Wind Load

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Project

ABEINSA -BARKA
J ob no.
Calcs for
WIND LOAD
Start page no./Revision
1 00
Calcs by
GPE
Calcs date
9/23/2012
Checked by Checked date Approved by Approved date
WIND LOADING (BS6399)
TEDDS calculation version 3.0.05
48780
3
3
0
0
0
Plan
33000
1
4
5
0
9
Elevation
Bui l di ng dat a
Type of roof; Duopitch
Length of building; L = 48780 mm
Width of building; W =33000 mm
Height to eaves; H =11600 mm
Pitch of roof; 0 =10.0 deg
Reference height; Hr =14509 mm
Dynami c cl assi f i cat i on
Building type factor (Table 1); Kb =1.0
Dynamic augmentation factor (1.6.1); Cr =[Kb ( H / (0.1 m) )
0.75
] / ( 800 log( H / (0.1 m))) = 0.02
Si t e wi nd speed
Location; Other
Basic wind speed (Figure 6 BS6399:Pt 2) Vb =20.0 m/s
Site altitude S = 10 m
Upwind distance from sea to site dsea = 10 km
Direction factor Sd =1.00
Seasonal factor Ss =1.00
Probability factor Sp =1.00
Critical gap between buildings; g = 5000 mm
Topography
Type of feature; Cliffs and escarpments
Actual length of upwind slope in wind direction; Lu =50000 mm
Effective height of feature; Z = 20000 mm
Upwind slope in upwind direction; U =Z / Lu = 0.40
Effective slope of topographic feature; e = 0.30
Effective length of upwind slope (cl 2.2.2.2.4); Le =Z / 0.3 = 66667 mm
Horiz distance of the site from the top of the crest; x =-5000 mm
Altitude of upwind base of topographic feature; T =-8.000 m
Site altitude; S = 10.000 m
Topographic location factor (Figure 10a); s =0.46
Project
ABEINSA -BARKA
J ob no.
Calcs for
WIND LOAD
Start page no./Revision
2 00
Calcs by
GPE
Calcs date
9/23/2012
Checked by Checked date Approved by Approved date
Topographic increment (Table 25); Sh =0.6 s = 0.27
Altitude factor; Sa =1 + 0.001 T/1m = 0.99
Site wind speed Vs =Vb Sa Sd Ss Sp =19.8 m/s
Terrain category; Sea
Displacement height (sheltering effect excluded); Hd = 0mm
The vel oci t y pressure f or t he wi ndward f ace of t he bui l di ng wi t h a 0 degree wi nd i s t o be consi dered as 1 part as
t he hei ght h i s l ess t han b (cl .2.2.3.2)
Dynami c pressure - wi ndward wal l - Wi nd 0 deg
Reference height (at which q is sought); Href =11600mm
Effective height; He = max(Href Hd, 0.4 Href) =11600mm
Fetch factor (Table 22); Sc =1.096
Turbulence factor (Table 22); St = 0.176
Gust peak factor; gt =3.44
Terrain and building factor; Sb =Sc (1 + (gt St) + Sh) =2.06
Effective wind speed; Ve =Vs Sb =40.9 m/s
Dynamic pressure; qs = 0.613 kg/m
3
Ve
2
=1.023 kN/m
2
Dynami c pressure - roof
Reference height (at which q is sought); Href =14509mm
Effective height; He = max(Href Hd, 0.4 Href) =14509mm
Fetch factor (Table 22); Sc =1.142
Turbulence factor (Table 22); St = 0.172
Gust peak factor; gt =3.44
Terrain and building factor; Sb =Sc (1 + (gt St) + Sh) =2.13
Effective wind speed; Ve =Vs Sb =42.3 m/s
Dynamic pressure; qs = 0.613 kg/m
3
Ve
2
=1.095 kN/m
2
Si ze ef f ect f act ors
Diagonal dimension for gablewall; aeg =36.0 m
External size effect factor gablewall; Caeg = 0.851
Diagonal dimension for side wall; aes =50.1 m
External size effect factor side wall; Caes =0.826
Diagonal dimension for roof; aer = 51.6 m
External size effect factor roof; Caer =0.824
Room/storey volume for internal size effect factor; Vi = 0.125 m
3
Diagonal dimension for internal size effect factors; ai =10 ( Vi )
1/3
=5.000 m
Internal size effect factor; Cai =1.000
Pressures and f orces
Net pressure; p = qs cpe Cae - qs cpi Cai;
Net force; Fw = p Aref;
Project
ABEINSA -BARKA
J ob no.
