FIREBARRIER SILICONE SL INTUMESCENT SEALANT INSERTS OR PUTTY PADS FOR ELECTRICAL BOXES MORTAR CPVC/PVC/ABS PLASTIC PIPE STEEL, IRON & COPPER METALLIC PIPE MINERAL WOOL MINERAL WOOL SILICONE ACRYLIC SEALANT OR INTUMESCENT SEALANT SPRAYACRYLIC SPRAYACRYLIC COLLAR FIRESTOP SYSTEMS FIREBARRIER Silicone & Silicone SL Forms a durable, flexible, water-tight bond May be applied over a wide temperature range, -18C to 50C (0F to 120F) Physical properties will remain stable over time Will not crack or crumble Tools easily SL = self-levels - no tooling required Neutral cure - low odour Underside of floor applications tested Colours Silicone: Red or Grey Silicone SL: Red Plumbing Pipes, insulated pipes, glass, copper, steel, iron and combustible (plastic) pipes Electrical Conduits, cables, cable trays, bundled cables Ducts Steel ducts Joint Systems Horizontal and vertical (horizontal only for SL) Joints - Movement Capable UL 2079 tested Cartridges 10.3 fl.oz. (304 mL) 28.7 fl.oz. (850 mL) Containers 2.64 US gal (10 L) pails 4.5 US gal (17 L) pails Foil pack 20 fl oz (600 mL) ULI, ULC, cUL, ITS (WH), FM Intumescent Sealant Water based, intumescent Economical Forms a durable, water-tight bond Physical properties remain stable over time During a fire expands to fill opening where combustible piping was located Tools easily Low odour Ideal for caulk and walk systems Colour: Red Plumbing Copper, steel, iron insulated, and combustible (plastic) pipes Ducts Steel ducts Electrical Cables, cable trays, bundled cables and electrical conduits Cartridges 10.1 fl.oz. (300 mL) 28.7 fl.oz. (850 mL) Containers 5 US gal (18.9 L) pails Foil Pack 20.3 fl.oz. (600 mL) ULI, cUL Acrylic Sealant Water based Economical Forms a durable, flexible water-tight bond Applied by caulking or trowel Physical properties remain stable over time Colour: Red Plumbing Pipes, insulated pipes, copper, steel, and combustible (plastic) pipes Electrical Conduits, cables, cable trays Joint Systems Horizontal and vertical Joints - Movement Capable UL 2079 tested Cartridges 10.1 fl.oz. (300 mL) 28.7 fl.oz. (850 mL) Containers 5 US gal (18.9 L) pails Foil Pack 20.3 fl.oz. (600 mL) ULI, cUL P R O D U C T S F E A T U R E S U S A G E S I Z E S L I S T E D / C E R T I F I E D FIRESTOP SYSTEMS A/D FIREBARRIER Silicone, Silicone SL, Seal, Seal NS, Intumescent Caulk or Putty A/D FIREBARRIER Seal, Seal NS, SprayMastic, Silicone or Silicone SL A/D Fire Protection Systems ofrece un sistema completo de productos requeridos para sellos corta fuego. Todos son certificados por laboratorios independientes y probados para asegurar clasificaciones de proteccin contra fuego en penetraciones y aberturas en pisos y paredes con clasificaciones contra fuego. A/D FIREBARRIER son productos listados por Underwriter Laboratories, Intertek Testing Services (Warnock Hersey), y Factory Mutual, y son certificados bajo rigurosos programas de inspecciones a la fbrica. Seal & Seal NS Water based Economical Forms a durable, water-tight bond Seal may be poured, pumped or sprayed Underside of floor applications tested Physical properties remain stable over time Colours Seal: Blue Seal NS: White (may be tinted in the field), and Red Plumbing Pipes, insulated pipes, glass, copper, steel, and CPVC Electrical Conduits, cables, cable trays Joint Systems Horizontal and vertical Joints - Movement Capable UL 2079 tested Cartridges (Seal NS only) 10.3 fl.oz. (304 mL) 28.7 fl.oz. (850 mL) Containers (Seal & Seal NS) 5 US gal (19 L) pails ULI, ULC, cUL, ITS (WH), FM SprayAcrylic Water based elastomeric Economical Forms a durable, water tight bond Physical properties will remain stable over time May be sprayed or trowelled Curtain wall / floor joints tested Colour: Red Joint Systems Horizontal and vertical, curtain wall, head-of-wall, perimeter and floor to wall Joints - Movement Capable UL 2079 tested Containers 5 US gal (18.9 L) pails ULI, cUL Mortar Foamed cement Single component Easy to use Economical Mixes easily with water to form a lightweight non-slumping paste that is easy to place and tool Self-supporting Tested for very large openings Non-combustible Colour: Grey Plumbing Glass, copper, steel, iron, insulated pipes and multi- ple penetrations Electrical Conduits, cables, cable trays, multiple penetrations Ducts Steel ducts Large openings Containers 15.5 lb (7 kg) bags ULI, ULC, cUL, ITS (WH), FM Mineral Wool Non-combustible Pre-cut strips facilitate easy installation and provide a smooth surface to help control depth of sealant that is applied High quality, proprietary insulation blankets/strips UL and ULC listed and certified General A/D FIREBARRIER Mineral Wool is the recommended and/or required backing for A/D FIREBARRIER sealants in most firestop applications Packaged 25 lb (11 kg) nominal in plastic bags in various pre-cut x 4 ft strips or blankets ULI, ULC, ITS (WH), FM A/D FIREBARRIER Intumescent Sealant A/D FIREBARRIER Acrylic Sealant A/D FIREBARRIER Silicone & Silicone SL A/D FIREBARRIER SprayAcrylic A/D FIREBARRIER Seal & Seal NS A/D FIREBARRIER Mineral Wool Pillows Quick and clean single product installation No mesh or lath required No sealant or putty required Ideal for cable retrofitting Easy to install, remove or replace Electrical Cables, cable trays, bundled cables General Blank or temporary openings 2 x 4 x 8 in. (50 x 100 x 200 mm) packaged 25 per box ULI, ULC, cUL Collars, Wrap Strip & Collar Strips Easy to install with common tools Collars - Convenient, ready to install 3, 4 and 6-in. nominal trade sizes Wrap Strip - For use with or without steel Collar Strip Intumescent feature closes off and seals plastic pipes and pipe insulation Passes 50 Pa test requirement in Canada (refer to test designs) Plumbing Combustible (plastic) pipes and insulated pipes through concrete or gypsum wallboard, vertical and horizontal Collars Nominal 3, 4 and 6 in. trade sizes Wrap Strip 1 or 2 in. wide x 1/4 in. thick x 12 ft strips Collar Strip 50 ft coil ULI, ULC, cUL Putty Easy to install Single component Intumescent No mixing Remains soft and pliable Plumbing Pipes through concrete walls and floors Electrical Cables and conduits through gypsum wallboard. Sticks 66.2 in 3 (1085 mL) packaged 12 per carton ULI, cUL Putty Pads & Inserts Used to maintain hourly fire resistance ratings of fire resistive walls and partitions containing electrical boxes Permit greater density of outlet and switch boxes in rated walls than would otherwise be permitted by codes for unprotected boxes Intumescent materials expand when exposed to fire to seal off the box Single component Easy to install Electrical Protect electrical outlet and switch boxes Inserts 2 x 4 in. or 4 x 4 in. packaged 50 per carton Putty Pads 6 x 7 x .2 in. & 9.25 x 9.25 x .2 in. packaged 12 per carton ULI, cUL A/D FIREBARRIER Mortar A/D FIREBARRIER Pillows A/D FIREBARRIER Putty Pads & Inserts A/D FIREBARRIER Putty A/D FIREBARRIER Collars A/D FIREBARRIER Wrap Strip & Collar Strips FIREBARRIER INTUMESCENT SEALANT
1. PRODUCT NAME A/D FIREBARRIER Intumescent Sealant. 2. PRODUCT DESCRIPTION Basic Use: A/D FIREBARRIER Intumescent Sealant is a single component intumescent acrylic water based sealant intended for use as a firestop system component. Composition and Materials: A/D FIREBARRIER Intumescent Sealant forms a durable, flexible, watertight bond with most construction materials. It is applied independently for caulk and walk systems or over mineral wool or backer rod (refer to test design details) to seal the openings where building services such as pipes and cables penetrate fire rated assemblies. May be applied by caulking gun or trowel. Clean up is with water. A/D FIREBARRIER Intumescent Sealant contains water and is best if protected from freezing. Packaging: See table 2. Refer to the A/D FIREBARRIER estimating guide for complete volume and coverage information. Color: Red Application Limitations: A/D FIREBARRIER Intumescent Sealant is intended for use at interior locations in buildings only. Protect from direct contact with water until cured. Curing time will vary with temperature and humidity. Do not use where abrasion or physical abuse is anticipated. Installation in confined or air-free spaces may inhibit cure. Do not apply to surfaces with special protective or cosmetic coatings without prior consul- tation with the manufacturer and first testing adhesion. A/D FIREBARRIER Intumescent Sealant has been tested in numerous firestop configurations. For optimum economy and performance, apply to a thickness equal to or slightly greater than the minimum test design thickness. Excessive depth to width ratios may cause sealant failure DO NOT apply excessive thickness. As a guideline, A/D Fire Protection Systems recommends the minimum tested system thick- nesses not be exceeded by more than 25%. 