set this up? ArticleID: Q5591 Created: 28/10/2009 Last Updated: 31/10/2009 Suggested By: Michel Latumaelissa
Applies To: CitectSCADA Summary: I would like to use the MELSECQ driver to talk to a Mitsubishi Q03UDECPU PLCs is this possible and how do I set this up? Solution: It is possible to use the MELSECQ driver since the QnUDE(H) uses the QnA compatible 3E frame. Follow the below screenshots as a reference for configuring this driver. *Note: Make sure that the value of 255 is specified in the "Address" field of the IODevice.
Page 1 of 2 Q5591 Is it possible to use the MELSECQ driver to talk to a Mitsubishi Q03UDECPU PL... 10/28/2014 mk:@MSITStore:C:\d%20drive\Help%20Files\CitectSCADA%20KB%202013-05-28.ch... Schneider Electric (Australia) Pty Ltd Disclaimer Related Links Attachments
The port no in Citect is entered in a decimal format and in hexadecimal in the PLC. Keywords: MELSECQ, Mitsubishi, Q03UDECPU