Calcs for
WIND LOAD
Start page no./Revision
3 00
Calcs by
GPE
Calcs date
9/23/2012
Checked by Checked date Approved by Approved date
Roof l oad case 1 - Wi nd 0, cpi -0.30, - cpe
Zone
Ext pressure
coefficient,
cpe
Dynamic
pressure, qs
(kN/m
2
)
External size
factor, Cae
Net
Pressure,
p (kN/m
2
)
Area,
Aref (m
2
)
Net force,
Fw (kN)
A (-ve) -1.45 1.10 0.824 -0.98 85.51
-83.79
B (-ve) -1.00 1.10 0.824 -0.57 58.23
-33.41
C (-ve) -0.50 1.10 0.824 -0.12 673.55
-82.57
E (-ve) -1.10 1.10 0.824 -0.66 85.51
-56.79
F (-ve) -0.60 1.10 0.824 -0.21 58.23
-12.39
G (-ve) -0.45 1.10 0.824 -0.08 673.55
-52.18
Total vertical net force; Fw,v = -316.27 kN
Total horizontal net force; Fw,h = -13.62 kN
Wal l s l oad case 1 - Wi nd 0, cpi -0.30, - cpe
Zone
Ext pressure
coefficient,
cpe
Dynamic
pressure, qs
(kN/m
2
)
External size
factor, Cae
Net
Pressure,
p (kN/m
2
)
Area,
Aref (m
2
)
Net force,
Fw (kN)
A -1.30 1.10 0.851 -0.88 70.29
-62.08
B -0.80 1.10 0.851 -0.42 312.93
-130.51
C -0.50 1.10 0.851 -0.14 47.58
-6.54
w 0.70 1.02 0.826 0.90 565.85
506.66
l -0.50 1.02 0.826 -0.12 565.85
-65.41
Overal l l oadi ng
Equiv leeward net force for overall section; Fl =Fw,wl = -65.4 kN
Net windward force for overall section; Fw = Fw,ww =506.7 kN
Overall loading overall section; Fw,w =0.85 (1 + Cr) (Fw - Fl +Fw,h) =484.8 kN
Roof l oad case 2 - Wi nd 0, cpi -0.30, + cpe
Zone
Ext pressure
coefficient,
cpe
Dynamic
pressure, qs
(kN/m
2
)
External size
factor, Cae
Net
Pressure,
p (kN/m
2
)
Area,
Aref (m
2
)
Net force,
Fw (kN)
A (+ve) 0.10 1.10 0.824 0.42 85.51
35.82
B (+ve) 0.10 1.10 0.824 0.42 58.23
24.39
C (+ve) 0.10 1.10 0.824 0.42 673.55
282.15
E (+ve) -1.10 1.10 0.824 -0.66 85.51
-56.79
F (+ve) -0.60 1.10 0.824 -0.21 58.23
-12.39
G (+ve) -0.45 1.10 0.824 -0.08 673.55
-52.18
Total vertical net force; Fw,v = 217.64 kN
Total horizontal net force; Fw,h = 80.52 kN
Project
ABEINSA -BARKA
J ob no.
Calcs for
WIND LOAD
Start page no./Revision
4 00
Calcs by
GPE
Calcs date
9/23/2012
Checked by Checked date Approved by Approved date
Wal l s l oad case 2 - Wi nd 0, cpi -0.30, + cpe
Zone
Ext pressure
coefficient,
cpe
Dynamic
pressure, qs
(kN/m
2
)
External size
factor, Cae
Net
Pressure,
p (kN/m
2
)
Area,
Aref (m
2
)
Net force,
Fw (kN)
A -1.30 1.10 0.851 -0.88 70.29
-62.08
B -0.80 1.10 0.851 -0.42 312.93
-130.51
C -0.50 1.10 0.851 -0.14 47.58
-6.54
w 0.70 1.02 0.826 0.90 565.85
506.66
l -0.50 1.02 0.826 -0.12 565.85
-65.41
Overal l l oadi ng
Equiv leeward net force for overall section; Fl =Fw,wl = -65.4 kN
Net windward force for overall section; Fw = Fw,ww =506.7 kN
Overall loading overall section; Fw,w =0.85 (1 + Cr) (Fw - Fl +Fw,h) =566.6 kN
Roof l oad case 3 - Wi nd 0, cpi 0.20, - cpe
Zone
Ext pressure
coefficient,
cpe
Dynamic
pressure, qs
(kN/m
2
)
External size
factor, Cae
Net
Pressure,