3. TECHNICAL DATA Physical Properties: Refer to Table 1. Standards: A/D FIREBARRIER Intumescent Sealant has been tested in accordance with the following: ANSI/UL1479, ASTM E814 and CAN4/ULC-S115M. Systems certified for use in Canada are available under the cUL mark. FGG/BM/CZ System Compatible indicates that this product has been tested, and is monitored on an ongoing basis, to assure its chemical compatibility with FlowGuard Gold, BlazeMaster and Corzan pipe and fittings. FGG/BM/CZ, FlowGuard Gold, BlazeMaster, and Corzan are licensed trademarks of the Lubrizol Corporation. Contact A/D Fire Protection Systems for a current list of fire rated systems. 4. INSTALLATION Clean all openings to be firestopped by removal of foreign matter and contaminants such as oil, dust, grease, frost, water, surface dirt, old sealants glazing compound, protective coatings, etc. Refer to fire test design / system. Priming: A/D FIREBARRIER Intumescent Sealant does not require any priming. In view of the unpredictability of surface characteristics, it is recommended that a test sample of sealant be applied on the surface to test adhesion. Masking: Areas adjacent to openings to be firestopped can be masked to assure a neat appearance. The masking tape should not be allowed to touch the clean surfaces to which the caulk is to adhere. Remove masking tape immediately. Applications: For caulk and walk systems, simply apply the product where required and let cure. Where backer material (mineral wool, backer rod, etc.) is required by fire test design or system, install backer material as specified. Surfaces of backer material to receive caulk should be recessed in the opening to a depth equal to the required thickness of sealant. Table 1 PHYSICAL PROPERTIES*
Properties Results Color Red Odor Mild pH 7.0 - 10.0 VOC (grams/liter) 0 Flame Spread (ASTM E-84) 0 Smoke Developed (ASTM E-84) 0 Cure Time (ASTM C-679) 3 - 5 days Skin over Time Overnight Shore A Hardness (ASTM C-661) 15 - 20 Application Temperature 40 - 110F (5 - 43C) Freeze Sensitive Yes Paintable Yes
*Values given are not intended for specification preparation. Where mineral wool is required backer material, we recommend the use of A/D FIREBARRIER Mineral Wool this high quality material is available pre-cut for easy installation and allows a controlled depth of caulk to be applied for maximum economy. Apply A/D FIREBARRIER Intumescent Sealant in a continuous operation to fill and seal the opening. Tool the sealant to spread it against the backer material and the opening surfaces. Simply fill the annular space to the required depth and form a smooth bead or crown at the surfaces. Excess sealant should be cleaned with water. CURED SEALANT IS USUALLY VERY DIFFICULT TO REMOVE WITHOUT ALTERING OR DAMAGING THE SURFACE TO WHICH THE SEALANT HAS BEEN MISAPPLIED. Precaution: On direct contact, uncured sealant may irritate eyes. Flush with water and call a physician. Avoid prolonged contact with skin. Keep out of reach of children. To safely use this product, read and abide by Material Safety Data Sheet (MSDS). Shelf Life: A/D FIREBARRIER Intumescent Sealant has shelf life of one year from the date of manufacture when stored in original and unopened container at or below 110F (43C) and above 40F (5C). See top of box or label on pail for date of manufacture (day/ month/ year). 5. AVAILABILITY AND COST Availability: A/D sales offices and technical representatives are located throughout North America. (See below) 6. MAINTENANCE No maintenance should be required. If intumescent sealant becomes damaged, replace damaged portion. Clean surfaces in damaged areas, and repair with fresh A/D FIREBARRIER Intumescent Sealant. 7. TECHNICAL SERVICES Contact nearest A/D representative.
March 10, 2008 Table 2 Type of Packaging Size Volume Coverage at deep x 1 wide 10.1 fl. oz. (300 mL) 18.2 in 3
(300 cm 3 ) 6.1 lineal ft. (1.86 lineal m) Cartridges 28.7 fl. oz. (850 mL) 51.8 in 3
(850 cm 3 ) 17.3 lineal ft. (5.27 lineal m)
Foil packs 20 fl. oz. (600 mL) 36 in 3
(600 cm 3 ) 12.2 lineal ft. (3.72 lineal m)
Pails 5 gal (18.9 L) 1155 in 3
(18900 cm 3 ) 384.4 lineal ft. (117.18 lineal m) FIREBARRIER INTUMESCENT CAULK
1. PRODUCT NAME A/D FIREBARRIER Intumescent Caulk. 2. PRODUCT DESCRIPTION Basic Use: A/D FIREBARRIER Intumescent Caulk is a water based, single component elastomeric sealant intended for use as a firestop system component. Composition and Materials: A/D FIREBARRIER Intumescent Caulk forms a durable, flexible, watertight bond with most construction materials. It is applied independently for caulk and walk systems or over mineral wool or backer rod (refer to test design details) to seal the openings where building services such as pipes and cables penetrate fire rated assemblies. May be applied by caulking gun or trowel. Clean up is with water. A/D FIREBARRIER Intumescent Caulk contains water and is best if protected from freezing. If frozen, thaw completely before use Packaging: A/D FIREBARRIER Intumescent Caulk is available in 10.3 fl. oz (304 ml) cartridges, 20 fl. oz (600 ml) foil packs and nominal 4.5 gal (17 L) plastic pails. Contents are 18.6 in 3 , 36.1 in 3 and 1050 in 3
respectively. Refer to the A/D FIREBARRIER estimate guide for volume and coverage information. Color: Red Application Limitations: A/D FIREBARRIER Intumescent Caulk is intended for use at interior locations in buildings only. Protect from direct contact with water until cured. Curing time will vary with temperature and humidity. Do not use where abrasion or physical abuse is anticipated. Installation in confined or air-free spaces may inhibit cure. Do not apply to surfaces with special protective or cosmetic coatings without prior consul- tation with the manufacturer and first testing adhesion. A/D FIREBARRIER Intumescent Caulk has been tested in numerous firestop configurations. For optimum economy and performance, apply to a thickness equal to or slightly greater than the minimum test design thickness. Excessive depth to width ratios may cause sealant failure DO NOT apply excessive thickness. As a guideline, A/D Fire Protection Systems recommends the minimum tested system thick- nesses not be exceeded by more than 25%. 3. TECHNICAL DATA Physical Properties: Refer to Table 1. Fire Resistance Ratings: A/D FIREBARRIER Intumescent Caulk has been tested and certified by ULI and ULC in accordance with ULC- S115, ASTM E814 and ANSI/UL1479. The following tested firestop systems were published at the time of this writing: ULI System Nos: C-AJ-1343, -1344, -1345, -1365, -1492, -1493, -2464, -5260, -7042 WL-1225, 1235, 1236 F-C-1086, -2195, -2206, -3061 and -5051. ULC Systems Nos: SP961, -962, -964, -965, -966, -967, -968, -969, -984, -989, -1001, -1002, -1003, -1076, -1077, -1078 and 1079, SPC53, -58, -98, -99 and -100. Contact A/D Fire Protection Systems for a current list of fire rated systems. 4. INSTALLATION Clean all openings to be firestopped by removal of foreign matter and contaminants such as oil, dust, grease, frost, water, surface dirt, old sealants glazing compound, protective coatings, etc. Refer to fire test design / system. Priming: A/D FIREBARRIER Intumescent Caulk does not require any priming. In view of the unpredictability of surface characteristics, it is recommended that a test sample of sealant be applied on the surface to test adhesion. Masking: Areas adjacent to openings to be firestopped can be masked to assure a neat PHYSICAL PROPERTIES*
Properties Results Color Red Odor Mild
Uncured Flow rate (ASTM C920) 175 mL/min Volatile by Volume 35.7% Tack Free Time 30 min. (@ 70F (21C) 50% RH) Specific Gravity 1.25 VOC (ASTM D 3960-92) 0.14 lb/gal US (16 g/L) Cured Flow, Sag or Slump 0 Hardness (A) (ASTM D2240) 35-40 Elongation at Break (ASTM D412) 85% Tensile Strength (ASTM D412) 145 psi Effects of Accelerated Weathering UV Exposure (ASTM C920) No Cracking Cold Temperature (ASTM C920) No Cracking *Values given are not intended for specification preparation.
