF. PAG. REF. PAG.
EXTERNAL PROTECTION 318 INDEX PAR LIGNE DE PRODUITS INDEX BY PRODUCT LINE INDEX BY REFERENCE
AT-104A 24
AT-104B 27
AT-104E 40
AT-104F 62
AT-104H 256
AT-105A 24
AT-105B 27
AT-105E 40
AT-105F 61
AT-105H 256
AT-106A 24
AT-106E 40
AT-106F 65
AT-106H 256
AT-107A 24
AT-107E 40
AT-107F 64
AT-107F 65
AT-108A 24
AT-108E 40
AT-108F 64
AT-108F 65
AT-109A 24
AT-109E 40
AT-109F 64
AT-110A 24
AT-110B 26
AT-110D 77
AT-110E 40
AT-110F 64
AT-111A 24
AT-111B 26
AT-111E 40
AT-111F 64
AT-112A 25
AT-112B 27
AT-112E 40
AT-112F 62
AT-112J 272
AT-113A 25
AT-113B 27
AT-113D 77
AT-113E 40
AT-113F 62
AT-113J 64
AT-113J 274
AT-114A 23
AT-114B 27
AT-114D 77
AT-114E 40
AT-114J 64
AT-114J 274
AT-115A 23
AT-115B 27
AT-115D 77
AT-115E 40
AT-115F 62
AT-115J 64
AT-115J 274
AT-116A 23
AT-116B 27
AT-116D 77
AT-116E 40
AT-116F 61
AT-116H 262
AT-116J 267
AT-117A 23
AT-117D 77
AT-117E 40
AT-117F 61
AT-117H 262
AT-117J 267
AT-118A 23
AT-118D 77
AT-118E 40
AT-118F 61
AT-118H 262
AT-118J 267
AT-119A 23
AT-119E 40
AT-119F 60
AT-119H 262
AT-119J 267
AT-120B 28
AT-120D 77
AT-120E 40
AT-120F 60
AT-120H 262
AT-120J 268
AT-121A 22
AT-121B 28
AT-121E 40
AT-121F 62
AT-121H 262
AT-122A 22
AT-122B 28
AT-122E 40
AT-122F 62
AT-122H 262
AT-123B 28
AT-123D 78
AT-123E 41
AT-123F 64
AT-123H 262
AT-124B 27
AT-124D 78
AT-124E 41
AT-124F 64
AT-125B 27
AT-125D 77
AT-125E 41
AT-125F 62
AT-125H 262
AT-126D 78
AT-126E 41
AT-126H 262
AT-126J 274
AT-127D 78
AT-127E 41
AT-127J 62
AT-127J 274
AT-128D 77
AT-128E 45
AT-128F 62
AT-128H 262
AT-128J 62
AT-128J 274
AT-129D 77
AT-129E 45
AT-129J 275
AT-130D 76
AT-130E 45
AT-130F 60
AT-130J 275
AT-131D 76
AT-131E 45
AT-131F 60
AT-131J 275
AT-132D 76
AT-132E 45
AT-132J 275
AT-133D 76
AT-133E 46
AT-133F 60
AT-133J 275
AT-134D 76
AT-134E 46
AT-134F 61
AT-134J 275
AT-135D 76
AT-135E 46
AT-135F 60
AT-135J 61
AT-135J 274
AT-136E 46
AT-136F 59
AT-136J 59
AT-137E 46
AT-137J 59
AT-137J 275
AT-138D 77
AT-138E 49
AT-138J 59
AT-138J 275
AT-139D 75
AT-139E 49
AT-140D 75
AT-140E 49
AT-141D 75
AT-141E 49
AT-142D 75
AT-142E 49
AT-143D 75
AT-143E 49
AT-144D 75
AT-144E 49
AT-145D 75
AT-145E 51
AT-1465 22
AT-1467 22
AT-1469 22
AT-146D 75
AT-1470 22
AT-147E 51
AT-148E 51
AT-149E 51
AT-150D 77
AT-150E 52
AT-1515 19
AT-151E 52
AT-152E 52
AT-1530 19
AT-153E 54
AT-1545 19
AT-1560 19
AT-156E 54
AT-157E 54
AT-158E 54
AT-159E 53
AT-160E 53
AT-161E 53