p (kN/m
2
)
Area,
Aref (m
2
)
Net force,
Fw (kN)
A (-ve) -1.45 1.10 0.824 -1.53 85.51
-130.63
B (-ve) -1.00 1.10 0.824 -1.12 58.23
-65.31
C (-ve) -0.50 1.10 0.824 -0.67 673.55
-451.51
E (-ve) -1.10 1.10 0.824 -1.21 85.51
-103.62
F (-ve) -0.60 1.10 0.824 -0.76 58.23
-44.29
G (-ve) -0.45 1.10 0.824 -0.63 673.55
-421.12
Total vertical net force; Fw,v = -1197.99 kN
Total horizontal net force; Fw,h = -13.62 kN
Wal l s l oad case 3 - Wi nd 0, cpi 0.20, - cpe
Zone
Ext pressure
coefficient,
cpe
Dynamic
pressure, qs
(kN/m
2
)
External size
factor, Cae
Net
Pressure,
p (kN/m
2
)
Area,
Aref (m
2
)
Net force,
Fw (kN)
A -1.30 1.10 0.851 -1.43 70.29
-100.58
B -0.80 1.10 0.851 -0.96 312.93
-301.91
C -0.50 1.10 0.851 -0.69 47.58
-32.60
w 0.70 1.02 0.826 0.38 565.85
217.17
l -0.50 1.02 0.826 -0.63 565.85
-354.90
Overal l l oadi ng
Equiv leeward net force for overall section; Fl =Fw,wl = -354.9 kN
Net windward force for overall section; Fw = Fw,ww =217.2 kN
Overall loading overall section; Fw,w =0.85 (1 + Cr) (Fw - Fl +Fw,h) =484.8 kN
Project
ABEINSA -BARKA
J ob no.
Calcs for
WIND LOAD
Start page no./Revision
5 00
Calcs by
GPE
Calcs date
9/23/2012
Checked by Checked date Approved by Approved date
Roof l oad case 4 - Wi nd 0, cpi 0.20, + cpe
Zone
Ext pressure
coefficient,
cpe
Dynamic
pressure, qs
(kN/m
2
)
External size
factor, Cae
Net
Pressure,
p (kN/m
2
)
Area,
Aref (m
2
)
Net force,
Fw (kN)
A (+ve) 0.10 1.10 0.824 -0.13 85.51
-11.02
B (+ve) 0.10 1.10 0.824 -0.13 58.23
-7.50
C (+ve) 0.10 1.10 0.824 -0.13 673.55
-86.79
E (+ve) -1.10 1.10 0.824 -1.21 85.51
-103.62
F (+ve) -0.60 1.10 0.824 -0.76 58.23
-44.29
G (+ve) -0.45 1.10 0.824 -0.63 673.55
-421.12
Total vertical net force; Fw,v = -664.09 kN
Total horizontal net force; Fw,h = 80.52 kN
Wal l s l oad case 4 - Wi nd 0, cpi 0.20, + cpe
Zone
Ext pressure
coefficient,
cpe
Dynamic
pressure, qs
(kN/m
2
)
External size
factor, Cae
Net
Pressure,
p (kN/m
2
)
Area,
Aref (m
2
)
Net force,
Fw (kN)
A -1.30 1.10 0.851 -1.43 70.29
-100.58
B -0.80 1.10 0.851 -0.96 312.93
-301.91
C -0.50 1.10 0.851 -0.69 47.58
-32.60
w 0.70 1.02 0.826 0.38 565.85
217.17
l -0.50 1.02 0.826 -0.63 565.85
-354.90
Overal l l oadi ng
Equiv leeward net force for overall section; Fl =Fw,wl = -354.9 kN
Net windward force for overall section; Fw = Fw,ww =217.2 kN
Overall loading overall section; Fw,w =0.85 (1 + Cr) (Fw - Fl +Fw,h) =566.6 kN
A A B
C
14509 19761 14509
2
9
0
2
1
3
5
9
8
E E F
G
2
9
0
2
1
3
5
9
8
48780
3
3
0
0
0
W
i
n
d

-

0
o
Plan view - Duopitch roof
Project
ABEINSA -BARKA
J ob no.
Calcs for
WIND LOAD
Start page no./Revision
6 00
Calcs by
GPE
Calcs date
9/23/2012
Checked by Checked date Approved by Approved date
A B C
3
9
8
1
23215
5
8
0
4
33000
1
4
5
0
9
Side face
w
48780
1
1
6
0
0
Windward face
l
48780
1
1
6
0
0
Leeward face
;