May 2004 appearance. The masking tape should not be allowed to touch the clean surfaces to which the caulk is to adhere. Remove masking tape immediately. Applications: For caulk and walk systems, simply apply the product where required and let cure. Where backer material (mineral wool, backer rod, etc.) is required by fire test design or system, install backer material as specified. Surfaces of backer material to receive caulk should be recessed in the opening to a depth equal to the required thickness of sealant. Where mineral wool is required backer material, we recommend the use of A/D FIREBARRIER Mineral Wool this high quality material is available pre-cut for easy installation and allows a controlled depth of caulk to be applied for maximum economy. Apply A/D FIREBARRIER Intumescent Caulk in a continuous operation to fill and seal the opening. Tool the caulk to spread it against the backer material and the opening surfaces. Simply fill the annular space to the required depth and form a smooth bead or crown at the surfaces. Excess sealant should be cleaned with water. CURED SEALANT IS USUALLY VERY DIFFICULT TO REMOVE WITHOUT ALTERING OR DAMAGING THE SURFACE TO WHICH THE SEALANT HAS BEEN MISAPPLIED. Precaution: A/D FIREBARRIER Intumescent Caulk is a water-based product. No acetic acid or objectionable byproducts are evolved during application. On direct contact, uncured caulk may irritate eyes. Flush with water and call a physician. Avoid prolonged contact with skin. Keep out of reach of children. To safely use this product, read and abide by Material Safety Data Sheet (MSDS). Shelf Life: A/D FIREBARRIER Intumescent Caulk has shelf life of one year from the date of manufacture when stored in original and unopened container at or below 90F (32C) and above 32F (0C). See top of box or label on pail for date of manufacture (day/ month/ year). 5. AVAILABILITY AND COST Availability: A/D sales offices and technical representatives are located throughout North America. (See below) 6. MAINTENANCE No maintenance should be required. If intumescent caulk becomes damaged, replace damaged portion. Clean surfaces in damaged areas, and repair with fresh A/D FIREBARRIER Intumescent Caulk. 7. TECHNICAL SERVICES Contact nearest A/D representative.
FIREBARRIER ACRYLIC SEALANT
1. PRODUCT NAME A/D FIREBARRIER Acrylic Sealant 2. PRODUCT DESCRIPTION A/D FIREBARRIER Acrylic Sealant is a single component, water-based acrylic sealant intended for use as a firestop system component. Basic Use: A/D FIREBARRIER Acrylic Sealant is designed for economical use in joint and service penetration firestop configurations. It forms a durable, flexible, watertight bond with most construction materials. In most cases, no primer is required. May be applied by caulking gun or trowel. Physical properties will remain stable over time. Composition and Materials: A/D FIREBARRIER Acrylic Sealant is designed to tool easily. It is water based and must be protected from freezing and from water until fully cured. Store and install at temperatures above 40F (5C). Color: Red Packaging: See table 2. Refer to the A/D FIREBARRIER estimating guide for complete volume and coverage information. Application Limitations: Do not install when ambient temperature or temperature of substrate is below 40F (5C). Protect from freezing and water until sealant is fully cured. Do not install to surfaces with special protective or cosmetic coatings without prior consul- tation with manufacturer and first testing adhesion. Do not install where abrasion or physical abuse is anticipated. For best economy and performance the product should be applied to a thickness equal to or slightly greater than the minimum test design thickness. Excessive depth to width ratios may cause sealant failure do not apply excessive thick- ness. As a guideline, we recommend that the minimum test system thicknesses not be exceeded by more than 25%. Standards: A/D FIREBARRIER Acrylic Sealant has been tested in accordance with the following: ANSI/UL1479, ANSI/UL 2079, ASTM E814 and CAN/ULC-S115M. 3. TECHNICAL DATA A/D FIREBARRIER Acrylic Sealant is listed by ULI. For details of rated firestop systems see ULI s Fire Resistance Directory, Volume 2. Systems certified for use in Canada are available under the cUL mark. 4. INSTALLATION Clean all openings to be firestopped by removal of foreign matter and contaminants such as oil, dust, grease, frost, water, surface dirt, old sealants, glazing compounds, protective coatings etc. Cleaning of all surfaces should be done on the same day in which the sealant is applied. Priming: A/D FIREBARRIER Acrylic Sealant does not require priming. In view of the unpredictability of surface characteristics, it is recommended that a test sample of sealant be applied on the surface to test adhesion. Masking: Areas adjacent to openings to be firestopped can be masked to assure a neat appearance. The masking tape should not be allowed to touch the clean surface to which the sealant is to adhere. Remove masking tape immediately. Install backup materials as specified. Excess sealant should be wiped from glass, metal and plastic surfaces while uncured. Clean up is with water. CURED SEALANT IS USUALLY VERY DIFFICULT TO REMOVE WITHOUT ALTERING OR DAM- AGING THE SURFACE TO WHICH THE SEALANT HAS BEEN APPLIED. Precaution: May cause irritation. May be harmful if swallowed. Avoid getting in eyes. Wash hands thoroughly after handling. Use only as directed. Keep out of reach of children. To safely use this product, read and abide by Material Safety Data Sheet (MSDS). Shelf Life: When stored at or below 110F (43C) and above 40F (5C), A/D FIREBARRIER Acrylic Sealant has a shelf life of one year from date of manufacture. Note: Protect from freezing.
Table 1 PHYSICAL PROPERTIES* Color Red pH 7.0 - 9.0 VOC (grams/liter): 65 Flame Spread (ASTM E84) 15 Smoke Developed (ASTM E84) 0 Cure Time 3 - 5 days Skin over Time Overnight Movement Capability: (UL 2079; class I, II, III) + 25 %, maximum Shore A Hardness (ASTM C-661) 15 - 20 Application Temperature 40 - 110F (5 - 43C) Freeze Sensitive Yes Paintable Yes *Values given above are not intended for specification preparation.
5. AVAILABILITY AND COST Availability: A/D sales offices and technical representatives are located throughout North America. (See below) 6. MAINTENANCE No maintenance should be required. If sealant becomes damaged, replace damaged portion. Clean surfaces in damaged area and repair with fresh A/D FIREBARRIER Acrylic Sealant. Damage by other trades should be patched at the expense of trade causing damage. 7. TECHNICAL SERVICES Contact nearest A/D office.
