Professional Documents
Culture Documents
WFC SC 50 en (Yajaki)
WFC SC 50 en (Yajaki)
com
WFC-SC50
Specifications:
Water Fired Chiller absorption type with H
2
O/LiBr
System functionality provides cooling
Utilizing Hot Water
ITEM
MODEL
WFC-SC50
kW 175.8
kW -
Inlet 12.5
Outlet
7.0
Inlet -
Outlet -
kPa 40.2
kPa 588
L/sec 7.64
m
3
/hr 27.5
L 120
kW 427.0
Inlet 31.0
Outlet
35.0
kPa 41.2
kPa 588
L/sec 25.5
m
3
/hr 91.8
L 335
kW 251
Inlet 88
Outlet
83
Inlet Limit 70 - 95
kPa 85.2
kPa 588
L/sec 12.0
m
3
/hr 43.2
L 170
W 590
On
Off
mm 1,785
mm 1,960 (2,060)
mm 2,085 (2,223)
A 80
A 80
A 80
kg 2,100
kg 2,725
*1.Power consumption of chiller only (excluding recirculation pumps and cooling tower fan)
*2. Dimensions in ( ) include junction box.
*3.Dimensions in ( ) include leveling bolt and eye bolt
- Specification are subject to change without prior notice.
- The allowable flow rate ranges are: Chilled-hot water: 80 to 120% of nominal, Cooling water: 100 to 120% of nominal.
-The table shows standard operating condition ( i.e. 88 C heat medium inlet temperature)
Cooling Capacity
Heating Capacity
Chilled Water
and
Hot Water
Chilled Water
Temperature
Hot Water
Temperature
Evaporator Pressure Loss(Max)
Max Operating Pressure
Water Retention Volume
Rated Water Flow
Cooling
Water
Water Retention Volume
Cooling Water
Temperature
Abs.&Cond.Pressure Loss(Max)
Heat Rejection
Water Retention Volume
Electrical
Power Source 400V 50Hz 3ph.
Consumption *1
Heat Medium Generator. Pressure Loss(Max)
Rated Water Flow
Cooling Water
Weight
Dry Weight
Operating Weight
Piping
Chilled Water
Heat Medium
Height *3
Dimension
Max Operating Pressure
Max Operating Pressure
Rated Water Flow
Heat Input
Heat Medium
Temperature
Width
Depth *2
Control