AT-162E 53
AT-163E 53
AT-164E 53
AT-165E 53
AT-166E 53
AT-167E 53
AT-168E 53
AT-169E 53
AT-170E 55
AT-171E 55
AT-172E 55
AT-173E 55
AT-174E 55
AT-175E 58
AT-176E 58
AT-177E 58
AT-178E 52
AT-179E 52
AT-182E 56
AT-183E 51
AT-184E 51
AT-185E 56
AT-186E 56
AT-190E 44
AT-191E 44
AT-192E 44
AT-193E 44
AT-194E 56
AT-195E 56
AT-196E 43
AT-197E 43
AT-198E 43
AT-199E 43
AT-200E 43
AT-201E 43
AT-202E 43
AT-203E 43
AT-204E 43
AT-205E 43
AT-206E 43
AT-207E 43
AT-208E 43
AT-209E 43
AT-2102 237
AT-2103 237
AT-2104 237
AT-2105 237
AT-2106 237
AT-2107 225
AT-2108 237
AT-2109 237
AT-210E 43
AT-2110 237
AT-2111 237
AT-2112 237
AT-2115 237
AT-2118 237
AT-211E 43
AT-212E 43
AT-216E 40
AT-217E 40
AT-218E 42
AT-2201 232
AT-2206 231
AT-2207 225
AT-2208 231
AT-2209 231
AT-2215 232
AT-511 297
AT-513 294
AT-516 297
AT-517 297
AT-518 297
AT-519 297
AT-520 294
AT-2102 237
AT-2103 237
AT-2104 237
AT-2105 237
AT-2106 237
AT-2108 237
AT-2109 237
AT-2110 237
AT-2111 237
AT-2115 237
AT-2118 237
AT-2201 232
AT-2107 225
AT-2204 225
AT-2206 231
AT-2207 225
AT-2208 231
AT-2209 231
AT-2211 233
AT-2212 233
AT-2213 227
AT-2215 232
AT-2217 233
AT-2221 229
REF. PAG. REF. PAG. REF. PAG. REF. PAG. REF. PAG.
EXTERNAL PROTECTION 319 INDEX PAR LIGNE DE PRODUITS INDEX BY PRODUCT LINE INDEX BY REFERENCE
REF. PAG. REF. PAG.
AT-2300 235
AT-3501 196
AT-8000 132
AT-8001 132
AT-8002 132
AT-8003 144
AT-8004 152
AT-8005 132
AT-8006 132
AT-8007 132
AT-8009 136
AT-8010 136
AT-8011 136
AT-8012 136
AT-8013 136
AT-8014 181
AT-8015 136
AT-8016 136
AT-8111 164
AT-8112 164
AT-8113 201
AT-8115 201
AT-8117 168
AT-8118 181
AT-8119 168
AT-8120 168
AT-8121 181
AT-8122 168
AT-8125 181
AT-8130 168
AT-8131 168
AT-8132 160
AT-8133 160
AT-8134 181
AT-8139 168
AT-8140 168
AT-8141 181
AT-8149 168
AT-8150 168
AT-8152 162
AT-8153 162
AT-8160 168
AT-8161 168
AT-8201 148
AT-8202 140
AT-8203 144
AT-8204 152
AT-8205 126
AT-8208 152
AT-8209 152
AT-8214 122
AT-8215 122
AT-8216 158
AT-8217 156
AT-8220 148
AT-8221 152
AT-8222 140
AT-8223 144
AT-8226 140
AT-8224 148
AT-8225 152
AT-8226 140
AT-8227 144
AT-8228 125
AT-8229 127
AT-8230 148
AT-8232 128
AT-8233 128
AT-8234 128
AT-8235 128
AT-8236 128
AT-8237 128
AT-8238 128
AT-8240 148
AT-8241 152
AT-8242 140
AT-8243 144
AT-8244 148
AT-8245 152
AT-8246 140
AT-8247 144
AT-8248 125
AT-8249 127
AT-8250 148
AT-8260 148
AT-8261 152
AT-8262 140
AT-8263 144
AT-8264 148