June 25, 2007 Table 2 Type of Packaging Size Volume Coverage at deep x 1 wide 10.1 fl. oz. (300 mL) 18.2 in 3
(300 cm 3 ) 6.1 lineal ft. (1.86 lineal m) Cartridges 28.7 fl. oz. (850 mL) 51.8 in 3
(850 cm 3 ) 17.3 lineal ft. (5.27 lineal m)
Foil packs 20 fl. oz. (600 mL) 36 in 3
(600 cm 3 ) 12.2 lineal ft. (3.72 lineal m)
Pails 5 gal (18.9 L) 1155 in 3
(18900 cm 3 ) 384.4 lineal ft. (117.18 lineal m)
FIREBARRIER SILICONE
1. PRODUCT NAME A/D FIREBARRIER Silicone 2. PRODUCT DESCRIPTION A primerless single component silicone sealant. The sealant cures to a durable, flexible, silicone rubber when exposed to atmospheric moisture. Basic Use: A/D FIREBARRIER Silicone is designed for economical use in joint and service penetration firestop configurations. It forms a durable, flexible, watertight bond with most construction materials. In most cases, no primer is required. Composition and Materials: A/D FIREBARRIER Silicone is designed to tool easily. Its' physical properties will remain stable over time. It may be applied over a wide temperature range, 0F to 120F (-18C to 50C), allowing the sealant to be applied in any season. Packaging: A/D FIREBARRIER Silicone is available in nominal 10.3 fl. oz. (304 mL) and 28.7 fl. oz. (850 mL) cartridges, 20 fl. oz (600 mL) foil packs and 2.64 US gallon (10L) and 4.5 US gallon (17L) bulk containers. Contents are 18.6 in 3 , 49 in 3 , 36.1 in 3 , 634 in 3 and 1050 in 3 respectively. Refer to the A/D FIREBARRIER estimate guide for volume and coverage information. Color: Red or Grey* (*Note: requires special order) Application Limitations: Do not use where abrasion or physical abuse is anticipated. Installation in confined or air- free spaces may inhibit cure. Silicones may be painted, but movement of the silicone may cause the paint film to crack and peel. We recommend the sealant be applied after painting is completed. Do not apply to surfaces that will be in direct contact with food. Do not apply to surfaces with special protective or cosmetic coatings without prior consul- tation of the manufacturer and first testing adhesion. For optimum economy and performance the product should be applied to a thickness equal to or slightly greater than the minimum test design thickness. Excessive depth to width ratios may cause sealant failure Do not apply excessive thickness. As a guideline, A/D Fire Protection Systems recommends that the minimum test system thicknesses not be exceeded by more than 25%. Standards: A/D FIREBARRIER Silicone has been tested in accordance with the following: ULC-S115, Standard Method of Fire Tests of Firestop Systems. ASTM E814-83, Standard Method of Fire Tests of Through- Penetration Fire Stops ANSI/ULC 2079, Tests for Fire Resistance of Building J oint Systems. FGG/BM/CZ System Compatible indicates that this product has been tested, and is monitored on an ongoing basis, to assure its chemical compatibility with FlowGuard Gold, BlazeMaster and Corzan pipe and fittings. FGG/BM/CZ, FlowGuard Gold, BlazeMaster, and Corzan are licensed trademarks of the Lubrizol Corporation. 3. TECHNICAL DATA A/D FIREBARRIER Silicone sealant remains flexible indefinitely between temperatures of -50F and 300F (-45 and 149C). It will not crack or crumble. A/D FIREBARRIER Silicone conforms to the requirements of ASTM C 920 for Elastomeric joint sealants, Type S, Grade NS, class 25, use NT, G, A and M. A/D FIREBARRIER Silicone is listed by ULC, ULI, ITS (Warnock Hersey) and Factory Mutual. For details of rated firestop systems see ULCs List of Equipment and Materials, Fire- stop System and Components, ULIs Fire Resistance Directory, Volume 2, ITS' s Listings Book PHYSICAL PROPERTIES
Properties Results
Uncured Tool/Work Time 5 minutes Skin Over Time @ 25C (77F) Less than 60 minutes @ 50% RH Curing Time @ 25C (77F) 48 hours @ 50% RH Flow, Sag or Slump Nil Specific Gravity 1.13 Maximum strength After 21 days VOC (ASTM D 3960-92) Less than 0.69 lb/gal US
Cured 7 days @ 25C (77F) 50% RH. Hardness (A) (ASTM D2240) 12 Tear Strength (ASTM D624, Die B) 3.5 kN/m (20 ppi) Elongation at Break (ASTM D412) 600% Shrink Factor Negligible ASTM C 920 Type S, NS, 25, NT, G, A & M *Values given above are not intended to be used in specification preparation.
August 2008 and Factory Mutual s Approval Guide. 4. INSTALLATION Clean all openings to be firestopped by removal of foreign matter and contaminants such as oil, dust, grease, frost, water, surface dirt, old sealants glazing compound, protective coatings, etc. Priming: A/D FIREBARRIER Silicone generally does not require priming. In view of the unpredictability of surface characteristics, it is recommended that a test sample of sealant be applied on the surface to test adhesion. Masking: Areas adjacent to openings to be firestopped can be masked to assure a neat appearance. The masking tape should not be allowed to touch the clean surfaces to which the silicone is to adhere. Remove masking tape immediately. A/D FIREBARRIER Mineral Wool is the required backup material in most systems. The material allows a controlled depth of sealant to be applied for maximum economy. Install backup material as specified. Surfaces of mineral wool to receive sealant should be recessed in the opening to a depth equal to the required thick- ness of sealant. Apply A/D FIREBARRIER Silicone in a continuous operation to fill and seal the opening. Tool the sealant to spread it against the backup material and the opening surfaces. Individual penetrations through drywall may not require a backing material for the silicone. Simply fill the annular space to the required depth and form a smooth bead or crown at the surfaces. Excess sealant should be dry- wiped from glass, metal and plastic surfaces while still uncured, followed with a commercial solvent such as xylol, toluol, or methyl ethyl ketone. CURED SEALANT IS USUALLY VERY DIFFICULT TO REMOVE WITHOUT ALTERING OR DAMAGING THE SURFACE TO WHICH THE SEALANT HAS BEEN MISAPPLIED. Precaution: On direct contact, uncured sealant may irritate eyes. Flush with water and call a physician. Avoid prolonged contact with skin. Keep out of reach of children. To safely use this product, read and abide by Material Safety Data Sheet (MSDS). Provide adequate ventilaion. Shelf Life: When stored in original and unopened container at or below 32C (90F), A/D FIREBARRIER Silicone has a shelf life of one year from date of manufacture. 5. AVAILABILITY AND COST Availability: A/D sales offices and technical representatives are located throughout North America. (See below) 6. MAINTENANCE No maintenance should be required. If silicone sealant becomes damaged, replace dam- aged portion. Clean surfaces in damaged areas, and repair with fresh A/D FIREBARRIER Silicone. 7. TECHNICAL SERVICES Contact nearest A/D representative.
FIREBARRIER SILICONE SL
1. PRODUCT NAME A/D FIREBARRIER Silicone SL 2. PRODUCT DESCRIPTION Basic Use: A primerless single component self-leveling silicone sealant. It cures to a durable, flexible, silicone rubber when exposed to atmospheric moisture. It is designed for economical use in joint and service penetration firestop configurations. It forms a durable, flexible, watertight bond with most construction materials. In most cases, no primer is required. Composition and Materials: A/D FIREBARRIER Silicone SL is designed to self-level. No tooling is required. Physical properties will remain stable over time. It may be applied over a wide temperature range, 0F to 120F (-18C to 50C), allowing the sealant to be applied in any season. Packaging: A/D FIREBARRIER Silicone SL is available in nominal 10.3 fl. oz. (304 mL) and 28.7 fl. oz. (850 mL) cartridges, 20 fl. oz (600 mL) foil packs and 2.64 US gallon (10L) and 4.5 US gallon (17L) bulk containers. Contents are 18.6 in 3 , 49 in 3 , 36.1 in 3 , 634 in 3 and 1050 in 3
respectively. Refer to the A/D FIREBARRIER estimate guide for volume and coverage information. Color: Red
Application Limitations: Do not use where abrasion or physical abuse is anticipated. Installation in confined or air-free spaces may inhibit cure. Silicones may be painted, but movement of the silicone may cause the paint film to crack and peel. We recommend the sealant be applied after painting is completed. A/D FIREBARRIER Silicone SL is self-leveling and is therefore limited to horizontal applications. Do not apply to surfaces with special protective or cosmetic coatings without prior consul- tation of the manufacturer and first testing adhesion. Do not apply to surfaces that will be in direct contact with food. For optimum economy and performance the product should be applied to a thickness equal to or slightly greater than the minimum test design thickness. Excessive depth to width ratios may cause sealant failure. Do not apply excessive thick- ness. As a guideline, A/D Fire Protection Systems recom- mends the minimum tested system thicknesses not be exceeded by more than 25%. Standards: A/D FIREBARRIER Silicone SL has been tested in accordance with the following: ULC-S115, Standard Method of Fire Tests of Firestop Systems. ASTM E814-83, Standard Method of Fire Tests of Through-Penetration Fire Stops. ANSI/UL 2079, Tests for Fire Resistance of Building J oint Systems. FGG/BM/CZ System Compatible indicates that this product has been tested, and is monitored on an ongoing basis, to assure its chemical compatibility with FlowGuard Gold, BlazeMaster and Corzan pipe and fittings. FGG/BM/CZ, FlowGuard Gold, BlazeMaster, and Corzan are licensed trademarks of the Lubrizol Corporation. 3. TECHNICAL DATA A/D FIREBARRIER Silicone SL sealant remains flexible indefinitely between temperatures of -50F and 300F (-45C to 149C). It will not crack or crumble. A/D FIREBARRIER Silicone SL is listed by ULC, ULI, ITS and FM. For details of rated firestop systems see ULIs Fire Resistance Directory, Volume 2, ULCs List of Equipment and Materials, Firestop Systems and Components, ITS's Listings Book and FMs Approval Guide.
