Duct Traverse 0904-High
Duct Traverse 0904-High
ATBEC
ADVANCED TESTING BALANCING AND ENERGY CONSULTING
657 Meeker Ave., Brooklyn, NY 11222/Ph #: (718) 486-6764 Fax: (718) 486-8249
DESIGN DATA
OD ID
Type: Main Hgt/Diam (in.) 48 Serves Outlets
Shape: Rect Width (in.) 48 Air Flow Temp °F
Insulation Type: Area (sq. ft.) 16
TEST DATA
Point 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
A 1024 979 844 1235 1150 1141 1261 1196 1371
B 1175 1061 1207 1426 1427 1398 1587 1581 1226
C 1136 1187 1177 1287 1426 1419 1559 1572 1277
D 884 1215 1092 1426 1415 1225 1407 1287 1500
E 1121 1381 1124 1426 1275 1123 1174 1537 1471
F 1085 1321 1295 1262 1005 1217 1259 1387 1065
Design CFM Total FPM Num of Reading Average FPM Area (sq. ft.) Total CFM
68,188 54 1,262 16 20,192
% of Design Static Pressure, in w.g.
1.0
Remarks
Fan on high speed.