AT-8265 152
AT-8266 152
AT-8267 152
AT-8268 125
AT-8269 152
AT-8270 148
AT-8280 128
AT-8281 124
AT-8283 124
AT-8284 124
AT-8285 124
AT-8286 124
AT-8287 124
AT-8289 124
AT-8290 140
AT-8291 144
AT-8292 140
AT-8293 144
AT-8294 144
AT-8295 144
AT-8296 126
AT-8297 126
AT-8298 126
AT-8299 152
AT-8310 114
AT-8312 114
AT-8350 112
AT-8351 112
AT-8352 112
AT-8398 114
AT-8399 112
AT-8435 166
AT-8463 166
AT-8505 196
AT-8510 196
AT-8511 198
AT-8512 196
AT-8513 197
AT-8515 196
AT-8514 199
AT-8516 197
AT-8524 196
AT-8525 197
AT-8526 199
AT-8530 196
AT-8531 197
AT-8548 196
AT-8549 199
AT-8550 198
AT-8560 196
AT-8561 198
AT-8580 196
AT-8581 198
AT-8590 199
AT-8601 120
AT-8602 120
AT-8603 116
AT-8604 116
AT-8607 118
AT-8608 118
AT-8611 117
AT-8612 117
AT-8613 117
AT-8702 245
AT-8704 244
AT-8705 249
AT-8706 249
AT-8707 248
AT-8708 248
AT-8711 246
AT-8712 246
AT-8713 246
AT-8714 246
AT-8715 246
AT-8716 247
AT-8717 247
AT-8718 247
AT-8719 247
AT-8720 247
AT-8901 192
AT-8905 195
AT-9001 242
AT-9002 242
AT-9003 242
AT-9004 242
AT-9005 242
AT-9006 243
AT-9007 243
AT-9008 243
AT-9009 243
AT-9010 243
AT-9101 214
AT-9104 216
AT-9105 220
AT-9106 220
AT-9107 215
AT-9108 218
AT-9109 220
AT-9205 222
AT-9206 223
AT-9210 222
AT-9211 224
AT-9212 222
AT-9213 223
AT-9215 222
AT-9216 223
AT-9224 222
AT-9225 223
AT-9230 222
AT-9231 223
AT-9248 222
AT-9249 224
AT-9260 222
AT-9261 224
AT-9280 222
AT-9281 224
AT-9320 201
AT-9325 201
AT-9326 201
AT-9401 205
AT-9402 205
AT-9403 205
AT-9501 207
AT-9601 209
C120/C120/12 284
C120/C120/16 284
C120/C120/17 284
C120/M/49 284
C120/T14/64 284
C120/T16/64 284
C120/V20/57 284
C150/C150/12 284
C150/C150/16 284
C150/C150/17 284
C150/M/49 284
C150/T14/64 284
C150/T16/64 284
C150/V20/57 284
C35/C35/12 284
C35/C35/16 284
C35/C35/17 284
C35/M/49 284
C35/T14/64 284
C35/T16/64 284
C35/V20/57 284
C50/C50/12 284
C50/C50/16 284
C50/C50/17 284
C50/M/49 284
C50/T14/64 284
C50/T16/64 284
REF. PAG. REF. PAG.
C50/V20/57 284
C70/C70/12 284
C70/C70/16 284
C70/C70/17 284
C70/M/49 284
C70/T14/64 284
C70/T16/64 284
C70/V20/57 284
C95/C95/12 284
C95/C95/16 284
C95/C95/17 284
C95/M/49 284
C95/T14/64 284
C95/T16/64 284
C95/V20/57 284
E0032 280
E0045 280
E0065 280
E0090 280
E0115 280
E0150 280
E0200 280
E0250 280
MM-C95-P-T14 283
MM-C95-P-T16 283
P302/C50/31 284
P302/P302/21 284
P302/P302/23 284
P302/P302/29 284
P302/T14/71 284
P302/T16/71 284