Contact A/D Fire Protection Systems for a current list of tested systems. 4. INSTALLATION Clean all openings to be firestopped by removal of foreign matter and contaminants such as oil, dust, grease, frost, water, surface dirt, old sealants, glazing compound, protective coatings, etc. Priming: A/D FIREBARRIER Silicone SL generally does not require priming. In view of the PHYSICAL PROPERTIES
Properties Results
Uncured Color Red Skin Over Time @ 25C (77F) 75 minutes Curing Time @ 25C (77F) 48 hours Flow, Sag or Slump Self-leveling Specific Gravity 1.15 VOC (ASTM D 3960-92) <0.50 lb/gal US (59.9 g/L)
Cured (21 days @ 25C (77F) 50% RH) Color Red Hardness (A) (ASTM D2240) 5 Elongation at Break (ASTM D412) 600% Movement Capability (ASTM C719) +100/-50 % Tensile strength (ASTM D412) 98.5 kg/cm 2 (140 psi) Adhesion in peel (ASTM C794)
15.7 lbs. (180 , 2 in. per min., mortar, cohesive failure) *Values given above are not intended for specification preparation. August 2008 unpredictability of surface charac- teristics, it is recommended that a test sample of sealant be applied on the surface to test adhesion. Masking: Areas adjacent to openings to be firestopped can be masked to assure a neat appearance. The masking tape should not be allowed to touch the clean surfaces to which the silicone is to adhere. Remove masking tape immediately. A/D FIREBARRIER Mineral Wool is the required backer material in most tested systems. The material allows a controlled depth of sealant to be applied for maximum economy. Install backer material as specified. Surfaces of mineral wool to receive sealant should be recessed in the opening to a depth equal to the required thickness of sealant. Apply A/D FIREBARRIER Silicone SL in sufficient quantity to fill and seal the opening to the specified depth. It is self-leveling and therefore no tooling is required. Excess sealant should be dry-wiped from glass, metal and plastic surfaces while still uncured, followed with a commercial solvent such as xylol, toluol, or methyl ethyl ketone. Cured sealant may be very difficult to remove without altering or damaging the surface to which the sealant has been misapplied. Precaution: On direct contact, uncured sealant may irritate eyes. Flush with water and call a physician. Avoid prolonged contact with skin. Keep out of reach of children. To safely use this product, read and abide by Material Safety Data Sheet (MSDS). Provide adequate ventilation Shelf Life: When stored in original and unopened container at or below 90F (32C), A/D FIREBARRIER Silicone SL has a shelf life of one year from date of manufacture. 5. AVAILABILITY AND COST Availability: A/D sales offices and technical representatives are located throughout North America. (See below) 6. MAINTENANCE No maintenance should be required. If silicone sealant becomes damaged, replace damaged portion. Clean surfaces in damaged areas, and repair with fresh A/D FIREBARRIER Silicone SL. 7. TECHNICAL SERVICES Contact nearest A/D representative.
FIREBARRIER SPRAYACRYLIC
1. PRODUCT NAME A/D FIREBARRIER SprayAcrylic 2. PRODUCT DESCRIPTION A/D FIREBARRIER SprayAcrylic is a single component, water-based elastomeric that cures to a durable, flexible, fire resistant seal. Basic Use: A/D FIREBARRIER SprayAcrylic is designed for use as a firestop sealant in joint firestop configurations including head-of- wall, curtain wall, perimeter and floor to wall construction joints. Composition and Materials: A/D FIREBARRIER SprayAcrylic is water-based. It is designed for spray and trowel application to vertical and horizontal surfaces. It forms durable, flexible, watertight bonds with most materials. Physical properties will remain stable over time. Product contains mold growth inhibiters. A/D FIREBARRIER SprayAcrylic contains water and is best if protected from freezing. If frozen, thaw completely before use. Store, transport and install at temperatures above 40F (5C). Packaging: A/D FIREBARRIER SprayAcrylic is available in 5 US gallon (18.9 L) pails. Coverage per pail is approximately 67 ft 2 (6.3 m 2 ) at 1/8-in. (3 mm) wet thickness. Color: Red Application Limitations: Do not install when ambient temperature or temperature of substrate is below 40F (5C). Protect from freezing and water until sealant is fully cured. Do not apply to surfaces with special protective or cosmetic coatings without first testing adhesion and prior consultation with manufacturer. Not intended for immersion or continuous exposure to water. Do not install on hot surfaces above 200F (90C). A/D FIREBARRIER SprayAcrylic has been tested in numerous firestop joint firestop systems. For optimum economy and performance, the product should be applied to a thickness equal to or slightly greater than the required minimum test design thickness. Excessive depth to width ratios may cause sealant failure do not apply excessive thickness. As a guideline, we recommend that the minimum test system thicknesses not be exceeded by more than 25%. 3. TECHNICAL DATA Standards: A/D FIREBARRIER SprayAcrylic has been tested and in accordance with the following: ANSI/UL1479, ANSI/UL2079, ASTM E814 and CAN4/ULC-S115M. For details of rated firestop systems see UL s Fire Resistance Directory, Volume 2. Systems certified for use in Canada are available under the cUL mark. Surface Burning Characteristics: (ASTM E84 ) Flame Spread: 15 Smoke Developed: 0 4. INSTALLATION No dilution or mixing is required for use. Clean all openings to be firestopped by removal of foreign matter and contaminants such as oil, dust, grease, frost, water, surface dirt, old sealants, glazing compounds, protective coatings, etc. Priming: Generally, a primer will not be required. It is recommended that a test sample of sealant be applied on the surface to test adhesion. Masking: Surfaces adjacent to openings to be firestopped can be masked to assure a neat appearance. The masking tape should not be allowed to touch the clean surface to which the sealant is to adhere. Remove masking tape immediately. Forming/Backing: Install forming / backing material as specified by the tested firestop system. Unless otherwise specified, A/D FIREBAR- RIER Mineral Wool is the recommended backup material. Application: A/D FIREBARRIER SprayAcrylic may be applied by spray or trowel to vertical and horizontal surfaces. Refer to tested firestop system for minimum wet film thickness that is required - usually 1/8 (3.2 mm). Use a wet film gauge to measure wet film thickness. Apply A/D FIREBARRIER SprayAcrylic so as to seal the mineral wool backer with the required thickness and overlap adjacent surfaces a minimum of in. (13 mm) or as otherwise specified in tested firestop system. Excess sealant should be wiped from glass, metal and plastic surfaces while uncured. Clean up with water. Follow equipment manufacturers instructions for clean up and use. Protect adjacent surfaces from overspray and unintended contact - Cured Sealant May Be Very Difficult To Remove Without Altering Or Damaging The Surface To Which The Sealant Has Been Applied.
Table 1 PHYSICAL PROPERTIES* Color Red pH 7.0 - 9.0 VOC (grams/liter): 65 Flame Spread (ASTM E84) 15 Smoke Development (ASTM E84) 0 Cure Time 3 - 5 days Skin over Time Overnight Movement Capability: (UL 2079; class I, II, III) +25 %, maximum Shore A Hardness (ASTM C-661) 15 - 20 Application Temperature 40 - 110F (5 - 43C) Freeze Sensitive Yes Paintable Yes *Values given above are not intended for specification preparation.
