Professional Documents
Culture Documents
UNITEN ARSEPE 07 L7 Non-Dir Overcurrent - MRO - Short
UNITEN ARSEPE 07 L7 Non-Dir Overcurrent - MRO - Short
UNITEN ARSEPE 07 L7 Non-Dir Overcurrent - MRO - Short
Non-Directional
Overcurrent & Earth
Fault Protection
F1
F2
F3
Fuses
Total
Operating
Time
Fuse B
Tripping Methods
51
Trip Coil
IF
X AC series trip
common for electromechanical O/C relays
IF '
+
51
-
Sensitive
Trip
Coil
IF
51
DC
BATTERY
SHUNT
TRIP COIL
Overcurrent Protection
X Operating Speed
Instantaneous
Time delayed
X Discrimination
Current setting
Time setting
Current and time
X Cost
Generally cheapest form of protection relay
50
IF2
50
IF1
TOP
IS
(Relay Current Setting)
Applied Current
51
51
0.9 sec
0.5 sec
IS
(Relay Current Setting)
Applied Current
I>1
I>2
Time
I>3
I>4
Current
Co-ordination
R2
R1
IF1
T
IS2 IS1
Maximum
Fault
Level
10
E
D
C
B
0.1
0.01
Current (A)
FLB
FLC
FLD
t =
0.14
(I0.02 -1)
X VI t = 13.5
(I2 -1)
X EI t =
80
(I2 -1)
X LTI t = 120
(I - 1)
100
Operating Time (s)
X SI
10
LTI
SI
1
VI
EI
0.1
1
10
100
100
10
0.1
1
100
10
Current (Multiples of Is)
R1
R2
IF1
R1
R2
X Traditional
breaker op time
relay overshoot
allow. For errors
safety margin
Total
X Calculate using formula
0.1
0.05
0.15
0.1
0.4s
Tf
Tr
I FMAX
X 1.175Tr
Allowance for CT
and relay error
or
X Tf = 2Tr + 0.33s
0.1 +
CB
0.1
Safety margin
0.6Tf
Allowance for fuse
error (fast)
100
10
0.1
1
100
10
Current (Multiples of Is)
Overcurrent Protection
Time Multiplier Setting - Calculation
200/5
100/5
I
FMAX
= 1400 Amp
B
Is = 5 Amp
A
Is = 5 Amp; TMS = 0.05, SI
200/5
100/5
I
FMAX
= 1400 Amp
B
Is = 5 Amp
A
Is = 5 Amp; TMS = 0.05, SI
B
Is = 5 Amp
100/5
I FMAX
= 1400 Amp
Overcurrent Protection
LV Protection Co-ordination
11kV
MCGG
CB
350MVA
2 x 1.5MVA
11kV/433V
5.1%
CTZ61
ACB
CTZ61
(Open)
ACB
1
1
2
3
4
F
Relay 1
Relay 2
Relay 3
Relay 4
Fuse
MCCB
27MVA
Fuse
Load
K
20MVA
Overcurrent Protection
LV Protection Co-ordination
1000S
100S
TX damage
10S
Very
inverse
1.0S
0.1S
0.01S
0. 1kA
10kA
1000kA
Overcurrent Protection
LV Protection Co-ordination
11kV
KCGG 142
CB
350MVA
2 x 1.5MVA
11kV/433V
5.1%
KCEG 142
ACB
(Open)
ACB
1
1
2
3
4
F
Relay 1
Relay 2
Relay 3
Relay 4
Fuse
MCCB
27MVA
Fuse
Load
K
20MVA
Overcurrent Protection
LV Protection Co-ordination
1000S
Long time
inverse
100S
TX damage
10S
1.0S
0.1S
0.01S
0. 1kA
10kA
1000kA
Overcurrent Protection
Blocked OC Schemes
Graded
protection
R3
R2
IF2
R1
Block t >
I > Start
IF1
M
(Transient backfeed ?)
Blocked
protection
Delta/Star Transformers
Overcurrent Protection
Transformer Protection - 2-1-1 Fault Current
X A phase-phase fault on
one side of transformer
produces 2-1-1
distribution on other
side
X Use an overcurrent
element in each phase
(cover the 2x phase)
X 2 & EF relays can be
used provided fault
current > 4x setting
Turns Ratio
= 3 :1
Iline
Idelta
0.866 If3
Overcurrent Protection
Transformer Protection - 2-1-1 Fault Current
Turns Ratio
= 3 :1
Iline
Idelta
0.866 If3
X Iline = If3
Overcurrent Protection
Transformer Protection - 2-1-1 Fault Current
51
51
HV
LV
X Grade HV relay
with respect to 21-1 for - fault
X Not only at max
fault level
86.6%If3
If3
Overcurrent Protection
Instantaneous Protection
X Fast clearance of faults
ensure good operation factor, If >> Is (5 x ?)
X Current setting must be co-ordinated to prevent
overtripping
X Used to provide fast tripping on HV side of
transformers
X Used on feeders with Auto Reclose, prevents
transient faults becoming permanent
AR ensures healthy feeders are re-energised
X Consider operation due to DC offset - transient
overreach
Overcurrent Protection
Instantaneous OC on Transformer Feeders
HV2
HV1
LV
TIME
HV2
HV1
LV
IF(LV)
IF(HV)
1.3IF(LV)
CURRENT
Earthfault Protection
Overcurrent Protection
Earth Fault Protection
Overcurrent Protection
Earth Fault Relay Connection - 3 Wire System
E/F
OC
OC
OC
E/F
OC
OC
X Economise using 2x OC
relays
Overcurrent Protection
Earth Fault Relay Connection - 4 Wire System
E/F
OC
OC
OC
E/F
OC
OC
OC
X Independent of neutral
current but must use 3
OC relays for phase to
neutral faults
Overcurrent Protection
Earth Fault Relays Current Setting
X Solid earth
30% Ifull load
adequate
X Resistance earth
setting w.r.t earth fault
level
special considerations
for impedance
earthing - directional?
Overcurrent Protection
Sensitive Earth Fault Relays
A
B
C
X Settings down to
0.2% possible
E/F
X Isolated/high
impedance earth networks
X For low settings cannot use residual connection, use
dedicated CT
X Advisable to use core balance CT
X CT ratio related to earth fault current not line current
X Relays tuned to system frequency to reject 3rd
harmonic
Overcurrent Protection
Core Balance CT Connections
OPERATION
NO OPERATION
CABLE GLAND
CABLE
BOX
E/F
CABLE GLAND/SHEATH
EARTH CONNECTION