Clearance Requirement Cisco 9006

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

1-28

Cisco ASR 9000 Series Aggregation Services Router Hardware Installation Guide
OL-17499-12
Chapter 1 Preparing for Installation
Site Requirement Guidelines
Cisco ASR 9006 Clearance Requirements
To install a Cisco ASR 9006 Router in a 4-post enclosed cabinet:
The front and rear doors of the cabinet must be removed or be perforated with a minimum open area
of 70 percent. In addition, the right side panel must be removed or perforated with a minimum of 65
percent open area (70 percent for ETSI 800-mm racks).
There must be a minimum unobstructed space of 6 inches (15.24 cm) between the routers right side
air inlet and the adjacent wall or cabinet side panel, and a minimum unobstructed space of 6 inches
(15.24 cm) between adjacent cabinets. In addition, there should be no exhaust from any source
blowing into the right side panel of the cabinet.
Rear chassis clearance: Minimum of 2.50 inches (6.40 cm) of clearance.
Sides chassis clearance: Minimum of 6 inches (15.24 cm) of clearance on the right side of the
chassis (as viewed from the front). There is no clearance requirement for the left side of the
chassis.
Figure 1-24 shows the side and rear chassis air-flow clearance requirements for mounting the Cisco ASR
9006 Router in a 4-post enclosed rack.

1-29
Cisco ASR 9000 Series Aggregation Services Router Hardware Installation Guide
OL-17499-12
Chapter 1 Preparing for Installation
Site Requirement Guidelines
Figure 1-24 Cisco ASR 9006 Router Clearance Requirements for an Enclosed 4-Post Rack
Installation
2
4
5
6
3
0
Rear of chassis
Front of chassis
ASR 9006
No minimum clearance
requirement for left
side of chassis.
5.73 in
(14.55 cm)
Rack
mounting
surface
2.50 in
(6.40 cm)
6.00 in
(15.20 cm)