Precautions: May cause irritation. May be harmful if swallowed. Avoid contact with eyes. Wash hands thoroughly after handling. Use only as directed. Keep out of reach of children. To safely use this product, read and abide by Material Safety Data Sheet (MSDS). Shelf Life: A/D FIREBARRIER SprayAcrylic has a shelf life of 1 year from the date of manufacture when stored in original and unopened container below 110F (43C) and above 40F (5C). 5. MAINTENANCE No maintenance should be required. If product becomes damaged, rep- lace with new A/D FIREBARRIER SprayAcrylic. All surfaces should be clean and free of any material that would prevent adhesion. 6. AVAILABILITY AND COST Availability: A/D sales offices and technical representatives are located throughout North America. (See below). 7. TECHNICAL SERVICES Contact nearest A/D office or representative
J une 25, 2007 Table 2 Quick Reference Guide Spray Application of SprayAcrylic Hoses 50 ft of 1/4 in. (I.D.) Blue Max Whip line 6 ft - (I.D.) whip line with swivel Tips 419 - 423 heavy-duty self cleaning reversible type 621 - 625 heavy-duty self cleaning reversible type Spray machine Airless sprayer capable of 3300psi pressure and min. delivery of 0.95 gpm without surging Filters 60-80 mesh in gun & 60-80 in manifold Mixing Heavy-duty drill with paddle for 30 seconds Application Rate 1/8 in. (3 mm) wet Finish Follows profile of backer material Trowel May be toweled Clean-up Water
FIREBARRIER MORTAR
1. PRODUCT NAME A/D FIREBARRIER Mortar 2. PRODUCT DESCRIPTION A non-combustible fiber reinforced, foamed cement mortar. Basic Use: A/D FIREBARRIER Mortar is intended to provide non- combustible and tight fitting firestops at openings and penetrations through fire-rated wall and floor assemblies. A/D FIREBARRIER Mortar powder mixes easily with water to form a mousse or shaving cream-like non- slumping paste. This feature permits easy installation with a minimum of damming. When cured, A/D FIREBARRIER Mortar is self-supporting and therefore may be used for large openings where other firestopping materials are impractical. Composition and Materials: A/D FIREBARRIER Mortar mixes and trowels easily. Tools are cleaned with water. A/D FIREBARRIER Mortar requires and contains no solvents. It is comprised of materials of low toxicity. Dust protection is recom- mended see INSTALLATION. Color: A distinctive charcoal (dark grey). Packaging: A/D FIREBARRIER Mortar is packaged in 15.5 lb. (7 kg) bags. A 275 mL measuring cup is provided in each bag of product for convenience. One bag will yield approximately 850 in. 3 (13,930cm 3 ) - approximately enough for a 1 x 2 ft. (305 x 610 mm) opening at an installed depth of 3 in. (75 mm). Note: Ignores volume occupied by penetrating items. Yield calculation is based on product mixed in accordance with our installation instructions. Application Limitations: Do not install when temperature is below 40F (5C). In horizontal applications, inter- mediate support may be required. Do not permit pedestrian or other traffic. Where A/D FIREBARRIER Mortar will be subject to acidic exposure, like other Portland cement-based products it may require a protective coating. 3. TECHNICAL DATA Physical Properties: Refer to Table 1. Fire Resistance Ratings: A/D FIREBARRIER Mortar has been tested and certified by ULI, ULC, ITS and FM in accordance with ANSI / UL 1479, ASTM E814 and ULC-S115-95. For details of rated firestop systems see ULIs Fire Resistance Directory, Volume 2, ULCs List of Equipment and Materials, Firestop Systems and Components, ITS' s Listing Book and Factory Mutual s Approval Guide. Current systems include: ULI: CAJ-1126, -1128, -1195, - 1196, -2249, -5095, -7029, -7030, - 8029 and WL-8005. ULC: SP196, -229, -230, -326, - 341, -396, -422, -423, -424, -758, - 765 and -767. FM: 91, 92, 94 and 205 ITS: AD/PHV 180-01, -02 and -03.
4. INSTALLATION Clean openings to be fire-stopped by removal of foreign matter and contaminants such as oil, dust, grease, frost, water, dirt, old sealants or glazing compounds, protective coatings, original formwork, etc. Priming: Surfaces to receive A/D FIREBARRIER Mortar generally do not require priming. Keying: For large horizontal openings, it is recommended that A/D FIREBARRIER Mortar be mechanically keyed into the concrete surround and/or that intermediate support be provided. Mixing: A/D FIREBARRIER Mortar is mixed with water in the ratio of 2.6 quarts US (2.5 L) of water to each 15.5 lb. (7 kg) bag. An empty milk container makes a convenient measuring device for water at the job site. A measuring cup is supplied in each bag for convenience when mixing less than a full bag. Portion water and Mortar powder in accordance with Table 2. Forming or Damming: Horizontal openings may be dammed temporarily with any Table 1 - PHYSICAL PROPERTIES Properties Results Before Curing Mix Time 1.5 to 5 min. Pot Life 50 min. (max.) Workability Excellent Wet Density 43.7 + 0.6 pcf (700+10 kg/m) Set Time 10 to 15 hr. After Curing Density 40 + 2.5 pcf (640 + 40 kg/m) Compressive Strength (28 days) 478 + 44 psi (3.3 + 0.3 MPa) Shrinkage None Noncombustibility (ASTM E136) Noncombustible Noncombustibility (CAN4-S114) Noncombustible Thermal Conductivity (ASTM C-518) 0.197 W/m.K @ 24C (1.365 Btu. in/ft.h.F)
*Values given are not intended to be used in specification preparation. October 2004 convenient material (i.e. plywood, polystyrene insulation boards, wire mesh, etc.). Damming is generally not required for vertical openings due to the low slump, dimensional stability and cohesive strength of the mortar paste. Forms, if used, may be removed after 24 hours. Placement: Apply A/D FIRE- BARRIER Mortar paste into opening with trowel, or pour into large horizontal openings from mixer or mixing container. Work paste with trowel to ensure that all voids are filled. Give particular attention to voids between multi- cable/pipe installations. Product may be vibrated for this purpose. Tool surface to desired finish. Clean up with water. Re-Penetration: Should it become necessary to penetrate cured A/D FIREBARRIER Mortar for new or additional building services (i.e. cables or pipes), simply drill or poke through mortar to provide opening of sufficient size. After installation of new penetrating item(s), firestop remaining voids with fresh A/D FIREBARRIER Mortar or with A/D FIREBARRIER Mineral Wool and Silicone where permitted by fire tested system. Precaution: Avoid inhalation of dust or contact with eyes. Use of dust mask and eye protection is recommended. Thoroughly wash skin after contact and before eating, etc. To safely use this product, read and abide by Material Safety Data Sheet (MSDS). 5. AVAILABILITY AND COST Availability: A/D sales offices and technical representatives are located throughout North America. (See below)
6. MAINTENANCE No maintenance should be required. If mortar becomes dam- aged replace damaged portion. Damage by other trades should be patched at the expense of trade causing damage. 7. TECHNICAL SERVICES Contact nearest A/D office.
A/D FIRE PROTECTION SYSTEMS Table 2 A/D FIREBARRIER Mortar Powder Water Full bag, 7 kg (15.5 lb.) 2.5 L (9 cups*) (2.6 quarts US) bag (32 cups*) 1.875 L (6 cups*) (2 quarts US) bag (21 cups*) 1.25 L (4 cups*) (1.3 quarts US) bag (10 cups*) 0.625 (2 cups*) (0.7 quarts US)
*Note: Refers to 275 mL cup supplied in bag. Use clean potable water. Add mortar powder to water in mixer or mixing container. Mix until the mortar paste takes on a consistent mousse-like or shaving cream-like texture. DO NOT ADD MORE WATER continue to mix until mixture wets out. Mixing time will depend on method used - 1 to 3 minutes for mortar mixer, 3 to 5 minutes with electric hand-held mixer. Hand mixing may take longer. NOTE: DO NOT ADD MORE WATER. IT IS NORMAL FOR MIX TO APPEAR QUITE DRY AT FIRST. CONTINUE TO MIX.
