CUSTOMER : NEYVELI LIGNITE CORPORATION
Gen.Capacity
Rated Power Factor
Gen.Capacity at 0.85 PF
= 247 MVA
= 0.85
= 210 MW
Terminal Voltage
= 15.75KV/110V
Synchronous reactance Xd
= 2.05 pu
= 2.05 x 15.75 x 15.75/247 MVA
= 2.058 ohm.
Transient reactance Xd
= 0.217 pu
= 0.217 x 15.75 x 15.75/247
MVA
Sub transient reactance Xd
= 0.217 ohms
= 0.105 pu
CT/PT Details:
Generator Phase CT / Neutral pri
Phase CT / Neutral sec
= 10000 A
=5A
Generator PT ratio
CT/PT Ratio
= 13.97
Referred to sec
= 9055 / 10000/5
Page 1 of 13
= 4.53 A
a.biased differential
Since we are setting the relay as Biased differential we use the
following settings
The minimum Pick-up current ( Is1 )
= 10%
= 120%
Group 1
Referred to sec
= 9055 / 10000/5
= 4.53 A
Since we are setting the relay as High Impedance Differential we
use the
Following setting.
Maximum Value of the three phase symmetrical short circuit current
Fault current referred to the secondary
Voltage developed across the relay circuit
Vr =KIf x (RCT + 2 RL)
(Note: RCT and RL are assumed, as it is not available)
Page 2 of 13
Active settings
Group 1
= CT Ratio / PT Ratio
= 13.97
Diameter of circle
= Xd x 13.97
= 2.058 x 13.97
= 28.75 ohm
Offset
= 0.5 x Xd x 13.97
= 0.5 x 0.217 x 13.97
= 1.52 ohm
Page 3 of 13
Status
Enabled
Setting
47.00 Hz
Time Delay 3.000 s
Status
Disabled
Status
Disabled
Page 4 of 13
F<4 Status
Disabled
F< Function Link 0000
OVER FREQUENCY
F>1 Status
Disabled
F>2 Status
Disabled
Alarm
Enabled
Current Set 0.25 A
Time Delay : 5s
Trip
Enabled
Current Set 0.36 A
k Setting 16.38
kRESET
16.38
tMAX
500.00 s
tMIN
0.25 s
tMIN : This value has been chosen with the assumption that the
machine can withstand 0.5 pu of unbalance for a period of 500 sec.
tMIN :This setting has to be chosen as to co-ordinate with down
stream over current relays / Zone 3 of distance protection / dead
time setting of auto recloser / CB pole discrepancy timer , which
ever is higher.
---(CUSTOMER RECOMMNADED )
I2>1
I2>1
I2>2
I2>2
I2>2
I2>2
I2>2
I2>2
Page 5 of 13
Z<2 Setting
1.700 Ohm
Z<2 Time Delay 3.000 s
Z<2 tRESET
0s
Measured
DT
50.00mA
Page 6 of 13
Input
Measured
VN>1 Function DT
VN>1 Current
5V
VN>1 Time Delay 3.000 s-(CUSTOMER
RECOMMNADED 0.5s)
VN>1 tRESET
0s
VN>2 Status
Disabled
The pick up setting may be kept to 5 volts so as to provide
maximum coverage of the stator winding towards earth faults and if
the standing voltage level is higher than this, Voltage setting should
be increased accordingly.
11) 100% Stator Earth Fault Protection(64G2)
VN3H<: Enabled
VT Supervision: Enabled
VTS Status : Blocking
VTS Reset Time Delay :- 5 Sec
VTS I> Inhibit : 20 A -(CUSTOMER RECOMMNADED 5.0A)
VTS I2> Inhibit : 0.15 A -(CUSTOMER RECOMMNADED
0.25A)
CT Supervision : Disabled
Page 7 of 13
=
=
120 degrees
75 degrees
Page 8 of 13
450mA
80 Volts
5sec
500msec
4K
1.00
1k
5.00
Ohms
sec
Ohms
Sec
STAGE 2
R<,Alarm
Time delay
R<<,Trip
Time delay
4K
1.00
1k
5.00
Ohms
sec
Ohms
sec
Page 9 of 13
=
140MVA / 113
7348A
=
7348 x 5/8000
4.59 A
=
7348 x 5/8000
4.59 A
=
140MVA / 1383
585.73A
=
=
585.73 x 1/800
0.732 A
Page 10 of 13
=
3.29
=
=
5 / 4.59
1.08
=
1.08
5 / 3.29
1.519
0.732x 2.6 x 3
5 / 4.59
Vector correction :
Yy0
Yy0
Yy0
CTR 8000/5
CTR 8000/5
CTR 800/1
= 33.3 Ohms
Referred to sec
= 585.73 / 800/1
= 0.732 A
Page 11 of 13
=
15MVA / 6.83
1273.6A
=
=
1273.6 x 5/1500
4.24 A
=
15MVA / 113
787.3A
=
=
787.3 x 5/1000
3.9365 A
=
5 / 4.24
1.179
=
=
1.27
Vector correction :
Yy0
Yy0
CTR 1000/5
CTR 1500/5
=
15MVA
=
1000/5A
=
11KV
= 15 x 106 / 3 x 11 x 103
= 787.3 A
Referred to sec
= 787.3 / 1000/5
= 3.93 A
Page 12 of 13
5 / 3.93
Page 13 of 13