Download as pdf or txt
Download as pdf or txt
You are on page 1of 28

MULTI-CHAMBER ARRESTERS AND

INSULATOR-ARRESTERS
for lightning protection of overhead
distribution and transmission lines
Multi chamber system (S)
2 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
Multi chamber system (S)
3 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
1 silicone rubber length;
2 intermediate electrodes;
3 arc quenching chamber;
4 discharge channel.
a) Initial stage of discharge
b) Final stage of discharge
Multi-Chamber Arrester 20 V
4 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
against Induced overvoltages (MCA-20-I)
Multi-Chamber Insulator- Arrester (MCIA) 20 V
5 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
against Induced overvoltages (MCA-20-I)
Multi-Chamber Insulator (MCIA)
6 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
Insulator U120AD
Multi-Chamber
System (MCS)
Insulator-arrester at tests
7 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
Multi-Chamber Insulator Arresters at 35 V Overhead Line
8 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
TESTS OF 220 kV MCIA STRINGS
FOR COMMERCIAL LINE 150 KM
Copyright 2010 Streamer Inc. All rights
reserved.
9
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
Flashover characteristics at:
- lightning and switching impulses
- operational voltage at clean, wet and polluted conditions
- operational voltage and ice
Power follow current quenching
Electrodynamic and thermal stability
Radio interference
Climatic tests
Mechanical tests.
Power arc follow test chart
10
Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
LIGHTNING
IMPULSE
GENERATOR
POWER LINE
VOLTAGE
GENERATOR
Imax=1 to 30 kA.
for Imax =2 kA T0,5=500 mcs
for Imax = 30 kA T0,5= 55 mcs
Umax=250 kV
Ueff=2 to 30 kV
Ieff=1 to 10 kA
Voltage and current oscillograms
11 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
Impulse quenching Zero quenching
Multi-Chamber Insulator-Arrester
(MCIA) at quenching tests
12 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
impulse quenching
Im =30 kA, 8/20 mcs
general view
MCIA string at quenching tests
13 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
impulse quenching
Im=30 kA, 8/20 mcs
general view
220 kV MCIA string at impulse tests
14 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
220 kV MCIA strings at steep voltage impulse tests
15 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
du/dt=2 MV/mcs
du/dt=4 MV/mcs
Voltage-time characteristics of 220 kV MCIA string
16 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
MCIA string at operational voltage
17 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
clean and dry
under rain
220 kV MCIA string at pollution tests
18 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
initial stage final stage
= 11,0-13,7 mcS
breakdown voltage U
50
=215-235 kVeff
220 kV MCIA string at ice tests
19 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
ice thickness 30 mm
flashover voltage is 236/230 kV with/without MCS
and higher than maximum phase voltage 146 kVeff
220 kV MCIA string at radio interference measurements
20 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
220 kV MCIA string at climatic tests
21 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
- temperature : -60..+50 C
-humidity : 10-100%
-frost and its melting
-solar radiation
50 Hz
generator
MCIA at vibration tests
22 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
220 kV MCIA string installation
23 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
220 kV commercial line with MCIA strings
24 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
25 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
Less wind and ice load
Less weight and cost of
towers
Less direct lightning
strokes
Grounding is not
neccessary
with sheilding wire
without sheilding wire but with MCIAs
MCIA
vs. sheilding wire
500 V line with MOA and with MCIA
26 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
MOA line with MOA line with MCIA
CONCLUSIONS
27 Copyright 2010 Streamer Inc. All rights reserved.
MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS
1. Multi Chamber Arresters (MCAs) and Insulator-
Arresters (MCIAs) can be developed for any rated
voltage.
2. 220 kV MCIA string has passed successfully the whole
complex of electrical, mechanical and climatic tests
3. MCAs and MCIAs are very competitive with
conventional lightning protection means.
THANK YOU FOR YOUR ATTENTION!