FIREBARRIER SEAL and SEAL NS
1. PRODUCT NAME A/D FIREBARRIER Seal and Seal NS 2. PRODUCT DESCRIPTION Single component, water based elastomeric sealants intended for use as firestop system components. Basic Use: A/D FIREBARRIER Seal and Seal NS are designed for economical use in joint and service penetration firestop configurations. They form durable, flexible, watertight bonds with most construction materials. In most cases, no primer is required. Physical properties will remain stable over time. Composition and Materials: A/D FIREBARRIER Seal may be pumped or poured into the opening. A/D FIREBARRIER Seal NS (non- slumping) is designed for trowel and spray applications. A/D FIREBARRIER Seal and Seal NS contain water and must be protected from freezing and from water until fully cured. Store, transport and install at temperatures above 40F (5C). Colors: A/D FIREBARRIER Seal is blue in color. Seal NS is available in white or red please specify when ordering. The white version of Seal NS in 5 gal (18.9 L) pails may be tinted in the field with a variety of color tint pastes. Refer to Seal NS Tinting data sheet. Packaging: A/D FIREBARRIER Seal and Seal NS are available in 5 US gallon (18.9 L) pails. Theoretical coverage per pail is 40 ft 2 (3.8 m 2 ) at an applied wet film thickness of 0.2 in. (5 mm) and approximately 64 ft 2
(5.7 m 2 ) at 1/8-in. (3 mm) wet thickness. Seal NS is also available in 10.3 fl. oz. (304mL) and 28.7 fl. oz. (850 mL) tubes. Application Limitations: Do not install when ambient temperature or temperature of substrate is below 40F (5C). Protect from freezing and water until sealant is fully cured. Do not install to surfaces with special protective or cosmetic coatings without prior consul- tation with manufacturer and first testing adhesion. Do not install where direct contact with food will occur. Do not install where abrasion or physical abuse is anticipated. Seal is intended for horizontal applications only. Seal NS can be used for vertical and horizontal applications. Seal and Seal NS have been tested in numerous firestop joint and through-penetration firestop systems. For best economy and performance the product should be applied to a thickness equal to or slightly greater than the minimum test design thickness. Excessive depth to width ratios may cause sealant failure do not apply excessive thick- ness. As a guideline, we recommend that the minimum test system thicknesses not be exceeded by more than 25%. Standards: A/D FIREBARRIER Seal and Seal NS have been fire tested in accordance with the following: ULC-S115-M, Standard Method of Fire Tests of Firestop Systems, ASTM E814-83 and ANSI/UL 1479, Standard Method of Fire Tests of Through - Penetration Fire Stops and ANSI/UL 2079, "Tests for Fire Resistance of Building Joint Systems." 3. TECHNICAL DATA A/D FIREBARRIER Seal and Seal NS are listed by ULC, ULI, ITS and FM. For details of rated firestop systems see ULI s Fire Resistance Directory, Volume 2, ULC s List of Equipment and Materials, Firestop Systems and Components, ITS' s Listings Book and FM s Approval Guide. ULC: JF9, -29, -50, -51, -93, -99 and -100. HW36, -38, -39, -40, -41, -42, -43, -44, -45, -46, -47, -48, -49, -50, -51, -52, -53, -54, Table 1 - PHYSICAL PROPERTIES Result Property Seal Seal NS Uncured Color blue white or red VOC (ASTM D3960) 0.2 lb/gal US (26 g/L) 0.23 lb/gal US (27 g/L) % Volatile by volume (ASTM D2697) 43.0 41.9 Tack Free Time*, hours 4 1 Curing Time*, hours 24 96 Brookfield Viscosity (nominal), centipoises 10,000 (LVF, spindle 4 @ 5 rpm) 200,000 (RVT, spindle E @ 10 rpm) pH 9.1 8.5 8.8 Weight per Gallon, lb / imp. gal. 13.5 Cured Color blue white or red Dirt Resistance Excellent Tensile Strength (ASTM D412), psi 330 365 Tensile Strength (ASTM D2370), psi 385 Elongation at break (ASTM D412), % 255 350 Elongation at break (ASTM D2370), % 370 * Curing time will vary with temperature, humidity and thickness. Values given above are not intended for specification preparation.
-55 and -56. SP218, -219, -220, -221, -759, -761, -881, -882 and -1080. ULI: CAJ-1125, -1127, -1324 and 1450. FF-D-1032 and -1038. FW-D- 1029 and -1036. HW-D-0060, -0061, -0118, -0119, -0120, -0247, -0249, -0250, -0254, -0282, -0301, -0302, -0303, -1012, -1020 and -1029. WW-D-1033. FM: 90, 93, 95. ITS: AD/PH 180-01, -02 and -03. AD/PHV 120-01, -02 and -03, 180-09, -10, -11 and -12. 4. INSTALLATION Clean all openings to be firestopped by removal of foreign matter and contaminants such as oil, dust, grease, frost, water, surface dirt, old sealants, glazing compounds, protective coatings etc. Cleaning of all surfaces should be done on the same day in which the sealant is applied. Priming: A/D FIREBARRIER Seal and Seal NS generally do not require priming. In view of the unpredictability of surface charac- teristics, it is recommended that a test sample of sealant be applied on the surface to test adhesion. Masking: Areas adjacent to openings to be firestopped can be masked to assure a neat appearance. The masking tape should not be allowed to touch the clean surface to which the seal is to adhere. Remove masking tape immediately. A/D FIREBARRIER Mineral Wool is the required backup material for firestops. Install backup materials as specified. A/D FIREBARRIER Seal is intended only for horizontal applications. Check fire test design for required thickness - usually 0.2 in. (5 mm) wet. Pour or pump Seal in a continuous operation to fill and seal the opening. A light pass with a trowel over the surface of the seal will ensure a smooth surface. A/D FIREBARRIER Seal NS is non- slumping and may be sprayed or trowelled for vertical and / or horizontal applications. For spray applications refer to Table 2. Check fire test design for required minimum wet film thickness - usually 0.2 in. (5 mm) or 1/8 in. (3.2 mm). Excess sealant should be wiped from glass, metal and plastic surfaces while uncured. Clean up is with water. CURED SEALANT IS USUALLY VERY DIFFICULT TO REMOVE WITHOUT ALTERING OR DAM- AGING THE SURFACE TO WHICH THE SEALANT HAS BEEN APPLIED. Precaution: May cause irritation. May be harmful if swallowed. Avoid getting in eyes. Wash hands thoroughly after handling. Use only as directed. Keep out of reach of children. To safely use this product, read and abide by Material Safety Data Sheet (MSDS). Shelf Life: When stored at or below 80F (27C) and above 40F (5C), A/D FIREBARRIER Seal and Seal NS have a shelf life of one year from date of manufacture. Note: Protect from freezing. 5. AVAILABILITY AND COST Availability: A/D sales offices and technical representatives are located throughout North America. (See below) 6. MAINTENANCE No maintenance should be required. If seal becomes damaged, replace damaged portion. Clean surfaces in damaged area and repair with fresh A/D FIRE-BARRIER Seal or Seal NS. Damage by other trades should be patched at the expense of trade causing damage. 7. TECHNICAL SERVICES Contact nearest A/D office.
