1) Frascold Selection Software, Version 2.08/27/2014, 8/27/2014 Input Data Compressor
1) Frascold Selection Software, Version 2.08/27/2014, 8/27/2014 Input Data Compressor
08/27/2014, 8/27/2014
INPUT DATA
Compressor
NRH4-90-300Y
Power supply STANDARD!Capacity step (tent.data)
100% Liquid system
none Refrigerant R134a Reference temperature dew point temperature
Condensing temperature
22.0
C
Subcooling8.2 K
Evaporating temperature
-12.0
C
Superheating
20.0 K'Useful fraction of superheating 100.0 % RESULTS PRODUCT SELECTION
NRH4-90-300YRefrigerating capacity
kW 123.23$Refrigerating capacity (ref)
kW 115.02Evaporator capacity
kW 123.23Power input
kW 26.39"Condenser capacity, theor.
kW 149.62CurrentA
54.0COP-
4.67 Mass flowkg/s 0.651Operating frequency
Hz
50
Power supply-
400/3/50 PWSOperating mode- normalEvaporating pressure bar 1.9 Suction gas superheatingK
20.0 Suction gas temperature
C 8.0!Discharge temperature
!C
!59.9"Condensing pressure "bar "6.1#Liquid temperature
#C
#13.8