A/D FIRE PROTECTION SYSTEMS Head Office: 420 Tapscott Road, Scarborough, Ontario, M1B 1Y4 Tel: (800) 263-4087 or (416) 292-2361 Fax: (416) 298-5887 www.adfire.com Contact By State or Province AK, AR, AZ, CA, CO, HI, ID, LA, MT, NM, NV, OK, OR, TX, WA, WY, UT: Tel: (888) 323-3473, Fax: (949) 458-9220 AL, CT, DC, DE, FL, GA, IA, IL, IN, KS, KY, MA, MD, ME, MI, MN, MO, MS, NC, ND, NE, NH, NJ, NY, OH, PA, RI, SC, SD, TN, VA, VT, WI, WV: Tel: (800) 650-0881, Fax: (613) 841-7768 NB, NF, NS, PE, QC: Tel: (800) 914-6506, Fax: (450) 661-8776 AB, BC, MB, ON, SK: Tel: (800) 263-4087, Fax: (416) 298-5887 Table 2 Quick Reference Guide - Spray Application of Seal NS Hoses 300 ft max. 50ft of 3/8 in. dia. & 250 ft of 1/4 in. dia. Whip line 9 ft whip line with swivel Tips 5/17 heavy-duty self cleaning reversible type Spray machine Airless sprayer capable of 3000psi pressure and min. delivery of 1.0 gpm without surging Filters 60-80 mesh in gun & 60-80 in manifold Mixing Heavy-duty drill with paddle for 2 min. Application Rate 1/8 in. (3 mm) wet Finish Follows profile of backer material Trowel May be toweled Clean-up 10 gal water
April 2004 SELLOS CORTA FUEGO Y HUMO ESPECIFICACIN SECCIN 07860 1 General 1.1 LA SECCION INCLUYE 0.1 Cumplir con la Divisin 1, Requisitos General y Documentos referidos aqu 0.2 Es la intencin de esta seccin de las especificaciones de establecer una nica, y competente fuente que sea responsable de proveer toda la mano de obra, materiales, productos, equipos y servicios, para suministrar e instalar el trabajo del sistema de corta-fuego y sello de humo para toda la obra. 1.2 TRABAJO RELACIONADO ESPECIFICADO EN OTRO LUGAR (Especificar) 1.3 SECCIONES RELACIONADAS (Especificar) 1.4 ESTANDARES DE REFERENCIA 0.1 (ANSI/UL 1479 - Pruebas de Fuego de Corta Fuego a Travs de Penetraciones) (CAN4-S115-M85 - Mtodo Estndar de Pruebas de Fuego de Sistemas Corta Fuego) (ASTM E814 - Mtodo de Prueba de Pruebas de Fuego de Corta Fuego a Travs de Penetraciones) (ANSI/UL 2079 - Pruebas para Resistencia al Fuego de Sistemas de Juntas para Edificios). 1.5 DESCRIPCION DEL SISTEMA 0.1 Materiales Corta Fuego: Proveer Sistema(s) Corta Fuego para proveer y mantener una clasificacin de resistencia al fuego, como est indicado en los Planos y de acuerdo a los detalles de diseo de UL, WH, ULC, cUL o FM. 1.6 REMISIONES (Submittals) 0.1 (Especificar) (datos del fabricante) (planos de taller) (muestras) 1.7 ASEGURAR CALIDAD 0.1 Fabricante: Compaa especializada en fabricacin de productos de esta Seccin con un mnimo de tres (3) aos de experiencia documentada, y un sistema de gerencia de calidad registrado de acuerdo con los requisitos de ISO 9001:2000. 0.2 Aplicador: Compaa que tenga un mnimo de tres (3) aos de experiencia en la instalacin de los materiales aqu especificados en proyectos comparables a este proyecto. 1.8 REQUISITOS DE NORMAS 0.1 Cumplir con (Cdigos de Construccin locales), listados de (UL) (ULC) (cUL) (ITS) (FM) y (ANSI/UL 2079) (CAN4-S115) (ASTM E814) prueba de fuego estndar para obtener la clasificacin de proteccin al fuego requerida. 1.9 REQUISITOS AMBIENTALES 0.1 Cumplir con las recomendaciones de instalacin del fabricante en cuanto a temperatura, humedad, y condiciones de ventilacin. 1.10 ENTREGA, ALMACENAJE Y MANEJO 0.1 Entregar materiales al sitio de la obra en los envases originales del fabricante, intactos sellados y etiquetados por el fabricante. Manejar y almacenar los materiales de acuerdo a las instrucciones del fabricante. 1.11 CONDICIONES DEL PROYECTO/SITIO DE OBRA 0.1 Cumplir con los requisitos recomendados del fabricante en cuanto a temperatura, humedad relativa y condiciones del substrato durante la aplicacin y curado de los materiales. 1.12 SECUENCIA Y PROGRAMACIN 0.1 Coordinar con otras Secciones relacionadas. Programar el trabajo de otras actividades de manera que las aplicaciones de corta fuego puedan ser inspeccionadas antes de ser cubiertas por construccin subsecuente. 2 Productos 2.1 FABRICANTES ACEPTADOS 0.1 Proveer corta fuego de selladores de silicona, selladores a base de agua, morteros, o sistemas corta fuego del siguiente fabricante: A/D Fire Protection Systems. 2.2 MATERIALES 0.1 Los material(es) deben ser: A/D FIREBARRIER Mineral Wool (Lana Mineral) A/D FIREBARRIER Silicone and Silicone SL (Silicona) A/D FIREBARRIER Mortar (Mortero) A/D FIREBARRIER Collars (Collarines) A/D FIREBARRIER Intumescent Caulk (Calafateo Intumescente) A/D FIREBARRIER Pillows (Almohadas) A/D FIREBARRIER Seal and Seal NS A/D FIREBARRIER SprayMastic A/D FIREBARRIER Wrap Strip (Banda para Enrollar) A/D FIREBARRIER Putty (Masilla) A/D FIREBARRIER Putty Pads (Pads de Masilla) A/D FIREBARRIER Inserts (Pads de Masilla pequeos). 0.2 Clasificaciones de Sistemas Corta Fuego: Cumplir con los requisitos de cdigo de construccin aplicable para las ubicaciones y horas de clasificacin contra fuego de las designaciones (F) (T) (FT) (FH) (FTH). 0.3 Materiales de relleno y soporte trasero, soportes y anclajes deben ser de acuerdo a las recomendaciones del fabricante, del sistema/diseo de corta fuego probado, y aceptable a las autoridades que tienen jurisdiccin. 0.4 Base antioxidante: como sea requerido por el fabricante, y que sea compatible con el sistema y los materiales contiguos. 0.5 Agua: Potable 3 Ejecucion 3.1 EXAMINACION 0.1 Examinar substratos, aberturas, espacios, construccin adyacente, y condiciones bajo las cuales el corta fuego va a ser instalado. Confirmar compatibilidad con las superficies. 0.2 Verificar artculos que penetran estan fijados en forma segura, y ubicados debidamente dejando el debido espacio entre las penetraciones y las superficies de las aberturas. 3.2 PREPARACION 0.1 Las superficies que van a recibir el corta fuego deben estar libres de sucio, polvo, grasa, aceite, xido, materiales sueltos, agentes de separacin, congelacin, humedad o cualquier otro material que impida la unin del material corta fuego al substrato o artculo penetrante(s). 0.2 Aplicar base antioxidante a los substratos de acuerdo con las instrucciones escritas del fabricante. 0.3 No aplique corta fuego y sellos de humo a superficies previamente pintadas o tratadas con selladores, compuestos de curado, repelentes de agua o otros revestimientos a menos que se hayan hecho pruebas que aseguren compatibilidad de materiales. Remueva los revestimientos que sean requeridos. 0.4 Asegurar que los anclajes, materiales de soporte, clips, mangas, soportes y otros materiales relacionados usados en las pruebas de fuego sean utilizados. 0.5 Cubrir cuando sea necesario, para prevenir que los materiales corta fuego hagan contacto con superficies adyacentes que quedarn expuestas durante el trabajo. Remover la cinta adhesiva tan pronto sea posible sin daar el material corta fuego o el substrato. 3.3 INSTALACION 0.1 Cumplir con los listados de (UL) (ULC) (cUL) (ITS) (FM), y con las instrucciones del fabricante para el tipo de material y condicin de la abertura en cada caso. Consultar con el fabricante para determinar el procedimiento adecuado para las condiciones no totalmente cubiertas en las instrucciones escritas. Registrar por escrito cualesquiera instrucciones recibidas, con copia al fabricante. 0.2 Remover material corta fuego excedente prontamente en lo que el Trabajo avanza y cuando sea terminado. 0.3 Proveer bloqueos a prueba de goteos tal como sean requeridos para sellar aberturas y contener el material corta fuego hasta que se haya curado. Instalar los bloqueos de acuerdo al diseo de prueba y las instrucciones del fabricante. 3.4 CONTROL DE CALIDAD DE CAMPO 0.1 Notificar al Consultor cuando las instalaciones terminadas estn listas para ser inspeccionadas antes de encerrar o tapar las reas que contienen los materiales corta fuego. 0.2 Organizar las inspecciones por la compaa de inspecciones y pruebas independiente del Propietario, seleccionada y pagada por el Propietario. 0.3 Siguiendo las inspecciones de campo, proveer toda reparacin como sea requerido para asegurar cumplimiento con los Documentos del Contrato. 3.5 LIMPIEZA Y PROTECCIN 0.1 Al terminar este trabajo, remover todos los materiales, equipo y materiales sobrantes del sitio de la obra. Dejar el rea de trabajo y superficies adyacentes en una condicin aceptable al Consultor. StonCor South Cone con ms de 30 aos de experiencia en el pas, empresa del Grupo RPM, ofrece al mercado industrial una solucin integral en la proteccin anticorrosiva. Dicha solucin est compuesta por tres lneas de productos: Stoncor South Cone S.A. Einstein 1095 - Parque O.K.S. (B1619JWA) Garn-Bs.As. (54) 03327-442222 - Fax:442223 stoncor@stoncor.com.ar www.stoncor.com www.stoncor.com.ar Argentina Brasil Chile Peru Uruguay Bolivia Paraguay South Cone Carboline Company 350 Hanley Industrial Court St. Louis, MO 63144-1599 1-800-848-4645 Fax. 1-314-644-4617 www.carboline.com Planta Industrial Garin - Argentina